Bosch Appliances Smoke Alarm FMC 120 DKM User Manual

Fire Alarm Systems | FMC‑120‑DKM Manual Call Points  
FMC‑120‑DKM Manual Call Points  
u Adjustment of the manual call point after alarm trig-  
gering  
u Indicator LED for alarm or for inspection evaluation  
u Second contact with connections for panel control  
u Variants for indoor and outdoor use  
Variants  
The FMC-120-DKM Manual Call Points handle manual  
alarm triggering and are used with conventional tech-  
nology.  
The design of the manual call points for indoor  
(form G) and outdoor use (form H) are identical. Three  
color variants, red, blue, and yellow are available.  
Detectors for outdoor use (form H) have a cover  
equipped with a seal.  
Functions  
5
1
1
Certifications and Approvals  
Type Number  
Complies with  
2
4
FMC‑120‑DKM‑G‑R  
FMC‑120‑DKM‑H‑R  
FMC‑120‑DKM‑G‑Y  
FMC‑120‑EST‑G‑B  
EN54-11:2001/A1:2005  
EN54-11:2001/A1:2005  
EN12094-3:2003  
3
3
2
EN12094-3:2003  
In the event of an alarm, the glass pane (2) is broken  
first, then the manual call point (3) is pressed hard.  
This activates the micro switch for alarm triggering  
and the indicator LED (4) blinks.  
A locking mechanism holds the pressed manual call  
point.  
The manual call point can be reset with the reset lever  
(5). The indicator LED (4) goes out.  
This does not reset the alarm on the fire panel.  
Region  
Certification  
Germany  
VdS  
VdS  
VdS  
G 298061 FMC-120-DKM-G-R/-H-  
R_G298061  
G 206079 FMC-120-DKM-G-  
Y_G206079  
G 206080 FMC-120-EST-G-B/-H-  
HE_G206080  
 
3 | FMC‑120‑DKM Manual Call Points  
Environmental conditions  
FMC‑FST‑DE Printed Labeling Foils for the Upper Label  
Field  
For yellow and blue manual call points of Series  
FMC‑120 and FMC‑210, 1 unit = 5 sheets  
Order number FMC-FST-DE  
Protection class as per EN 60529  
Form G (indoor area)  
Form H (outdoor area)  
Norm  
IP 52  
IP 54  
FMC‑SPGL‑DEIL Spare Glasses  
For manual call points of Series DM, DKM, SKM,  
FMC‑120 and FMC‑210.  
FMC-120-DKM-G-R,  
FMC‑120‑DKM‑H‑R  
EN 54-11  
1 unit = 5 spare glasses  
Order number FMC-SPGL-DEIL  
FMC-120-DKM-G-Y,  
FMC‑120‑EST‑G‑B  
EN 12094-3  
Key for Fire Detectors Types G and H  
made of red plastic (ASA)  
Order number FMM-KEY-Form G/H  
Permissible operating tempera-  
ture  
Form G (indoor area)  
-10 °C . . . +55 °C /  
14 °F … 131 °F  
Form H (outdoor area)  
-25 °C . . . +70 °C /  
-13 °F … 158 °F  
Ordering Information  
FMC‑120‑DKM‑G‑R Form G, Red  
Manual Call Point for indoor use, indirect alarm trig-  
gering (type B), conventional technology  
Order number FMC-120-DKM-G-R  
FMC‑120‑DKM‑H‑R Form H, Red  
Manual Call Point for outdoor use, indirect alarm trig-  
gering (type B), conventional technology  
Order number FMC-120-DKM-H-R  
FMC‑120‑DKM‑G‑B Form G, Blue  
Manual Call Point for indoor use, indirect triggering  
(type B), conventional technology  
Order number FMC-120-DKM-G-B  
FMC‑120‑DKM‑H‑B Form H, Blue  
Manual Call Point for outdoor use, indirect triggering  
(type B), conventional technology  
Order number FMC-120-DKM-H-B  
FMC‑120‑DKM‑G‑Y Form G, Yellow  
Manual Call Point for indoor use, indirect triggering  
(type B), conventional technology  
Order number FMC-120-DKM-G-Y  
FMC‑120‑EST‑G‑B Form G, Blue  
Electronic Stop Device for indoor use, indirect trigger-  
ing (type B), conventional technology  
Order number FMC-120-EST-G-B  
Accessories  
FMX‑FSO‑GLT Punched, Self-adhesive Foil Sets (Blank)  
For the labeling field of conventional manual call  
points of the Series FMC‑120, 1 unit = 10 sheets  
Order number FMX-FSO-GLT  
 
4 | FMC‑120‑DKM Manual Call Points  
FMC-120-DKM Double Action Call Points  
FMC‑120‑DKM‑G‑R Form G, Red  
FMC‑120‑DKM‑H‑R Form H, Red  
FMC‑120‑DKM‑G‑B Form G, Blue  
Range of use  
indoor  
outdoor  
indoor  
Mounting  
surface-mounted/flush-mounted  
16.2 V DC . . . 30 V DC  
surface-mounted/flush-mounted  
16.2 V DC . . . 30 V DC  
surface-mounted/flush-mounted  
16.2 V DC . . . 30 V DC  
Operating voltage  
Current consumption  
specified by the respective security  
system  
specified by the respective security  
system  
specified by the respective security  
system  
Protection category  
Permissible operating temperature  
Color  
IP 52  
IP 54  
IP 52  
-10°C . . . +55°C  
red, RAL 3001  
-25°C . . . +70°C  
red, RAL 3001  
-10°C . . . +55°C  
blue, RAL 5005  
FMC‑120‑DKM‑H‑B Form H, Blue  
FMC‑120‑DKM‑G‑Y Form G, Yellow  
FMC‑120‑EST‑G‑B Form G, Blue  
Range of use  
outdoor  
indoor  
indoor  
Mounting  
surface-mounted/flush-mounted  
16.2 V DC . . . 30 V DC  
surface-mounted/flush-mounted  
16.2 V DC . . . 30 V DC  
surface-mounted/flush-mounted  
16.2 V DC . . . 30 V DC  
Operating voltage  
Current consumption  
specified by the respective security  
system  
specified by the respective security  
system  
specified by the respective security  
system  
Protection category  
Permissible operating temperature  
Color  
IP 54  
IP 52  
IP 52  
-25°C . . . +70°C  
blue, RAL 5005  
-10°C . . . +55°C  
yellow, RAL 1003  
-10°C . . . +55°C  
blue, RAL 5005  
Represented by:  
Americas:  
Europe, Middle East, Africa:  
Bosch Security Systems B.V.  
P.O. Box 80002  
5600 JB Eindhoven, The Netherlands  
Phone: + 31 40 2577 284  
Fax: +31 40 2577 330  
Asia-Pacific:  
Robert Bosch (SEA) Pte Ltd, Security Systems  
11 Bishan Street 21  
Singapore 573943  
Phone: +65 6258 5511  
Fax: +65 6571 2698  
Bosch Security Systems, Inc.  
130 Perinton Parkway  
Fairport, New York, 14450, USA  
Phone: +1 800 289 0096  
Fax: +1 585 223 9180  
© Bosch Security Systems 2012 | Data subject to change without notice  
1291424267 | en, V2, 08. Mar 2012  
 

Black Decker Coffeemaker TCM830 User Manual
Blount Chainsaw 633GC User Manual
Bolens Lawn Mower 115 020A User Manual
Brady Printer 200M User Manual
Braun Blender MR 6500 M User Manual
Braun Styling Iron C 20 User Manual
Breville Espresso Maker BES840 User Manual
Campbell Hausfeld Cordless Drill DX111425CD User Manual
Canon All in One Printer 4497B001AA User Manual
Cisco Systems IP Phone 7942G User Manual