IMI CORNELIUS REMCOR INC g 500 REGENCY DRIVE
g
GLENDALE HEIGHTS, IL 60139--2268
Facsimile (800) 519--4423
Telephone (800) 551--4423
CHILLER (“CH” SERIES)
Models : CH 951-A
CH 1500-A
CH 1502-A
CH 1503-A
Operator’s Manual
Part No. 92266
December 5, 1995
Revised: July, 1999
Revision C
THIS DOCUMENT CONTAINS IMPORTANT INFORMATION
This Manual must be read and understood before installing or operating this equipment
PRINTED IN U.S.A
Ó IMI CORNELIUS INC; 1995--99
GENERAL INFORMATION
INTRODUCTION
The REMCOR ”CH” Series Recirculating Liquid Chiller is designed to provide an accurate, reliable, and user--
friendly system for cooling a continuous flow of pure liquid and keep that liquid at a constant temperature in vari-
ous closed loop or tank cooling applications.
The ”CH” Series Chiller consists of an air--cooled refrigeration system housed in a sturdy sheet metal frame and
cabinet. A standard pump and insulated liquid reservoir package provides a complete liquid cooling and circu-
lating system.
The ”CH” Series Chiller is designed to operate in a clean laboratory or industrial environment where ambient
temperatures range from 40 to100° F (5 to 38° C). With proper installation, operation, and maintenance, the
”CH” Series Chiller will provide years of trouble free service.
UNPACKING AND INSPECTION
This unit was thoroughly inspected before leaving the factory and the carrier has accepted and signed for it.
Any damage or irregularities should be noted at the time of delivery and immediately reported to the carrier. Re-
quest a written inspection report from the Claims Inspector to substantiate any necessary claims. In the event
that an immediate replacement is necessary, please contact REMCOR Chiller Sales at 1--800--551--4423.
DESIGN DATA
Table 1. Des ign Data
CH951
CH1500
CH1502
CH1503
Cooling Capacity:
BTU/hr (W) at 80_ F(27_ C) and
70_ F (21_ C) Liquid Temperature.
12,000 (3,515) 18,000 (5,272) 18,000 (5,272) 18,000 (5,272)
Compressor Horsepower
1 (.746 kW)
1 1/2 (1.12 kW) 1 1/2 (1.12 kW) 1 1/2 (1.12 kW)
Electrical Data:
230/1/60
230/1/60
230/3/60
460/3/60
Voltage/Phase/Hertz/Amperage
11.0 Amps
13.0 Amps
16.4 Amps
10.0 Amps
Refrigerant Type:
R134a
R22
R22
R22
Reservoir Capacity
6.0 gallons (22.7 6.0 gallons (22.7 6.0 gallons (22.7 6.0 gallons (22.7
liters) liters) liters) liters)
Physical Dimensions, Width ¢ Depth 22I ¢ 26.5XI ¢ 22I ¢ 26.5XI ¢ 22I ¢ 26.5XI ¢ 22I ¢ 26.5XI ¢
¢ Height:
38.25I
(56cm ¢ 67cm (56cm ¢ 67cm (56cm ¢ 67cm (56cm ¢ 67cm
¢ 97cm) ¢ 97cm) ¢ 97cm) ¢ 97cm)
38.25I
38.25I
38.25I
Fittings:
Process Connections
3/4” FPT (S/S) 3/4I FPT (S/S) 3/4I FPT (S/S) 3/4I FPT (S/S)
CHILLER INSTALLATION
Location of Chiller
THE CHILLER MUST BE LOCATED NEAR A PROPERLY GROUNDED ELECTRICAL OUTLET. THE CIR-
CUIT SHOULD BE FUSED AND NO OTHER ELECTRICAL APPLIANCE SHOULD BE CONNECTED TO THE
CIRCUIT. ALL ELECTRICAL WIRING MUST CONFORM TO NATIONAL AND LOCAL ELECTRICAL
CODES.
The Chiller must be located in a well ventilated, indoor area where ambient temperatures will remain above
40_ F (5_ C) and will never increase above 100_ F (38_ C). To obtain optimum cooling capacity, the ambient
temperature should be at or below 80_ F (27_ C).
92266
1
It is very important that the air intake and discharge sides of the chiller are not obstructed by other free standing
objects. A minimum of two feet of space on all four sides of the chiller will be sufficient to prevent air flow ob-
structions.
It is also important to direct any hot air discharge from other equipment away from the air intake side of the chill-
er. Condenser air entering the “CH” unit should be below 100_ F (38_ C) .Condenser air temperatures above
100_ F (38_ C) can cause the high pressure safety control to shut down the unit.
Electrical Connections
All wiring must conform to the National Electric Code and any applicable local codes.
The “CH” unit must be PERMANENTLY wired by means of electrical conduit to a properly fused disconnect of
proper amperage OR wired to a properly rated power cord and plugged into an outlet with the appropriate dis-
connect and amperage rating. The electrical junction box includes a four terminal strip for power supply connec-
tions. The DATA PLATE located beside the junction box indicates the phase, voltage and amperage of the
chiller.
Proces s Connections
Follow standard plumbing practices and local codes in making liquid connections. The Chiller inlet and outlet
connections are 3/4”--inch FPT couplings. It is recommended that 3/4--inch I.D. or larger flexible hose and tube
fittings be used as process connections. Lines should be routed with as few bends as possible. Prevent lines
from running near radiators, hot water pipes, etc. Any lengths of tubing that are exposed to high ambient tem-
peratures should be insulated to prevent condensation and/or significant liquid heat gain.
Once the system has been properly plumbed, it is important that the circulation system be filled with liquid. The
reservoir can be filled by removing the fill port cap located on top of the Chiller. After ensuring that the drain is
closed, fill the reservoir via the fill port with pure liquid until the liquid level sight glass on the front of the unit indi-
cates ”FULL”. The fill port cap should then be replaced prior to operation.
DATA PLATE/SERIAL NO.
CONTROL PANEL
JUNCTION BOX
TERMINAL STRIP
TEMPERATURE CONTROLLER
FILL PORT
INTERLOCK STRIP
(IF APPLICABLE)
35.138
37.638
38.224
PRESSURE GAUGE
”FULL”
RESERVOIR LEVEL INDICATOR
DRAIN
OUTLET
INLET
14.000
REAR
21.963
FRONT
FIGURE 1. “CH” SERIES CHILLERS
92266
2
Chiller Operation
WARNING: NEVER OPERATE THE CHILLER WITH THE PANELS REMOVED.
ALWAYS USE THE POWER SWITCH TO TURN OFF THE CHILLER WHEN IT IS NOT BEING
USED.
ALWAYS ENSURE THAT ALL AIR INLETS AND OUTLETS ARE FREE FROM OBSTRUCTION.
BE SURE THAT THE RESERVOIR IS FILLED WITH FLUID PRIOR TO POWERING UP THE UNIT.
Proces s Liquid Flow
After ensuring that the system piping is free from obstruction, that all valves are open, and the reservoir is full,
push the CONTROL POWER switch to the ”ON” position. The pump should now be operating.
On three phase units such as the CH1502 and CH1503, it is important to check the pump rotation. Remove the
left side panel, push the POWER button in, and observe the motor shaft. Make sure that the shaft is rotating in
the direction of the arrow indicated on the pump housing. If the rotation is incorrect, reverse two of the three in-
coming power supply leads at the terminal strip.
NOTE: Running the pump in revers e for too long will res ult in permanent pump damage. The Phas e
Protection/3--Phas e Monitor Option will prevent the pump from operating backwards . See the full de-
s cription of the option for complete explanation.
All Chillers with pumps are supplied with a pressure regulating valve on the pump discharge. This valve is pre-
set at the factory to ensure that system pressure does not exceed the capabilities of the pump motor and/or pip-
ing. If this valve requires adjustment, please contact the REMCOR Service Group for the proper setting
procedure and pressures.
Once the flow has been established the thermostat can be programmed to the desired set--point.
Phas e Protection / 3--Phas e Monitor Option
The 3--Phase Monitor detects phase loss, low voltage, and phase reversal by continuously monitoring the
3--Phase power lines for abnormal conditions. When correct voltage and phase rotation are applied, the internal
relay will energize. A fault condition will de--energize the relay. When the fault is corrected, the monitor will auto-
matically reset. Both Trip and Norm condition indicators are provided on the relay to aid in adjustment and sys-
tem trouble--shooting.
This control is located in the enclosure labeled “Monitor” on top of the electrical box.
Phas e Protection / 3--Phas e Option Adjus tment
The following procedure will allow the 3--Phase Monitor to achieve a trip point just below the nominal phase-to-
phase voltage, where the unit is applied.
Rotate the adjustment control fully clockwise, or until the red (Trip) indicator illuminated. Slowly rotate the
adjustment control in a counter-clockwise direction, just until the green (Norm) indicator illuminates. At this point,
the 3--Phase Monitor is the most sensitive to irregular power line conditions. If nuisance tripping occurs, turn the
control slightly further counter--clockwise.
92266
3
COOLING OPERATION
REMCOR CHXXX SERIES CHILLER
CONTROL
POWER
COOLING
SAFETY
CONTROL PANEL
RED INDICATOR
GREEN INDICATOR
WHITE INDICATOR/PUSH BUTTON
FIGURE 2. CONTROL PANEL
Temperature Indicator/Controller (Thermos tat)
Combines a precise temperature control and easy programmability with a convenient LED temperature
readout that indicates system liquid temperature (2_ F Differential). To adjust thermostat, see next section.
1. CONTROL POWER SWITCH/LIGHT
A simple ON/OFF push--button that switches power to the 24 volt control circuit. When the switch is
pressed, the white light on the push--button illuminates to indicate that Chiller Control Power is present.
Light is no longer illuminated when button is returned to ”OFF” position.
2. COOLING LIGHT
A green light that illuminates to indicate that the refrigeration system is operating. This light may cycle on
and off in response to the thermostat or in response to HOT GAS BYPASS if the unit is equipped with the
hot--gas bypass option.
3. SAFETY LIGHT
A red light that illuminates to indicate that a problem is present with the chiller. The safety light will illumi-
nate under the following conditions:
A. High Refrigerant Pressure
B. Low Refrigerant Pressure
C. Low Reservoir Level (Alarm also sounds)
D. Low Evaporator Temperature
It is important to note that each of these conditions will shut down the ”CH” unit. For additional protection to
your equipment, some models are equipped with a LOW FLOW INTERLOCK which terminates power to
your equipment in the event that liquid flow from the ”CH” unit drops below 1.25 GPM.
92266
4
START--UP
IT IS IMPORTANT THAT THE LIQUID LEVEL SIGHT GLASS READS ”FULL”. IN THE EVENT THAT THE
RESERVOIR IS EMPTY, THE UNIT WILL REMAIN OFF UNTIL AN ADEQUATE LEVEL OF LIQUID IS AT-
TAINED. MAKE SURE CHILLER POWER IS ”OFF” PRIOR TO FILLING RESERVOIR.
Push CONTROL POWER button IN. All alarm indicators should be extinguished and the Chiller system will
cycle in order to maintain the established set-point. The Chiller is now ready for normal operation.
Thermos tat Control
_F
up
out
0
7
down
set
FIGURE 3. CH SERIES TEMPERATURE CONTROLLER
The following procedure should be followed to adjust the thermostat for any liquid cooling application:
1. Push the ”SET” button located to the right of the digital display. This will display the current set-point pro-
grammed in the thermostat.
2. The set-point can only be adjusted while being displayed. To adjust the set-point, push the ”UP” or
”DOWN” button until the desired set point is displayed on the thermostat.
3. Once the desired set-point is displayed, wait several seconds and the thermostat will display the process
liquid temperature. The set-point can be viewed at any time by pressing the ”SET” button.
The parameter settings of the thermostat have been preset at the factory. The range of the thermostat is
40_ F (5_ C) to 100_ F (38_ C). If operation outside of this range is desired, please contact the REMCOR
TECHNICAL SERVICE DEPARTMENT at 1--800--551--4423.
CHILLER MAINTENANCE
WARNING: Dis connect electrical power before performing any maintenance on the Chiller.
Condens er
On air cooled chillers, the CONDENSER FINS should be cleaned by blowing compressed air through the con-
denser from the fan side. Dirt and debris accumulate on the condenser fins over time, and this build up can se-
verely reduce the performance of the Chiller. Cleaning of the CONDENSER FINS should be done
approximately every three months, depending upon the cleanliness of your application.
Fan Motor
On air cooled chillers the condenser FAN MOTOR should be lubricated every 6 months with a few drops of SAE
10 oil.
92266
5
Pump Motor
The PUMP MOTOR should be lubricated with thirty drops of SAE 20 oil once a year.
Circulation Sys tem
The CIRCULATION SYSTEM should be drained and flushed periodically to avoid build up and possible flow re-
striction caused by contaminants.
Filters /Strainers
The FILTER located inside of the unit at the inlet of the pump should be cleaned periodically depending on ap-
plications. If a reduction in flow or cavitation of the pump occurs, remove the in--line FILTER, back-flush it with
water, rinse, and replace.
92266
6
TROUBLESHOOTING
WARNING: Dis connect electrical power to the Chiller to prevent pers onal injury before
attempting any internal maintenance. Only qualified pers onnel s hould s ervice internal
components or electrical wiring.
TROUBLE
PROBABLE CAUSE
A. No Power To Unit.
REMEDY
CHILLER DOES NOT
OPERATE, CONTROL
POWER LIGHT “OFF”
A. Check Main disconnect fuses,
wiring, and power lead to unit.
B. Defective Control Power
Switch.
B. Replace Switch
C. Defective Control Transformer. C. Replace Transformer
D. Wrong Voltage Supplied to
Unit.
D. Supplied Voltage Must be within
± 10% of nameplate rating.
E. 3--Phase Monitor tripped.
E. Check for correct voltage level on
each phase of incoming 3--phase
power. Check for correct phase
rotation.
PUMP DOES NOT OPERATE, A. Line to or from Chiller is
A. Inspect lines and remove any
obstructions.
BUT COOLING LIGHT IS
”ON”.
restricted.
B. Internal or external filter is
blocked with debris.
B. Remove filter, back-flush, and
replace.
C. Pump Contactor is
defective.
C. Replace.
D. Damaged pump motor or
impeller.
D. Replace pump motor or impeller.
A. Replace Thermostat
CHILLER DOES NOT COOL,
AND COOLING LIGHT IS
”OFF”.
A. Thermostat is defective.
PUMP RUNS, COMPRESSOR A. No process load on
A. Increase process load.
”SHORT CYCLES”.
chiller.
B. Refrigerant is low.
B. Check refrigerant charge.
A. Clean condenser.
UNIT RUNS CONTINUOUSLY, A. Condenser is restricted.
BUT IS NOT COOLING
PROCESS LIQUID ENOUGH.
B. Unit low on refrigerant.
C. Inefficient compressor.
B. Call Service.
C. Call Service.
D. Unit is undersized for
application.
D. Call REMCOR Chiller Sales Rep.
TROUBLE
PROBABLE CAUSE
REMEDY
CHILLER DOES NOT
OPERATE, BUT COOLING
LIGHT IS “ON” AND SAFETY
LIGHT IS “ON”.
A. Unit is operating under high
pressure conditions.
A. Check for dirty condenser fins or
obstruction of chiller air intake.
Press high pressure manual reset
switch.
B. Unit is operating under low
pressure conditions.
B. Check sight glass, if bubbles are
seen, leak check unit and
recharge with refrigerant.
or
If no bubbles are seen, replace
defective TXV.
C. Unit is operating under low
level conditions.
C. Add liquid to reservoir via fill port.
or
If level is above switch, replace
float switch.
D. Unit is operating under low
temperature conditions.
D. Low or no process liquid flow.
Ensure that there is adequate flow
through system plumbing.
or
Process liquid is too cold, below
35_ F. Increase thermostat
setting.
or
Defective thermostat, replace.
When servicing a REMCOR Chiller, it is important to note all information provided on the DATA PLATE located
in the upper rear of the unit. If technical assistance is needed, the REMCOR Service Technician will need this
information along with any description of the problem(s) you are encountering. The serial number and other
information will also be required when ordering replacement parts and any other Warranty Claims.
8
92266
46
48
51
10
13
44
49
11
32
35
17
24
15
23
39
25
47
33
50
52
33
45
50
35
6
5
27
16
42
13
26
43
17
41
28
36
32
14
39
36
29
30
16
38
37
20
34
1
40
9
3
31
2
17
4
35
7
21
19
22
12
18
16
17
35
8
FIGURE 4. CABINET SECTION EXPLODED VIEW
9
92266
CABINET SECTION
Index
No.
Index
No.
Part No. Qty
Name
Part No. Qty
Name
Indicator Light, Red, 24v
Indicator Light, Green, 24v
Switch, White, Lighted 24v
Gauge, Pressure (CH 951)
Gauge, Pressure (CH 1502)
Clamp
1
15166
15207
15426
61170
1
2
2
1
Frame
23
24
25
26
32807
32808
32806
71058
70950
70325
70951
70952
70953
70030
70274
1
1
1
1
1
2
8
8
8
4
8
2
Support Panel (CH 951)
Support Panel (CH 1502)
3
Pump and Tank Ass’y (CH 951; See
Figure 6)
61167
70190
1
2
Pump and Tank Ass’y (CH 1502; See
Figure 6)
27
28
29
30
31
32
Fastener, Clip On
4
Screw, Hex Hd, No. 8-32 By 1/2-In.
Long
Retainer, Push On
5
6
7
15159
15172
15165
15427
15164
15425
33437
1
1
2
2
2
2
1
Support, Condenser
Fill Port Ass’y
Screw, Sl Hd, Fastener
Nut
Panel, Side (CH 951)
Panel, Side (CH 1502)
Panel, Rear (CH 951)
Panel, Rear (CH 1502)
Screw, Cap Hex Hd, No. 5/16-18 By
3/4-In. Long
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
70048
70018
70171
70028
70065
70268
70070
32588
70877
51282
71042
60734
70344
70475
60686
61003
60975
70032
7
7
Lockwasher
8
9
Hex Nut, 1/4-20
20 Screw, Phil Hd, No.8-32 By 3/8-In. Long
12 Nut, 5/16-18
Electrical Box Ass”y (CH 951; See
Figure 5)
33585
1
Electrical Box Ass”y (CH 1502; See
Figure 5)
4
4
8
1
Lockwasher
Screw, CapHex Hd, 1/4-20 By 1-In. Long
Flatwasher
10
11
15167
15428
61061
61168
70217
1
1
1
1
4
Lid (CH 951)
Lid (CH 1502)
Probe, Temperature
Condenser Ass’y (CH 951)
Condenser Ass’y (CH 1502)
14 Nutsert
1
1
1
1
1
1
1
1
5
Adaptor, 3/4-MPT By 1/2-Barb
12
13
14
Screw, Hex Hd, No. 8--32 By 1/2-In.
Long
Clamp, Hose
70178
6
Screw, Phil Hd, No. 8--32 By 1/2-In.
Long
Solenoid Valve, Hot Gas
Bracket, Drier
15163
15424
32386
70076
70121
28876
70778
70923
32452
31036
1
1
2
Panel, Front (CH 951)
Panel, Front (CH 1502)
Thermostat Control, 24v
Clamp, TX Valve
Filter Drier
15
16
17
18
19
20
21
22
TX Valve
14 Hex Nut, No. 8-32
24 Lockwasher
Valve, Auto Expansion
Screw, Cap Hex Hd, 1/4-20 By 1/2-In.
Long
2
4
2
1
1
Coupling Ass’y
Caster
51
52
33283
22850
1
1
Coil, Solenoid 24v
Bracket, TX Valve
Handle
Terminal Block
Electrical Box, 4-In.
92266
10
24
23
4
18
3
5
22
16
19
6
18
18
2
1
7
14
21
17
20
15
FIGURE 5. ELECTRICAL BOX ASSEMBLY EXPLODED VIEW
ELECTRICAL BOX ASSEMBLY
Item Part
Item Part
No.
No. Qty.
Name
No.
No. Qty.
Name
1
2
3
4
5
6
7
8
15269
309060
31001
32804
32922
33082
33339
33573
1
1
1
1
1
1
1
1
Electrical Box
Terminal Board
Thermostat
12
33577
33606
1
Wire Harness, Hot Gas (CH 951; Not
Shown)
1
Wire Harness, Hot Gas (CH 1502; Not
Shown)
Transformer, 24V 50VA
Contactor, Compressor
Relay, 24V
13
14
15
16
17
18
33578
50459
50767
60501
70018
70190
1
1
1
1
2
Wire Harness, Thermostat (Not Shown)
Heyco Bushing
Heyco Bushing
Alarm, 24V
High Pressure Control
Hex Nut, 1/4-20
Wire Harness, Main Power (CH 951; Not
Shown)
11 Screw, Hex Washer Hd, No. 8-32 By
1/2-In. Long
33607
33574
33608
1
1
1
Wire Harness, Main Power (CH 1502;
Not Shown)
19
20
70215
70263
6
Screw, Sl Washer Hd, No. 8-32 By
1/4-In. Long
9
Wire Harness, Condenser (CH 951; Not
Shown)
2
Screw, Cap Hex Hd, 1/4-20 By 3/4-In.
Long
Wire Harness, Condenser (CH 1502;
Not Shown)
21
22
23
24
70475
15270
70121
70171
1
1
1
1
Clamp, Alarm
10
11
33575
33576
1
1
Wire Harness, Alarm (Not Shown)
Wire Harness, Switch (Not Shown)
Cover, Electrical Box
Lockwasher, No. 8
Screw, Phil Truss Hd, No. 8-32 By
3/8-In. Long
11
92266
35
23
18
28
17
44
18
46
14
45
38
3
8
31
35
16
17
18
28
29
2
48
7
22
34
39
40
37
1
9
14
14
46
15
22
16
28
30
18
26
32
30
19
10
18
24
33
14
35
43
11
12
13
6
25
27
16
16
35
36
18
47
32
18
33
16
35
42
19
30
18
17
35
21
41
4
17
20
5
FIGURE 6. PUMP AND TANK ASSEMBLY
92266
12
PUMP AND TANK ASSEMBLY
Item Part
Item Part
No.
No. Qty.
Name
No.
No. Qty.
Name
29
41473
1
Nipple, 1/2-NPT, Stainless Steel (CH
951)
1
2
15162
53206
53192
27866
61169
32382
53223
50351
33159
70028
70274
1
1
1
1
1
1
1
1
2
4
4
Base
40902
41477
1
2
Nipple, 1/2-NPT, Brass (CH 1502)
Tank
30
31
Nipple, 3/4-NPT, Stainless Steel (CH
951)
3
Cover
41442
41478
3
1
Nipple, 3/4-NPT, Brass (CH 1502)
4
Thermalwell
Evaporator
Fitting, 1/2-MPT, Stainless Steel (CH
951)
5
6
Motor, Pump, 1/3 HP 115/230V
PVC Valve
41495
41467
1
2
Fitting, 1/2-MPT, Brass (CH 1502)
7
8
Tube, .500 I.D. By 28-In. Long
Sensor, Low Level
32
33
Fitting, Elbow, 3/4-NPT, Stainless Steel
(CH 951)
9
10
11
Hex Nut, 5/16-18
Screw, Cap, Hex Hd, No. 5/16-18 By
3/4-In. Long
41096
41462
2
2
Fitting, Elbow, 3/4-NPT, Brass (CH 1502)
Fitting, Elbow, 3/4-NPT By 3/4-Barb,
Stainless Steel (CH 951)
12
13
14
15
16
70065
70070
50991
51842
41266
4
4
4
1
6
Lockwasher
Flatwasher
40841
2
Fitting, Elbow, 3/4-NPT By 3/4-Barb,
Brass (CH 1502)
Bulkhead, 1/2 I.D.
Bulkhead, 3/4 I.D.
Elbow, 1/2-NPT, Stainless Steel (CH
951)
34
35
51425
53157
53157
53157
53157
53157
53157
31971
26198
51704
53226
53225
32385
32384
32357
30121
51350
50351
71042
51280
70325
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
3
1
2
Plug, 1/4-MPT
Tube, .750 I.D. By 3-In. Long
Tube, .750 I.D. By 6-In. Long
Tube, .750 I.D. By 7-In. Long
Tube, .750 I.D. By 8-In. Long
Tube, .750 I.D. By 10 1/2-In. Long
Tube, .750 I.D. By 22-In. Long
Switch, Flow, Brass (CH 1502)
Bracket, Tank
40904
41474
6
4
Elbow, 1/2-NPT, Brass (CH 1502)
17
18
19
Bushing, Fitting, 3/4-NPT By 1/2-NPT,
Stainless Steel (CH 951)
41485
41468
4
9
8
3
2
1
Bushing, Fitting, 3/4-NPT By 1/2-NPT,
Brass (CH 1502)
Fitting, 1/2-MPT By 3/4-Barb, Stainless
Steel (CH 951)
Fitting, 1/2-MPT By 3/4-Barb, Brass (CH
1502)
36
37
38
39
40
41
42
41488
41444
41476
Fitting, 1/2-MPT, 2 1/2-In. Long,
Stainless Steel (CH 951)
Fitting, 1/2-MPT, 2 1/2-In. Long, Brass
(CH 1502)
Fitting, 3/8-PVC
20
21
Fitting, Tee, 3/4-NPT, Stainless Steel
(CH 951)
Fitting, Coupler, 3/8-PVC
Fitting, 3/8-PVC By 1 1/2-In. Long
Clamp, Pump to Motor
Pump (CH 951)
41040
41470
1
2
Fitting, Tee, 3/4-NPT, Brass (CH 1502)
Fitting, Elbow, 1/2-NPT, Stainless Steel
(CH 951)
41443
51075
71045
41438
24676
41461
40645
70018
41268
40903
1
2
Fitting, Elboe, 1/2-NPT, Brass (CH 1502)
Elbow, 1/2-MPT By 1/2-Barb
Pump (CH 1502)
22
23
24
25
26
10 Clamp, Tube
43
44
45
46
47
48
Electrical Cord
1
1
1
1
4
3
3
Filter, Water
Tube, .250 I.D. By 30-In. Long
Tube, .500 I.D. By 25-In. Long
Clamp, Tube
Thermowell
Bypass Valve, Stainless Steel(CH 951)
Bypass Valve, Brass (CH 1502)
Hex Nut, 1/4-20
27
28
Fitting, Elbow, 3/4-Barb (CH 1502)
Clip
Tee, 1/2-FPT, Stainless Steel (CH 951)
Tee, 1/2-FPT, Brass (CH 1502)
13
92266
WARRANTY
IMI Cornelius Inc. warrants that all equipment and parts are free from defects in material and workmanship un-
der normal use and service. For a copy of the warranty applicable to your Cornelius, Remcor or Wilshire prod-
uct, in your country, please write, fax or telephone the IMI Cornelius office nearest you. Please provide the
equipment model number, serial number and the date of purchase.
IMI Cornelius Offices
AUSTRALIA D P.O. 210, D RIVERWOOD, D NSW 2210, AUSTRALIA D (61) 2 533 3122 D FAX (61) 2 534 2166
AUSTRIA D AM LANGEN FELDE 32 D A-1222 D VIENNA, AUSTRIA D (43) 1 233 520 D FAX (43) 1-2335-2930
BELGIUM D BOSKAPELLEI 122 D B-2930 BRAASCHAAT, BELGIUM D (32) 3 664 0552 D FAX (32) 3 665 2307
BRAZIL D RUA ITAOCARA 97 D TOMAS COELHO D RIO DE JANEIRO, BRAZIL D (55) 21 591 7150 D FAX (55) 21 593 1829
ENGLAND D TYTHING ROAD ALCESTER D WARWICKSHIRE, B49 6 EU, ENGLAND D (44) 789 763 101 D FAX (44) 789 763 644
FRANCE D 71 ROUTE DE ST. DENIS D F-95170 DEUIL LA BARRE D PARIS, FRANCE D (33) 1 34 28 6200 D FAX (33) 1 34 28 6201
GERMANY D CARL LEVERKUS STRASSE 15 D D-4018 LANGENFELD, GERMANY D (49) 2173 7930 D FAX (49) 2173 77 438
GREECE D 488 MESSOGION AVENUE D AGIA PARASKEVI D 153 42 D ATHENS, GREECE D (30) 1 600 1073 D FAX (30) 1 601 2491
HONG KONG D 1104 TAIKOTSUI CENTRE D 11-15 KOK CHEUNG ST D TAIKOKTSUE, HONG KONG D (852) 789 9882 D FAX (852) 391 6222
ITALY D VIA PELLIZZARI 11 D 1-20059 D VIMARCATE, ITALY D (39) 39 608 0817 D FAX (39) 39 608 0814
NEW ZEALAND D 20 LANSFORD CRES. D P.O. BOX 19-044 AVONDALE D AUCKLAND 7, NEW ZEALAND D (64) 9 8200 357 D FAX (64) 9 8200 361
SINGAPORE D 16 TUAS STREET D SINGAPORE 2263 D (65) 862 5542 D FAX (65) 862 5604
SPAIN D POLIGONO INDUSTRAIL D RIERA DEL FONOLLAR D E-08830 SANT BOI DE LLOBREGAT D BARCELONA, SPAIN D (34) 3 640 2839 D FAX (34) 3 654 3379
USA D ONE CORNELIUS PLACE D ANOKA, MINNESOTA D (612) 421-6120 D FAX (612) 422-3255
LD004
4/21/98
92266
14
THIS PAGE LEFT BLANK INTENTIONALLY
15
92266
IMI CORNELIUS INC.
CORPORATE HEADQUARTERS:
One Cornelius Place
Anoka, Minnesota 55303-6234
(612) 421-6120
(800) 238-3600
|