DMP Electronics Home Security System LT 0229 5 97 User Manual

XR10/XR20 Command Processor Panels  
Installation Guide  
10/26 Zone Burglary/Fire/Access Control Panels with Built-in Communicator  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
LT-0229 (5/97)  
Downloaded from: http://www.guardianalarms.net  
 
TABLE OF CONTENTS  
Section  
Panel Specifications  
Power supply........................................................................................ 1.1  
Communication .................................................................................... 1.2  
Panel zones ......................................................................................... 1.3  
Keypads ............................................................................................... 1.4  
Outputs................................................................................................. 1.5  
Enclosure specifications....................................................................... 1.6  
Introduction  
Description ........................................................................................... 2.1  
System configurations .......................................................................... 2.2  
Before you begin .................................................................................. 2.3  
About this guide ................................................................................... 2.4  
How to use this guide ........................................................................... 2.5  
System Components  
Description ........................................................................................... 3.1  
Wiring diagram ..................................................................................... 3.2  
Lightning protection .............................................................................. 3.3  
Security Command keypads ................................................................ 3.4  
Installation  
Mounting the enclosure ........................................................................ 4.1  
Mounting keypads ................................................................................ 4.2  
Wiring Keypads .................................................................................... 4.3  
Primary Power Supply  
AC terminals 1 and 2............................................................................ 5.1  
Transformer types ................................................................................ 5.2  
Secondary Power Supply  
Battery terminals 3 and 4 ..................................................................... 6.1  
Earth ground ........................................................................................ 6.2  
Replacement period ............................................................................. 6.3  
Discharge/recharge .............................................................................. 6.4  
Battery supervision............................................................................... 6.5  
XR10/XR20 power requirements ......................................................... 6.6  
Bell Output  
Terminals 5 and 6 ................................................................................ 7.1  
Keypad Data Bus  
Description ........................................................................................... 8.1  
Terminal 7 - RED ............................................................................... 8.2  
Terminal 8 - YELLOW ........................................................................ 8.3  
Terminal 9 - GREEN .......................................................................... 8.4  
Terminal 10 - BLACK ........................................................................... 8.5  
Smoke and Glassbreak Detector Output  
Terminal 11 .......................................................................................... 9.1  
Burglary Zones  
Description ......................................................................................... 10.1  
Operational parameters ..................................................................... 10.2  
Zone response time ........................................................................... 10.3  
Keyswitch arming zone ...................................................................... 10.4  
Powered Zone for 2-Wire Smoke Detectors  
Terminals 25 and 26 .......................................................................... 11.1  
Annunciator Outputs  
Description ......................................................................................... 12.1  
Harness wiring ................................................................................... 12.2  
Telephone RJ Connector  
Description ......................................................................................... 13.1  
FCC registration ................................................................................. 13.2  
Notification ......................................................................................... 13.3  
Ground start ....................................................................................... 13.4  
 
TABLE OF CONTENTS  
Section  
Reset Jumpers J16  
Description ......................................................................................... 14.1  
Universal UL Burglary Specifications  
Introduction ........................................................................................ 15.1  
Wiring ................................................................................................. 15.2  
Police station phone numbers ............................................................ 15.3  
Bypass reports ................................................................................... 15.4  
System maintenance.......................................................................... 15.5  
Cross Zoning ...................................................................................... 15.6  
Ground Start....................................................................................... 15.7  
UL 1023 Specifications  
Bell cutoff ........................................................................................... 16.1  
Entry delay ......................................................................................... 16.2  
Exit delay............................................................................................ 16.3  
Zone expansion on 4-wire bus ........................................................... 16.4  
UL 1610 and 1076 Specifications  
Opening/Closing reports .................................................................... 17.1  
Automatic bell test .............................................................................. 17.2  
Proprietary dialer ................................................................................ 17.3  
UL 1635 Specifications  
Digital dialer telephone number ......................................................... 18.1  
Entry delay ......................................................................................... 18.2  
Exit delay............................................................................................ 18.3  
Test frequency ................................................................................... 18.4  
Automatic bell test .............................................................................. 18.5  
Grade B Central Station ..................................................................... 18.6  
UL 365 and 609 Specifications  
Entry delay ......................................................................................... 19.1  
Grade A bell ....................................................................................... 19.2  
Bell cutoff ........................................................................................... 19.3  
Automatic bell test .............................................................................. 19.4  
Grade A Mercantile ............................................................................ 19.5  
Mercantile Safe and Vault .................................................................. 19.6  
Line security for Police Connect......................................................... 19.7  
Universal UL and NFPA Fire Alarm Specifications  
Introduction ........................................................................................ 20.1  
Wiring ................................................................................................. 20.2  
Police station phone number.............................................................. 20.3  
System maintenance.......................................................................... 20.4  
Audible alarm ..................................................................................... 20.5  
Fire zone programming ...................................................................... 20.6  
Ground Start....................................................................................... 20.7  
UL 985 NFPA 72 (chapter 2) Specifications  
Bell output definition ........................................................................... 21.1  
California State Fire Marshal Specifications  
Bell output definition ........................................................................... 22.1  
Troubleshooting Section  
Description ......................................................................................... 23.1  
 
Introduction  
Panel Specifications  
1.1 Power supply  
Transformer Input: 16.5 VAC 40VA (Models 320 wire-in or 321 plug-in)  
Standby Battery: 12 VDC 6.5Ah (40VA transformer charges up to 2 batteries)  
Auxiliary Output: 12 VDC at 500mA  
Bell Output: 12 VDC at 1.5 Amps  
Smoke Detector Output: 12 VDC at 100mA  
All circuits inherent power limited  
1.2 Communication  
Built-in SDLC Digital Dialer communication to DMP Model SCS-1 Receivers  
Built-in 4-2 communication to non-DMP receivers.  
Built-in M2E (Radionics Modem IIe) communication to non-DMP receivers (XR20 only).  
Either panel can operate as a local system  
1.3 Panel zones  
Nine 1k EOL burglary zones (zones 1 to 9)  
One 3.3k EOL Class B powered fire zone with reset capability (zone 10)  
1.4 Keypads  
You can connect up to four of the following supervised keypads to the XR10/XR20 panels.  
• 16 or 32 character alphanumeric keypads  
• 10-zone LED keypads  
In addition, the following zone expanders can be added to the XR20 panel:  
• Four and single point zone expanders  
• Single point PIR and glassbreak detectors  
When using the FA426 Wireless Receiver, the XR20 allows unsupervised devices to be added to address five.  
1.5 Outputs  
The XR10/XR20 panels provide four open collector outputs rated for 50mA each. See section 12.1. A Model 300  
Wire Harness is required. Open collectors don't provide voltage but instead ground a positive voltage source.  
1.6 Enclosure specifications  
The XR10/XR20 ship in an enclosure with EOL resistors, battery leads, user's guide, and programming sheet.  
Size:  
12.5" W x 9.5" H x 2.75" D  
4 lbs  
Weight:  
Color:  
Gray or Black  
Construction:  
20 gauge cold rolled steel  
Introduction  
2.1 Description  
The DMP XR10/XR20 Command Processors are powerful 12 VDC burglary and fire communicator panels with  
battery backup. The XR10/XR20 provide nine on-board burglary zones and one on-board 12 VDC Class B  
powered fire zone. The fire zone has a reset capability to provide for 2-wire smoke detectors, relays, or other  
latching devices. The XR10/XR20 can communicate to one or two DMP SCS-1 Receivers using SDLC digital  
dialer or 4-2 reporting formats. In addition, the XR20 can communicate using the Radionics Modem IIe format.  
2.2 System configurations  
The XR10/XR20 can be programmed to operate as either an All/Perimeter system that provides one Perimeter  
area and one Interior area, or as a Home/Sleep/Away system that provides one Perimeter, one Interior, and one  
Bedrooms area. The Bedrooms area can include any protection devices the user wants disarmed during their  
sleeping hours and armed in the Away mode. In addition, the XR20 can operate as a four area system.  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 1  
 
Introduction  
2.3 Before you begin  
Before installing the XR10/XR20, we recommend you read through the entire contents of this guide. Familiarize  
yourself with the features of the panel and the key points to remember during the installation. Be sure to read  
and understand all of the caution statements printed in bold italics.  
In addition to this installation guide, you should also read through and familiarize yourself with these other  
product documents:  
• XR10 Programming Guide (LT-0230)  
• XR20 Programming Guide (LT-0305)  
• XR10 Security Command User's Guide (LT-0226)  
• XR20 Security Command User's Guide (LT-0303)  
• XR10 Program Information Sheet (LT-0212)  
• XR20 Program Information Sheet (LT-0302)  
2.4 About this guide  
The information contained in this guide is organized into three sections: Table of Contents, Introduction, and  
Installation.  
• The Table of Contents at the front of this guide lists all of the headings and subheadings used throughout  
each section. To the right of each heading is the section number where the information can be found.  
• The Introduction section gives you an overview of the various components that go into a XR10/XR20  
system and diagrams some typical system configurations. This section gives descriptions of the panel,  
keypads, and accessory modules and provides details on how each of them operate together in the  
system.  
• The Installation section begins with mounting instructions for the enclosure and takes you through the  
proper way to power up the panel prior to programming.  
Caution notes  
Throughout this guide you'll see caution notes containing information you need to know when installing the  
XR10/XR20 panel. These cautions are written with a bold, italicized introductory clause followed by a detailed  
description of the caution. See the example shown below:  
Always ground the panel before applying power to any devices: The XR10/XR20 must be properly  
grounded before connecting any devices or applying power to the panel. Proper grounding protects against  
Electrostatic Discharge (ESD) that can damage system components.  
Whenever you see a caution note, make sure you completely read and understand its information. Failing to  
follow the caution note can cause damage to the equipment or improper operation of one or more components in  
the system.  
2.5 How to use this guide  
To locate information about the installation of the XR10/XR20, first go to the Table of Contents at the front of this  
guide. Find the subject heading that closely describes the information you need and turn to the section number  
shown to the right of the heading.  
The text that follows the heading has been written to provide as much information about the subject as possible.  
If you can't find the information you need under that heading, try scanning through a few of the headings before  
and after and reading the text under those that sound similar.  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 2  
 
Introduction  
System Components  
3.1 Description  
The DMP XR10/XR20 system is made up of an alarm panel with built in communicator, an enclosure, a 16.5 VAC  
transformer, and a 12 VDC 6.5 Ah battery. You can add up to four Security Command keypads to the system and  
can also connect auxiliary devices to the panel's open collector outputs to expand the basic system. Combined  
current requirements of additional modules may require an auxiliary power supply. Refer to section 6.6 in this guide  
when calculating power requirements. In addition, up to 16 points of zone expansion can be added to the XR20.  
3.2 Wiring diagram  
The XR10/XR20 system below shows some of the accessory devices you can connect for use in various  
applications. A complete description of each module follows. Zone expanders can be added to the XR20.  
J11  
J16  
Output Header J11  
1
2
3
4
All outputs must be connected  
to devices located within the  
same room as the control panel.  
Command Processor Reset  
Use DMP Model 300 Harness.  
AC wiring must be in  
conduit and exit out the left  
side of the panel enclosure.  
J4  
Wiring on terminals 5 through 17 must exit  
to the right and maintain a 1/4" separation  
from the AC and battery positive wiring.  
Front Tamper  
Phone Jack Connector  
U11  
DMP transformers:  
Model 320  
Plug into  
120 VAC  
outlet not  
controlled  
by switch.  
16.5 VAC 40VA  
wire-in  
Rear Tamper  
Model 321  
16.5 VAC 40VA  
plug-in  
Tamper protection  
when required for  
Model 349A Attack  
Resistant Enclosure.  
1
2
3
4
5
6
7
8
9
10  
11  
12  
15  
16  
17  
18  
19  
20  
22  
23  
24  
25  
26  
13  
14  
21  
AC  
AC  
+B  
-B BELL GND RED YEL GRN BLK  
Z1 GND  
Z3  
GND  
Z10+ Z10-  
SMK  
Z2  
GND  
Z4  
Z5  
Z6  
Z 7 GND Z 8 Z 9  
Secondary Power Supply  
1.2 Amps max. charging current.  
Use only 12 VDC rechargable  
batteries. DMP Model 367.  
Replace every 3 to 5 years.  
16 to 18 gauge wire  
Zone 10 compatibility  
identifier: A  
MaximumACwiredistance  
With16gaugewire:70feet  
With18guagewire:40feet  
Maximumoperating  
range:  
8.8VDCto14.2VDC.  
2-wire  
smoke  
detector  
1k  
1k Ω  
1k 1k Ω  
1k 1k Ω  
1k 1k Ω  
Cold Water Pipe  
Earth Ground  
Smoke Output  
1k Ω  
100mA at 10.4 to 13.2 VDC  
Terminal 11  
Seesection11.1intheXR20  
InstallationGuide(LT-0229)foralist  
ofapproved2-wiresmokedetectors.  
Bell  
10.4 to 13.2 VDC  
Red  
Total current 1.5 Amps max.  
Black  
Bell  
4-wire smoke detector  
Heatdetectors, manualpullstations,  
oranyothershortingdevice.  
Unlimitednumberofunits.  
Household System  
An alarm sounding device  
must be installed indoors  
so that it is clearly heard  
in all sleeping areas.  
Smoke  
Power  
Detector  
Supervision  
Relay  
Up to 500mA auxiliary  
current at 10.4 to 13.2 VDC  
from Terminal 7.  
+ –  
Keypads  
Models 670, 770, and  
771  
3.3k Ω  
DMP Model 309  
100mA at 8 to 16 VDC  
125mA with display lit.  
Model 692  
75mA at 8 to 16 VDC.  
Up to four keypads can  
be connected to the  
XR10/XR20.  
ZONE EXPANDER  
Model 714  
15mA at 12 VDC  
ZONE EXPANDER  
Model 715  
15mA at 12 VDC  
XR20 only  
Figure 1: XR10/XR20 wiring diagram  
3.3 Lightning protection  
Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on input and  
output circuits of the XR10. Additional surge protection is available by installing the DMP 370 or 370RJ Lightning  
Suppressors.  
3.4 Security Command® keypads  
You can connect any combination of up to four Model 670, 770, and 771 vacuum fluorescent, 690, 693, 790,  
791, and 793 LCD, or 692 LED Security Command Keypads to the 4-wire keypad data bus provided by the  
panel on terminals 7, 8, 9, and 10. (Note: The XR10 does not support zone expansion on the keypad bus.)  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 3  
 
Installation  
Installation  
4.1 Mounting the enclosure  
The metal enclosure for the XR10/XR20 must be mounted in a secure, dry place to protect the panel from  
damage due to tampering or the elements. It is not necessary to remove the XR10/XR20 PC board when  
installing the enclosure.  
Dual 1/2" and 3/4" Conduit Knockouts  
J11  
J16  
1
2
3
4
Reset Jumper  
J4  
Phone Jack Connector  
U11  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
Z
24  
25  
26  
AC  
AC  
+B  
-B BELL GND RED YEL GRN BLK SMK  
Z1 GND  
Z2  
Z3 GND  
Z4  
Z5 GND Z6  
Z
7
GND  
8
Z10+ Z10-  
Z
9
Enclosure Mounting Holes  
Dual 1/2" and 3/4" Conduit Knockouts  
Figure 2: XR10/XR20 in standard enclosure  
Accessory Module  
Mounting Holes  
Accessory Module  
Mounting Holes  
Dual 1/2" and 3/4" Conduit Knockouts  
Tamper Switch  
Mounting Holes  
Enclosure Mounting Holes  
J11  
J16  
1
2
3
4
Reset Jumper  
J4  
Phone Jack Connector  
U11  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
Z
24  
25  
26  
AC  
AC  
+B  
-B BELL GND RED YEL GRN BLK SMK  
Z1 GND  
Z2  
Z3 GND  
Z4  
Z5 GND Z6  
Z
7
GND  
8
Z
9
Z10+ Z10-  
Wire Access  
Openings  
Enclosure Mounting Holes  
Battery Shelf  
Dual 1/2" and 3/4" Conduit Knockouts  
Figure 2A: XR10/XR20 in optional 349 Enclosure  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 4  
 
Installation  
4.2 Mounting keypads  
Security Command keypads have removable covers that allow you to easily mount the base with keypad circuit  
board to a wall or other flat surface using the screw holes provided on each corner. Before mounting the base,  
connect the keypad wire harness leads to the 4-wire keypad data bus cable from the panel. Next, attach the  
keypad wire harness connector to the pin connector on the keypad circuit board, mount the base, and install the  
keypad cover making sure all of the keys extend through their respective holes.  
For mounting keypads on solid walls, or for applications where conduit is required, use a DMP 775, 776, or 778  
keypad conduit backbox.  
4.3 Wiring keypads  
Keypad data bus  
The keypad data bus consists of a 4-wire cable that provides 12 VDC power, data in, data out, and a panel  
common. You can connect keypads in parallel on one 4-wire cable or provide a separate cable run back to the  
panel for each keypad. The maximum cable length for one keypad can be up to 500 feet using 22 gauge wire or  
up to 1000 feet using 18 gauge wire. Additional keypads installed on the same cable decrease the maximum  
distance at which they'll operate properly.  
Refer to the wiring diagram in this guide for additional wiring information. See section 3.2.  
Primary Power Supply  
5.1 AC terminals 1 and 2  
Connect the transformer wires to terminals 1 and 2 on the panel. Use no more than 70 ft. of 16 gauge, or 40 ft. of  
18 gauge, wire between the transformer and the XR10/XR20.  
Always ground the panel before applying power to any devices: The XR10/XR20 must be properly  
grounded before connecting any devices or applying power to the panel. Proper grounding protects against  
Electrostatic Discharge (ESD) that can damage system components. See Earth ground, section 6.2.  
5.2 Transformer types  
The standard transformer for the XR10/XR20 is 16.5 VAC 40VA, which provides up to 500mA of auxiliary current  
and 100mA of smoke detector output. You can use either the Model 320 wire-in or 321 plug-in transformer with  
the XR10/XR20. The total current available is limited by the total battery standby requirements of the installation.  
The transformer must be connected to a 120 VAC 60 Hz commercial power outlet that is not controlled by a wall  
switch. Never share the transformer output with any other equipment.  
Secondary Power Supply  
6.1 Battery terminals 3 and 4  
Connect the black battery lead to terminal 4 on the panel and to the negative terminal of the battery. The  
negative terminal connects to the enclosure ground internally through the XR10/XR20 circuit board. Connect the  
red battery lead to terminal 3 on the panel and to the positive terminal of the battery. Observe polarity when  
connecting the battery. The XR10 and XR20 panels can charge up to two batteries.  
Use sealed lead-acid batteries only: Use the DMP Model 367, 12 VDC 6.5Ah sealed lead-acid rechargeable  
battery. Batteries supplied by DMP or manufactured by Eagle Picher or Yuasa have been tested to ensure  
proper charging with DMP products.  
GEL CELL BATTERIES CANNOT BE USED WITH THE XR10/XR20 PANEL.  
6.2 Earth ground  
Terminal 4 of the XR10/XR20 panel must be connected to earth ground using 14 gauge or larger wire to provide  
proper transient suppression. DMP recommends connecting to a metal cold water pipe or ground rod only. Do  
not connect to electrical conduit or a telephone company ground.  
6.3 Replacement period  
DMP recommends the battery be replaced every 3 to 5 years under normal use.  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 5  
 
Installation  
6.4 Discharge/recharge  
The XR10/XR20 battery charging circuit float charges at 13.9 VDC at a maximum current of 1.2 Amps using a  
40VA transformer. The total current available is reduced by the combined auxiliary current draw from terminals  
7, 11, and 25. The various battery voltage levels are listed below:  
Battery Trouble:  
Battery Restored:  
Below 11.9 VDC  
Above 12.6 VDC  
6.5 Battery supervision  
The XR10/XR20 tests the battery once every hour when AC power is present. The test lasts for five seconds. A  
load is placed on the battery and if its voltage falls below 11.9 VDC a low battery is detected. If AC power has  
failed, a low battery is detected any time the battery voltage falls below 11.9 VDC.  
If a low battery is detected with AC power present, the test is repeated every two minutes until the battery  
charges above 12.6 VDC; the battery restored voltage. If a faulty battery is replaced with a fully charged battery,  
the restored battery will not be detected until the next two minute test is done.  
6.6 XR10/XR20 power requirements  
During AC power failure, the XR10/XR20 panel and all auxiliary devices connected to the XR10/XR20 draw their  
power from the battery. All devices must be taken into consideration when calculating the battery standby  
capacity. Below is a list of the power requirements of the XR10/XR20 panel. Add the additional current draw of  
Security Command keypads, smoke detector output, and any other auxiliary devices used in the system for the  
total current required. The total is then multiplied by the total number of standby hours required to arrive at the  
total ampere/hours required.  
XR10/XR20 STANDBY BATTERY POWER CALCULATIONS  
Standby Current  
Alarm Current  
XR10/XR20 Command Processor Panel  
Active Zones 1-9  
50mA ______ mA  
Qty _____ x 1.6mA ______ mA Qty _____ x *2mA ______ mA  
4mA ______ mA 30mA ______ mA  
50mA ______ mA  
Active Zone 10  
2-Wire Smokes  
Qty _____ x  
.1mA ______ mA Qty _____ x .1mA ______ mA  
Bell Output  
1500mA max. ______ mA  
670, 770, and 771 Keypads  
Annunciator (ON)  
Qty _____ x 125mA ______ mA Qty _____ x 125mA ______ mA  
Qty _____ x 20mA ______ mA  
690, 693, 790, 791, and 793 Keypads  
Annunciator (ON)  
Qty _____ x 100mA ______ mA Qty _____ x 100mA ______ mA  
Qty _____ x 20mA ______ mA  
692 Keypads  
Qty _____ x  
30mA ______ mA Qty _____ x 30mA ______ mA  
Qty _____ x 10mA ______ mA  
Annunciator (ON)  
Auxiliary Powered Devices on  
Terminals 7 and 11  
______ mA  
______ mA  
(Other than keypads)  
Total Standby ___________ mA  
Total Alarm ____________ mA  
* Based on 10% of active zones  
in alarm condition  
Total Standby ____________ mA x number of standby hours needed ______ = ___________ mA/hours  
Total Alarm + ___________ mA/hours  
Total ___________ mA/hours  
x _.001_____  
= ___________ A/hours required  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 6  
 
Installation  
Bell Output  
7.1 Terminals 5 and 6  
Nominal 12 VDC is supplied by terminal 5 on the panel to power alarm bells or horns. The output is rated for a  
maximum output of 1.5 Amps. This output can be steady or pulsed depending upon the Bell Action specified in  
Output Options. Terminal 6 is the ground reference for the bell circuit.  
Keypad Data Bus  
8.1 Description  
Terminals 7, 8, 9, and 10 of the XR10/XR20 panel are designated as the keypad data bus. In addition to  
keypads, the XR20 allows the connection of any combination of zone expanders, 5845LX Glassbreak Detectors,  
6155LX PIRs, and DS775LX PIRs to the data bus up to the maximum of four devices.  
8.2 Terminal 7 - RED  
Nominal 12 VDC is supplied at terminal 7 to power Security Command keypads and zone expanders. This is  
also where power for any auxiliary device is supplied. The ground reference for terminal 7 is terminal 10. The  
maximum output is rated at 500mA. All auxiliary devices totalled together must not exceed the panel's maximum  
current rating of 500mA.  
8.3 Terminal 8 - YELLOW  
Data receive from keypads and zone expanders.  
8.4 Terminal 9 - GREEN  
Data transmit to keypads and zone expanders.  
8.5 Terminal 10 - BLACK  
Terminal 10 is the ground reference for Security Command keypads, zone expanders, and any auxiliary devices  
being powered by terminals 7 and 11.  
Smoke and Glassbreak Detector Output  
9.1 Terminal 11  
Nominal 12 VDC at 100mA maximum (shared by terminal 25) is supplied at terminal 11 to power 4-wire smoke  
detectors or other auxiliary powered devices. This output can be turned off by the user for 5 seconds using the  
Sensor Reset Menu Option. Terminal 10 is the ground reference for terminal 11.  
Burglary Zones  
10.1 Description  
Terminals 12 to 24 are the nine burglary zones. For programming purposes, the zone numbers are 1 to 9. The  
zone configurations on terminals 12 to 24 are described below.  
Terminal  
Function  
Terminal  
Function  
12  
13  
14  
15  
16  
17  
18  
Zone 1 voltage sensing  
Ground for zones 1 & 2  
Zone 2 voltage sensing  
Zone 3 voltage sensing  
Ground for zones 3 & 4  
Zone 4 voltage sensing  
Zone 5 voltage sensing  
19  
20  
21  
22  
23  
24  
Ground for zones 5 & 6  
Zone 6 voltage sensing  
Zone 7 voltage sensing  
Ground for zones 7, 8, & 9  
Zone 8 voltage sensing  
Zone 9 voltage sensing  
The voltage sensing terminal measures the voltage flowing through the 1k End Of Line resistor to the zone's  
ground terminal. Dry contact sensing devices can be used in series (normally-closed) or in parallel (normally-  
open) with any of the burglary protection zones.  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 7  
 
Installation  
10.2 Operational parameters  
Each burglary protection zone detects three conditions: open, normal, and short.  
The parameters for each are listed below:  
Condition  
Open  
Resistance on zone  
over 1300 ohms  
Voltage on right terminal  
over 2.0 VDC  
Normal  
Short  
600 to 1300 ohms  
under 600 ohms  
1.2 to 2.0 VDC  
under 1.2 VDC  
1K  
1K  
1K  
NORMALLY CLOSED CONTACTS  
NORMALLY OPEN CONTACTS  
COMBINATION: NORMALLY OPEN AND  
NORMALLY CLOSED CONTACTS  
Figure 3: Protection zone contact wiring  
10.3 Zone response time  
A condition must be present on a zone for 500 milliseconds before it's detected by the XR10/XR20 panel.  
Ensure detection devices used on the protection zones are rated for use with this delay.  
10.4 Keyswitch arming zone  
Momentary keyswitches  
You can use a momentary keyswitch on a zone programmed as an Arming type for use in arming and disarming  
the system without a code.  
How it works  
When the Arming zone is placed into a shorted codition from a normal condition, the panel disarms any areas  
that are armed. If all areas are disarmed, the panel arms all areas.  
If the Arming zone changes from normal to open while any area is armed, an alarm is indicated. If all areas are  
disarmed, only a trouble is indicated.  
Powered Zone for 2-Wire Smoke Detectors  
11.1 Terminals 25 and 26  
A resettable 2-wire Class B powered zone is provided on terminals 25 (positive) and 26 (negative) of the panel.  
For programming purposes, the zone number is 10. The zone uses a Model 309, 3.3k EOL resistor (provided  
with the panel) and has an operating range of 8.8 to 14.2 VDC.  
Power is dropped from zone 10 any  
Detector  
I D  
Base  
I D  
# of  
Detectors  
Manufacturer  
Model  
Base  
time a Sensor Reset is performed on  
the panel. Whenever non-Fire and  
non-Supervisory zone types are used  
on zone 10, make the appropriate  
adjustments to the zone's Armed  
Action to prevent false alarms from  
occurring.  
Detection Systems  
DS282  
B
B
None  
None  
N/A  
N/A  
A
10  
10  
10  
10  
10  
12  
7
Detection Systems DS282TH  
Detection Systems DS250  
B
MB2W  
Detection Systems DS250TH  
Detection Systems DS250HD  
B
MB2W, MB2WL  
MB2W, MB2WL  
None  
A
B
A
Sentrol/ESL  
DMP/Hochiki  
DMP/Hochiki  
Hochiki  
429AT  
SLK-835  
SLK-835H  
SLK-12  
S09A  
HD-5  
HD-5  
HD-4  
N/A  
HSB-200, HSB-200N HB-55  
HSB-200, HSB-200N HB-55  
HSB-12-1, HSB-12-1N HB-80  
The UL compatibility identifier is: A.  
7
20  
Figure 4: Compatible 2-wire smoke detectors  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 8  
 
Installation  
Annunciator Outputs  
12.1 Description  
The four annunciator outputs can be programmed to indicate the activity of the panel's zones or conditions  
occurring on the system. Annunciator outputs do not provide a voltage but instead switch to ground  
voltage from another source. The outputs can respond to any of the conditions listed below:  
1) Activation by zone condition: Steady, Pulse, Momentary, or Follower  
2) Manually from the Security Command keypad  
3) Communication failure  
4) Armed area annunciation  
5) Fire Alarm or Fire Trouble  
7) Ambush alarm  
8) Exit and Entry timers  
9) System Ready  
10) Ground start activation  
12.2 Harness wiring  
The open collector outputs are accessible by installing the DMP 300 Harness on the 4-pin header labeled J11.  
The output locations are shown below:  
Output  
Color  
Red  
Yellow  
Green  
Black  
Wire  
1
2
3
4
1
2
3
4
Devices connected to the outputs must be located within the same room as the XR10/XR20 panel.  
Telephone RJ Connector  
13.1 Description  
Connect the panel to the public telephone network by installing a DMP 356 RJ Cable between the panel's J4  
connector and the RJ31X or RJ38X phone jack.  
13.2 FCC registration  
The Model XR10/XR20 complies with FCC part 68 and is registered with the FCC.  
Registration number: CCKUSA - 18660 - AL - R  
Ringer Equivalence: 1.1B  
13.3 Notification  
Registered terminal equipment must not be repaired by the user. In case of trouble, the device must be  
immediately unplugged from the telephone jack. The factory warranty provides for repairs. Registered terminal  
equipment may not be used on party lines or in connection with coin telephones. Notification must be given to  
the telephone company of:  
a. The particular line(s) the service is connected to  
b. The FCC registration number  
c. The ringer equivalence  
d. The make, model, and serial number of the device  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 9  
 
Installation  
13.4 Ground start  
To configure the XR10/XR20 for ground start operation, you must install the appropriate ground start module and  
program one of the panel's available annunciator outputs for Ground Start operation. Refer to the XR10/XR20  
Programming Guide for complete programming information.  
Reset Jumpers J16  
14.1 Description  
There are two reset jumpers located at the top right of the panel's circuit board labeled RESET. Momentarily  
shorting these jumpers allows you to reset the microprocessor of the XR10/XR20. Resetting the panel allows  
you to enter the panel's internal Programmer.  
To reset the panel when first installing the system, place the blade of a slotted screwdriver across the two reset  
jumpers after applying power to the panel.  
To reset the panel while the system is operational (for example, prior to reprogramming), you can short the  
jumpers without powering down the system.  
After resetting the panel for programming, you must begin within 30 minutes. If you wait longer than 30 minutes,  
you'll have to reset the panel again.  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 10  
 
Installation  
UNIVERSAL UL BURGLARY SPECIFICATIONS  
15.1 Introduction  
The programming and installation specifications contained in this section must be completed when installing the  
XR10/XR20 panel in accordance with any of the UL burglary standards. Additional specifications may be  
required by a particular standard.  
15.2 Wiring  
All wiring must be in accordance with NEC, ANSI/NFPA 70, UL 681, and UL 611 for all burglary installations.  
15.3 Police station phone numbers  
The digital dialer telephone number programmed for communication must not be a police station phone number,  
unless that phone number is specifically provided for that purpose.  
15.4 Bypass reports  
The bypass reports option must be programmed as YES for all UL burglary applications. See section 5.5 of the  
XR10 Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
15.5 System maintenance  
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end  
user is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance  
program and acquainting the user with the correct procedure for use and testing of the system is also the  
responsibility of the installing alarm company.  
15.6 Cross zoning  
Zones used for cross zoning must be installed to allow detection of the same event. Cross zoning shall not  
conflict with UL 681 or 1641.  
15.7 Ground Start  
Ground Start phone lines must not be used for UL listed systems.  
15.8 UL Listed Receivers  
UL has verified operation with the DMP SCS-1 Security Receiver, Sur-Gard SG-HLR2-DG, FBII CP220PB,  
Osborne-Hoffman Quick-Alert and Radionics D6500 receivers.  
UL 1023 SPECIFICATIONS  
Household Burglar-Alarm System Units  
16.1 Bell cutoff  
The bell cutoff time cannot be less than five minutes. See section 7.2 of the XR10 Programming Guide (LT-0230)  
and XR20 Programming Guide (LT-0305).  
16.2 Entry delay  
The maximum entry delay used must not be more than 45 seconds. See section 6.4 of the XR10 Programming  
Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
16.3 Exit delay  
The maximum exit delay used must not be more than 60 seconds. See section 6.5 of the XR10 Programming  
Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
16.4 Zone expansion on 4-wire bus  
When expansion zones are used, the keypad and zone  
Normally Closed  
+
Voltage output  
expander 4-wire bus must be limited to three feet in length  
from terminal 11  
Normally Open  
unless an external communication fail indicator is added. A  
Zone activated  
annunciator output  
Common  
12 VDC relay may be wired as a communication fail  
indicator. To install, connect the negative side of the  
indicator to one of the panel's annunciator outputs and the  
positive side to the smoke power (terminal 11 of the XR10/  
XR20 panel). See section 7.5C of the XR10 Programming  
Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
+
Voltage output  
from terminal 11  
1k Ohm  
Device Fail LED  
Zone activated  
annunciator output  
In addition to the wiring described above, a 24 hour zone must be programmed to activate the appropriate  
annunciator output.  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 11  
 
Installation  
UL 1610 and 1076 SPECIFICATIONS  
Central-Station and Proprietary Burglar-Alarm Units  
17.1 Opening/Closing reports  
The Opening/Closing Reports option must be programmed as YES. See section 5.2 of the XR10 Programming  
Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
17.2 Automatic bell test  
This option must be programmed as YES. See section 7.3 of the XR10 Programming Guide (LT-0230) and XR20  
Programming Guide (LT-0305).  
17.3 Proprietary dialer  
The Model XR10/XR20 provides Grade A proprietary service when configured as a digital dialer.  
UL 1635 SPECIFICATIONS  
Digital Burglar Alarm Communicator System Units  
18.1 Digital Dialer telephone number  
Both programmed telephone numbers must begin with a D or P. See sections 3.17 and 3.18 of the XR10  
Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
18.2 Entry delay  
The maximum entry delay used must not be more than 60 seconds. See section 6.4 of the XR10 Programming  
Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
18.3 Exit delay  
The maximum exit delay used must not be more than 60 seconds. See section 6.5 of the XR10 Programming  
Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
18.4 Test frequency  
The Test Frequency option must be programmed so that the XR10 sends a report once every 24 hours. See  
section 3.6 of the XR10 Programming Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
18.5 Automatic bell test  
This option must be programmed as YES. See section 7.3 of the XR10 Programming Guide (LT-0230) and XR20  
Programming Guide (LT-0305).  
18.6 Grade B Central Station  
Grade B Central Station service can be provided under UL 1635 by adding a Grade A local audible signal  
appliance and placing the Model XR10/XR20 panel into the Model 349A Grade A Attack Resistant Housing.  
UL 365 and 609 SPECIFICATIONS  
Police Station Connected and Local Burglar Alarm Units and Systems  
19.1 Entry delay  
The maximum entry delay used must not be more than 60 seconds when using the Model 349A Grade A  
housing. See section 6.4 of the XR10 Programing Guide (LT-0230) and XR20 Programming Guide (LT-0305).  
19.2 Grade A bell  
A Grade A local audible signal appliance must be used.  
19.3 Bell cutoff  
The bell cutoff time cannot be less than 15 minutes. See section 7.2 of the XR10 Programming Guide (LT-0230)  
and XR20 Programming Guide (LT-0305).  
19.4 Automatic bell test  
The Automatic Bell Test option must be programmed as YES. See section 7.3 of the XR10 Programming Guide  
(LT-0230) and XR20 Programming Guide (LT-0305).  
19.5 Grade A Mercantile  
For Grade A Mercantile and Police Station Connect operation the Model XR10/XR20 must be mounted in a  
Grade A attack resistant housing, (DMP Model 349A).  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 12  
 
Installation  
19.6 Mercantile Safe and Vault  
When the DMP Model 349A housing is used, the XR10/XR20 provides operation as a mercantile safe and vault  
alarm. Bell Supervision and wiring must be in accordance with UL 681. If the Model XR10/XR20 is mounted  
outside the safe or vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration detectors  
should be used. The XR10/XR20 does not provide operation as a Bank Safe and vault alarm.  
19.7 Line security for Police Connect  
Basic line security is provided when the Model XR10/XR20 is configured as a dialer system.  
UNIVERSAL UL and NFPA FIRE ALARM SPECIFICATIONS  
20.1 Introduction  
The programming and installation specifications contained in this section must be completed when installing the  
Model XR10/XR20 in accordance with any of the UL or NFPA fire standards. Additional specifications may be  
required by a particular standard.  
20.2 Wiring  
All wiring must be in accordance with NEC, ANSI/NFPA 70.  
20.3 Police station phone number  
The digital dialer telephone number programmed for communication must not be a police station phone number,  
unless that phone number is specifically provided for that purpose.  
20.4 System maintenance  
Proper installation and regular maintenance by the installing alarm company and frequent testing by the end user  
is essential to ensure continuous satisfactory operation of any alarm system. Offering a maintenance program  
and acquainting the user with the correct procedure for use and testing of the system is also the responsibility of  
the installing alarm company.  
20.5 Audible alarm  
Fire Type zones should be programmed to activate an audible alarm. The Bell Action for Fire Type zones should  
not be programmed as “N”. See section 7.4A in the XR10 Programming Guide (LT-0230) and XR20  
Programming Guide (LT-0305).  
20.6 Fire zone programming  
Fire zones must be programmed to activate a trouble on open conditions and an alarm on short conditions. The  
swinger bypass function must not be used on any fire zones. See section 8.8 in the XR10 Programming Guide  
(LT-0230) and XR20 Programming Guide (LT-0305).  
20.7 Ground Start  
Ground Start phone lines must not be used for UL listed systems.  
20.8 UL Listed Receivers  
UL has verified operation with the DMP SCS-1 Security Receiver, Sur-Gard SG-HLR2-DG, FBII CP220PB,  
Osborne-Hoffman Quick-Alert and Radionics D6500 receivers.  
UL 985 NFPA 72 (chapter 2) SPECIFICATIONS  
Household Fire Warning System Units  
21.1 Bell output definition  
The bell output of the Model XR10/XR20 must be programmed to operate steady on burglary alarms and pulsed  
on fire alarms. See sections 7.4A and 7.4B of the XR10 Programming Guide (LT-0230) and XR20 Programming  
Guide (LT-0305).  
XR10/XR20 Installation Guide  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
Page 13  
 
Troubleshooting  
CALIFORNIA STATE FIRE MARSHAL SPECIFICATIONS  
22.1 Bell output definition  
The bell output of the Model XR10/XR20 must be programmed to operate steady on burglary alarms and pulsed  
on fire alarms. See sections 7.4A and 7.4B of the XR10 Programming Guide (LT-0230) and XR20 Programming  
Guide (LT-0305).  
Troubleshooting Section  
23.1 Description  
This section of the XR10/XR20 Installation Guide provides troubleshooting information for use when installing or  
servicing an XR10/XR20 system.  
Problem  
Possible Cause  
Solution  
Remove the J16 reset jumper.  
J16 reset jumper is installed.  
Check for broken or shorted wires  
between the keypad and panel.  
Open or short on the green data  
wire to the keypad.  
Security Command keypads  
display " SERVICE REQUIRED"  
Replace with a new or repaired  
keypad or zone expander.  
Bad keypad or zone expander.  
Open or short condition on the  
yellow data wire.  
Check for broken or shorted  
wires.  
Keypad display is not functional.  
When a key is pressed, only a  
short beep is emitted.  
Bad keypad or zone expander.  
Replace with a new or repaired  
keypad or zone expander.  
Set each keypad to a different  
address to match the Device  
Setup programming.  
Keypad beeps when keys are  
pressed but won't allow the user  
to arm or enter the User Menu.  
Two or more keypads are  
assigned to the same address.  
No jumper installed on phone jack  
terminals 2 and 7.  
Install a jumper across terminals 2  
and 7 on the phone jack.  
Keypad displays PHONE LINE  
1 TROUBLE.  
Digital Monitoring Products  
2841 E. Industrial Drive Springfield, MO 65802-6310 800-641-4282  
 

Conair Scale WW33D User Manual
Cooper Lighting Work Light EUS Series User Manual
Cornelius Ice Maker DF150 User Manual
Craftsman Chainsaw 316350850 User Manual
Creative Computer Drive GCD R542B User Manual
Crock Pot Slow Cooker Trio User Manual
DLS Svenska AB Speaker NOBELIUM 10 User Manual
Earthquake Sound Speaker EQ12S8 User Manual
Fisher Price Riding Toy T4262 User Manual
Glen Dimplex Home Appliances Ltd Cooktop 321R User Manual