BRK electronic Carbon Monoxide Alarm SCO7B User Manual

For additional coverage, it is recommended that you install a Smoke Alarm in  
all rooms, halls, storage areas, finished attics, and basements, where tempera-  
tures normally remain between 40˚ F (4˚ C) and 100˚ F (38˚ C). Make sure no  
door or other obstruction could keep smoke from reaching the Smoke Alarms.  
More specifically, install Smoke Alarms:  
ABOUT SMOKE ALARMS  
Battery (DC) operated Smoke Alarms: Provide protection even when  
electricity fails, provided the batteries are fresh and correctly installed. Units  
are easy to install, and do not require professional installation.  
HOW TO INSTALL THIS ALARM  
IF THE SMOKE ALARM SOUNDS  
WHAT YOU WILL SEE AND HEAR WITH THIS ALARM  
Under Normal Operations  
WHAT YOU NEED TO KNOW ABOUT CO  
RESPONDING TO AN ALARM  
USER’S MANUAL  
WHAT IS CO?  
CO is an invisible, odorless, tasteless gas produced when fossil fuels do not  
burn completely, or are exposed to heat (usually fire). Electrical appliances  
typically do not produce CO.  
These fuels include: Wood, coal, charcoal, oil, natural gas, gasoline, kerosene,  
and propane.  
Common appliances are often sources of CO. If they are not properly main-  
tained, are improperly ventilated, or malfunction, CO levels can rise quickly.  
CO is a real danger now that homes are more energy efficient. “Air-tight”  
homes with added insulation, sealed windows, and other weatherproofing  
can “trap” CO inside.  
This combination Smoke/CO Alarm was designed to be mounted on the  
ceiling or wall. It is not a tabletop device. You must install this device on the  
ceiling or wall as outlined below. Read “Where To Install This Alarm” before  
starting.  
Voice: Silent  
Power/Smoke LED: Flashes Green once a  
minute  
COMBINATION CARBON MONOXIDE & SMOKE ALARM  
WITH VOICE & LOCATION AND  
If the unit alarms and you are not testing the unit, it is warning you  
of a potentially dangerous situation that requires your immediate  
attention. NEVER ignore any alarm. Ignoring the alarm may result in  
injury or death.  
Never remove the batteries from a battery operated Smoke/CO Alarm  
to stop an unwanted alarm (caused by cooking smoke, etc.). Removing  
batteries disables the alarm so it cannot sense smoke, and removes  
your protection. Instead open a window or fan the smoke away from  
the unit. The alarm will reset automatically.  
AC powered Smoke Alarms: Can be interconnected so if one unit senses  
smoke, all units alarm. They do not operate if electricity fails.  
AC with battery (DC) back-up: will operate if electricity fails, provided the  
batteries are fresh and correctly installed. AC and AC/DC units must be  
installed by a qualified electrician.  
Smoke/CO Alarms for Solar or Wind Energy users and battery backup  
power systems: AC powered Smoke/CO Alarms should only be operated  
with true or pure sine wave inverters. Operating this Alarm with most battery-  
powered UPS (uninterruptible power supply) products or square wave or  
“quasi sine wave” inverters will damage the Alarm. If you are not sure about  
your inverter or UPS type, please consult with the manufacturer to verify.  
Smoke Alarms for the hearing impaired: Special purpose Smoke Alarms  
should be installed for the hearing impaired. They include a visual alarm and an  
audible alarm horn, and meet the requirements of the Americans With Disabilities  
Act. Can be interconnected so if one unit senses smoke, all units alarm.  
Smoke alarms are not to be used with detector guards unless the  
combination has been evaluated and found suitable for that purpose.  
Horn: Silent  
CO LED: Off  
On every level of your home, including finished attics and basements.  
REMOTE CONTROL TEST/SILENCE  
Inside every bedroom, especially if people sleep with the door partly or  
completely closed.  
When You Test the Alarm  
Features:  
Voice: Testing.” “Warning, evacuate smoke in [Location, example:  
In the hall near every sleeping area. If your home has multiple sleeping  
areas, install a unit in each. If a hall is more than 40 feet long (12 meters),  
install a unit at each end.  
At the top of the first-to-second floor stairway, and at the bottom  
of the basement stairway.  
“Kitchen”]. Evacuate.”  
PARTS OF THIS SMOKE/CO ALARM  
Separate sensors to detect smoke  
and CO; the two alarm systems  
work independently  
Horn: 3 beeps, pause, 3 beeps, voice  
Power/Smoke LED: Flashes Red  
1
Test/Silence Button and Remote  
Control Sensor  
CO LED: Off  
followed by  
Voice with programmable location  
2
3
4
Battery Compartment  
Power/Smoke Alarm LED  
CO Alarm LED  
If the unit alarms get everyone out of the house immediately.  
Voice: “Warning, evacuate carbon monoxide in [Location, example:  
Separate audible and visual  
signals to indicate alarm levels  
of smoke or CO  
SYMPTOMS OF CO POISONING  
“Kitchen”]. Evacuate.”  
WHAT TO DO IN CASE OF FIRE  
These symptoms are related to CO POISONING and should be discussed with  
ALL household members.  
Specific requirements for Smoke Alarm installation vary from state to state  
and from region to region. Check with your local Fire Department for current  
requirements in your area. It is recommended AC or AC/DC units be inter-  
connected for added protection.  
Horn: 4 beeps, pause, 4 beeps, voice  
Power/Smoke LED: Off  
CO LED: Flashes Red  
• Don’t panic; stay calm. Follow your family escape plan.  
• Get out of the house as quickly as possible. Don’t stop to get  
dressed or collect anything.  
• Feel doors with the back of your hand before opening them.  
If a door is cool, open it slowly. Don’t open a hot door. Keep doors  
and windows closed, unless you must escape through them.  
Remote infrared Test/Silence and  
programming  
Mild Exposure: Slight headache, nausea, vomiting, fatigue (“flu-like” symptoms).  
Medium Exposure: Throbbing headache, drowsiness, confusion, fast heart rate.  
Extreme Exposure: Convulsions, unconsciousness, heart and lung failure.  
Exposure to Carbon Monoxide can cause brain damage, death.  
Tools you will need: pencil, drill with 3/16” or 5mm drill bit,  
flathead screwdriver, hammer.  
Powered by two “AA” batteries  
Side access drawer for easy  
battery replacement  
If Battery Becomes Low or is Missing  
Voice: “Replace battery in [Location, example “Kitchen”].” Repeated  
every 5 hours  
All these Smoke Alarms are designed to provide early warning of fires if located,  
installed and cared for as described in the users manual, and if smoke reaches  
the Alarm. If you are unsure which type of Smoke Alarm to install, refer the  
National Fire Protection Association (NFPA) Standard 72 (National Fire Alarm  
Code) and NFPA 101 (Life Safety Code). National Fire Protection Association,  
One Batterymarch Park, Quincy, MA 02269-9101. Local building codes may also  
require specific units in new construction or in different areas of the home.  
Horn: chirps once a minute  
Power/Smoke LED: Flashes approximately once a minute  
CO LED: Off  
• Cover your nose and mouth with a cloth (preferably damp).  
Take short, shallow breaths.  
• Meet at your planned meeting place outside your home,  
and do a head count to make sure everybody got out safely.  
• Call the Fire Department as soon as possible from outside.  
Give your address, then your name.  
• Never go back inside a burning building for any reason.  
Do not connect this unit to any other alarm or auxiliary device. It is a  
single-station unit that cannot be linked to other devices. Connecting  
anything else to this unit may prevent it from working properly.  
This CO Alarm measures exposure to CO over time. It alarms if CO levels are  
extremely high in a short period of time, or if CO levels reach a certain mini-  
mum over a long period of time. The CO Alarm generally sounds an alarm  
before the onset of symptoms in average, healthy adults. Why is this important?  
Because you need to be warned of a potential CO problem while you can still  
react in time. In many reported cases of CO exposure, victims may be aware  
that they are not feeling well, but become disoriented and can no longer react  
well enough to exit the building or get help. Also, young children and pets may  
be the first affected. The average healthy adult might not feel any symptoms  
when the CO Alarm sounds. However, people with cardiac or respiratory  
problems, infants, unborn babies, pregnant mothers, or elderly people can  
be more quickly and severely affected by CO. If you experience even mild  
symptoms of CO poisoning, consult your doctor immediately!  
IMPORTANT! PLEASE READ CAREFULLY AND SAVE.  
This users manual contains important information  
about your Combination Carbon Monoxide & Smoke  
Alarm’s operation. If you are installing this Alarm for  
use by others, you must leave this manual—or a copy  
of it—with the end user.  
If Alarm is Not Operating Properly  
Do not install this unit over an electrical junction box. Air currents  
around junction boxes can prevent smoke from reaching the sens-  
ing chamber and prevent the unit from alarming. Only AC powered  
units are intended for installation over junction boxes.  
Voice: “Detector error in [Location, example “Kitchen”], please see  
manual.” Repeated every 5 hours  
Horn: Three rapid chirps every minute  
Power/Smoke LED: Flashes approximately once a minute  
CO LED: Off  
Model SCO7  
• Contact your Fire Department for ideas on making your home safer.  
SPECIAL COMPLIANCE CONSIDERATIONS  
M08-0048-006  
Q
10/06 Printed in Mexico  
If you want to lock the battery compartment, or lock the Smoke/CO  
Alarm to the mounting bracket, please read the “Optional Locking  
Features” section in the “Programming Guide” attachment before you  
begin installation.  
1. Hold base firmly and twist the mounting bracket counterclockwise (left) to  
separate it from the unit.  
2. Hold the mounting bracket against the ceiling (or wall) so the vertical  
mounting slot is aligned in the 12 o’clock position and trace around the  
inside of the mounting slots (vertical and horizontal mounting).  
3. Put the unit where it won’t get covered with dust when you drill the  
mounting holes.  
4. Using a 3/16” (5 mm) drill bit, drill a hole through the center of the oval  
outlines you traced.  
5. Insert the plastic screw anchors (in the plastic bag with screws) into the  
holes. Tap the screw anchors gently with a hammer, if necessary, until  
they are flush with the ceiling or wall.  
6. Line the mounting bracket up over the plastic screw anchors.  
7. Screw the mounting bracket to the ceiling or wall through the mounting  
slots using the two screws provided.  
Alarm Levels of CO are Detected  
Alarms have various limitations. See "General Limitations of Smoke/CO  
Alarms" for details.  
This unit alone is not a suitable substitute for complete fire detection  
systems in places housing many people—like apartment buildings,  
condominiums, hotels, motels, dormitories, hospitals, long-term health  
care facilities, nursing homes, day care facilities, or group homes of any  
kind—even if they were once single-family homes. It is not a suitable  
substitute for complete fire detection systems in warehouses, industrial  
facilities, commercial buildings, and special-purpose non-residential  
buildings which require special fire detection and alarm systems.  
Depending on the building codes in your area, this unit may be used to  
provide additional protection in these facilities.  
Voice: “Warning, evacuate carbon monoxide in [Location, example:  
TABLE OF CONTENTS  
“Kitchen”]. Evacuate.” “____ ppm.”  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
Fire Safety Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
Basic Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1  
Step By Step Guide to Programming This Alarm . . . . . . . . . . . . . . . . . . . . .1  
What You Will See and Hear With This Alarm . . . . . . . . . . . . . . . . . . . . . .2  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3  
Where to Install This Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2  
Where This Alarm Should NOT Be Installed . . . . . . . . . . . . . . . . . . . . . . .2  
How to Install This Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
If Your Smoke/CO Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4  
What To Do First–Identify The Type Of Alarm . . . . . . . . . . . . . . . . . . . . . .3  
If the CO Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3  
If the Smoke Alarm Sounds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Using the Silence Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Weekly Testing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
Regular Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4  
What You Need To Know About CO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
What is CO? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Symptoms of CO Poisoning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Potential Sources of CO in the Home . . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
How Can I Protect My Family From CO Poisoning? . . . . . . . . . . . . . . . . . . .5  
Regulatory Information For Smoke/CO Alarms . . . . . . . . . . . . . . . . . . . . .5-7  
Regulatory Information for CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . .5  
Regulatory Information for Smoke Alarms . . . . . . . . . . . . . . . . . . . . . . .5-6  
Recommended Locations for Smoke Alarms . . . . . . . . . . . . . . . . . . . .5-6  
About Smoke Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7  
Special Compliance Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7  
General Limitations Of Smoke/CO Alarms . . . . . . . . . . . . . . . . . . . . . . . . .6-7  
Troubleshooting Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7  
Horn: 4 beeps, pause, 4 beeps, voice*  
Power/Smoke LED: Off  
CO LED: Flashes Red  
FINDING THE SOURCE OF CO AFTER AN ALARM  
Carbon monoxide is an odorless, invisible gas, which often makes it difficult to  
locate the source of CO after an alarm. These are a few of the factors that can  
make it difficult to locate sources of CO:  
USING THE SILENCE FEATURES  
INSTALLING SMOKE ALARMS IN MOBILE HOMES  
For minimum security install one Smoke Alarm as close to each sleeping area as  
possible. For more security, put one unit in each room. Many older mobile homes  
(especially those built before 1978) have little or no insulation. If your mobile home  
is not well insulated, or if you are unsure of the amount of insulation, it is important  
to install units on inside walls only. Smoke Alarms should be installed where  
temperatures normally remain between 40˚ F (4˚ C) and 100˚ F (38˚ C).  
Never remove the batteries to quiet an unwanted alarm. Removing the  
batteries disables the alarm and removes your protection.  
*NOTE: If unit goes into CO alarm, the regular 4 beeps-brief pause cycle will  
repeat for four minutes. After four minutes, the pause will increase to one minute.  
House well ventilated before the investigator arrives.  
Problem caused by “backdrafting.”  
Transient CO problem caused by special circumstances.  
The Silence Feature is intended to temporarily silence the horn while you  
identify and correct the problem. Do not use the Silence Feature in emergency  
situations. It will not correct a CO problem or extinguish a fire.  
Smoke is Detected  
Voice: “Warning, evacuate smoke in [Location, example: “Kitchen”].  
The following information applies to all five types of buildings listed below:  
Evacuate.”  
AGENCY PLACEMENT RECOMMENDATIONS  
Because CO may dissipate by the time an investigator arrives, it may be diffi-  
cult to locate the source of CO. BRK Brands, Inc. shall not be obligated to  
pay for any carbon monoxide investigation or service call.  
In new construction, most building codes require the use of AC or AC/DC  
powered Smoke Alarms only. AC, AC/DC, or DC powered Smoke Alarms can  
be used in existing construction as specified by local building codes. Refer to  
NFPA 72 (National Fire Alarm Code) and NFPA 101 (Life Safety Code), local  
building codes, or consult your Fire Department for detailed fire protection  
requirements in buildings not defined as “households.”  
1. Single-Family Residence: Single family home, townhouse. It is recommend-  
ed this unit be installed on every level of the home, in every bedroom, and in  
each bedroom hallway.  
2. Multi-Family or Mixed Occupant Residence: Apartment building,  
condominium. This unit is suitable for use in individual apartments or condos,  
provided a primary fire detection system already exists to meet fire detection  
requirements in common areas like lobbies, hallways, or porches. Using this  
unit in common areas may not provide sufficient warning to all residents or  
meet local fire protection ordinances/regulations.  
3. Institutions: Hospitals, day care facilities, long-term health care facilities.  
This unit is suitable for use in individual patient sleeping/resident rooms,  
provided a primary fire detection system already exists to meet fire detection  
requirements in common areas like lobbies, hallways, or porches. Using this  
unit in common areas may not provide sufficient warning to all residents or  
meet local fire protection ordinances/regulations.  
4. Hotels and Motels: Also boarding houses and dormitories. This unit is  
suitable for use inside individual sleeping/resident rooms, provided a primary  
fire detection system already exists to meet fire detection requirements in  
common areas like lobbies, hallways, or porches. Using this unit in common  
areas may not provide sufficient warning to all residents or meet local fire  
protection ordinances/regulations.  
5. Warehouses/Commercial Buildings: DO NOT use this Smoke/CO Alarm in  
warehouses, industrial or commercial buildings, special-purpose non-residential  
buildings, RVs, boats, or airplanes. This Smoke/CO Alarm is specifically  
designed for residential use, and may not provide adequate protection in  
non-residential applications.  
The Silence Feature can temporarily quiet an unwanted alarm for several  
minutes. You can silence this Smoke/CO Alarm two ways:  
Horn: 3 beeps, pause, 3 beeps, voice  
Power/Smoke LED: Flashes Red  
CO LED: Off  
This equipment should be installed in accordance with NFPA (National Fire  
Protection Association) 72 and 101. National Fire Protection Association,  
One Batterymarch Park, Quincy, MA 02269-9101. Additional local building  
and regulatory codes may apply in your area. Always check compliance  
requirements before beginning any installation.  
Standards: Underwriters Laboratories Inc. Single and Multiple Station Smoke  
Alarms 217.  
1. Manually: Press the Test/Silence button on the alarm cover for at least  
POTENTIAL SOURCES OF CO IN THE HOME  
3-5 seconds.  
Smoke Alarm is Silenced  
Voice: Silent.  
CO Alarm is Silenced  
Voice: Silent.  
Fuel-burning appliances like:  
portable heater, gas or wood  
burning fireplace, gas kitchen  
range or cooktop, gas clothes dryer.  
2. Using Your Remote Control: Standing no further than 20 feet (6 meters)  
away from the Alarm, aim your IR remote at the Alarm and press the  
CHANNEL or VOLUME button for at least 3-5 seconds.  
Horn: Off  
Power/Smoke LED: Flashes Red  
CO LED: Off  
Horn: Off  
Power/Smoke LED: Off  
CO LED: Flashes Red  
8. Before attaching the Alarm to  
the bracket, insert the two (2)  
AA batteries (included) into the  
battery compartment. Match  
the terminals on the end of the  
battery with the terminals on  
the unit. Match “+” to “+” and  
“-” to “-.” If the batteries are  
not fully inserted, the unit  
Damaged or insufficient venting:  
corroded or disconnected water heater  
vent pipe, leaking chimney pipe or flue,  
or cracked heat exchanger, blocked or  
clogged chimney opening.  
Improper use of appliance/device:  
operating a barbecue grill or vehicle  
in an enclosed area (like a garage or  
screened porch).  
Transient CO Problems: “transient” or on-again-off-again CO problems can  
be caused by outdoor conditions and other special circumstances.  
The following conditions can result in transient CO situations:  
1. Excessive spillage or reverse venting of fuel appliances caused by outdoor  
conditions such as:  
After the Test/Silence or remote control button is released, the Red LED blinks  
during the silence mode.  
NFPA 72 (National Fire Code)  
Smoke Alarms shall be installed in each separate sleeping room, outside each  
sleeping area in the immediate vicinity of the bedrooms and on each additional  
story of the family living unit, including basements and excluding crawl spaces  
and unfinished attics.  
In new construction, Alarms shall be so arranged that operation of any one Alarm  
shall cause the operation of all Alarms within the dwelling.  
Smoke Detection-Are More Smoke Alarms Desirable? The required number of  
Smoke Alarms might not provide reliable early warning protection for those areas  
separated by a door from the areas protected by the required Smoke Alarms.  
For this reason, it is recommended that the householder consider the use of  
additional Smoke Alarms for those areas for increased protection. The additional  
areas include the basement, bedrooms, dining room, furnace room, utility room,  
and hallways not protected by the required Smoke Alarms. The installation of  
Smoke Alarms in kitchens, attics (finished or unfinished), or garages is not  
normally recommended, as these locations occasionally experience conditions  
that can result in improper operation.  
If the Alarm does not respond to your remote control, there may be an  
obstruction between you and the Alarm, you may be standing too far  
away, or your remote control may not be compatible.  
INSTALLATION  
WHERE TO INSTALL THIS ALARM  
Minimum coverage for Smoke Alarms, as recommended by the National Fire  
Protection Association (NFPA), is one Smoke Alarm on every floor, in every  
sleeping area, and in every bedroom (See “Regulatory Information For Smoke  
Alarms” for details on the NFPA recommendations).  
For CO Alarms, the National Fire Protection Association (NFPA) recommends  
that a CO Alarm should be centrally located outside of each separate sleeping  
area in the immediate vicinity of the bedrooms. For added protection, install  
additional CO Alarms in each separate bedroom, and on every level of your  
home.  
NOTE: For added protection, install an additional Smoke/CO Alarm at least  
15 feet (4.6 meters) away from the furnace or fuel burning heat source where  
possible. In smaller homes or in manufactured homes where this distance cannot  
be maintained, install the Alarm as far away as possible from the furnace or other  
fuel burning source. Installing the Alarm closer than 15 feet (4.6 meters) will not  
harm the Alarm, but may increase the frequency of unwanted alarms.  
When the Smoke Alarm is Silenced  
When the CO Alarm is Silenced  
cannot receive battery power.  
The Smoke Alarm will remain silent  
for up to 15 minutes, then return to  
normal operation.  
The CO alarm will remain silent for  
up to 4 minutes.  
NOTE: The unit may beep briefly when you install the batteries. This is normal.  
The GREEN Light flashes about every 60 seconds when the unit is  
receiving battery power.  
After 4 minutes, if CO levels remain  
potentially dangerous the horn will  
start sounding again.  
If the smoke has not cleared–or  
continues to increase–the device  
will go back into alarm.  
The battery door will resist closing unless batteries are installed. This  
warns you the unit will not operate without batteries.  
9. Attach the Smoke/CO Alarm to the mounting  
bracket. Line up the guides on the alarms  
base with the guides on the mounting bracket.  
When guides are lined up, turn the base  
clockwise (right) until it snaps into place.  
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-7  
© 2006 BRK Brands, Inc., a Subsidiary of Jarden Corporation. All rights reserved.  
BRK Brands, Inc., 3901 Liberty Street Road, Aurora, IL 60504-8122  
Consumer Affairs: (800) 323-9005 • www.firstalert.com  
Wind direction and/or velocity, including high, gusty winds. Heavy air in  
the vent pipes (cold/humid air with extended periods between cycles).  
Negative pressure differential resulting from the use of exhaust fans.  
Several appliances running at the same time competing for limited fresh  
air.  
SILENCING THE LOW BATTERY WARNING  
This silence feature can temporarily quiet the low battery warning “chirp” for  
up to 8 hours. You can silence the low battery warning “chirp” two ways:  
California State Fire Marshal (CSFM)  
®
All First Alert Smoke Alarms conform to regulatory requirements,  
Early warning detection is best achieved by the installation of fire detection  
equipment in all rooms and areas of the household as follows: A Smoke Alarm  
installed in each separate sleeping area (in the vicinity, but outside bedrooms),  
and Heat or Smoke Alarms in the living rooms, dining rooms, bedrooms,  
kitchens, hallways, finished attics, furnace rooms, closets, utility and storage  
rooms, basements, and attached garages.  
including UL217 and are designed to detect particles of combustion.  
Smoke particles of varying number and size are produced in all fires.  
Vent pipe connections vibrating loose from clothes dryers, furnaces, or  
1. Manually: Press the Test/Silence button on the alarm cover.  
NOTE: Once the Smoke Alarm is snapped  
onto the mounting bracket, you can rotate  
the Smoke Alarm to adjust the alignment.  
water heaters.  
Ionization technology is generally more sensitive than photoelectric  
technology at detecting small particles, which tend to be produced  
in greater amounts by flaming fires, which consume combustible  
materials rapidly and spread quickly. Sources of these fires may include  
paper burning in a wastebasket, or a grease fire in the kitchen.  
Photoelectric technology is generally more sensitive than ionization  
technology at detecting large particles, which tend to be produced in  
greater amounts by smoldering fires, which may smolder for hours  
before bursting into flame. Sources of these fires may include cigarettes  
burning in couches or bedding.  
In general, install combination Smoke and Carbon Monoxide Alarms:  
2. Using Your Remote Control: Standing no further than 20 feet (6 meters)  
away from the Smoke/CO Alarm, aim your IR remote at the Alarm and  
press the CHANNEL or VOLUME button for at least 3-5 seconds.  
Obstructions in or unconventional vent pipe designs which can amplify  
the above situations.  
On every level of your home, including finished attics and basements.  
Inside every bedroom, especially if people sleep with the door partly or  
completely closed.  
In the hall near every sleeping area. If your home has multiple sleeping  
areas, install a unit in each. If a hall is more than 40 feet (12 meters) long,  
install a unit at each end.  
At the top of first-to-second floor stairs.  
At the bottom of the basement stairs.  
10. Test the Smoke/CO Alarm. See “Weekly  
Testing” for details.  
2. Extended operation of unvented fuel burning devices (range, oven, fireplace).  
3. Temperature inversions, which can trap exhaust close to the ground.  
4. Car idling in an open or closed attached garage, or near a home.  
These conditions are dangerous because they can trap exhaust in your home.  
Since these conditions can come and go, they are also hard to recreate during  
a CO investigation.  
Once the low battery warning “chirp” silence feature is activated, the unit  
continues to flash the Green light twice a minute for 8 hours. After 8 hours, the  
low battery “chirp” will resume. Replace the batteries as soon as possible;  
this unit will not operate without battery power!  
To deactivate this feature: Press the Test/Silence button or use your remote  
control again. The unit will go into Test Mode and the low battery warning will  
resume (LED flashes and unit sounds “chirp” once a minute).  
GENERAL LIMITATIONS OF SMOKE/CO ALARMS  
This Smoke/CO Alarm is intended for residential use. It is not intended for use  
in industrial applications where Occupational Safety and Health Administration  
(OSHA) requirements for Carbon Monoxide Alarms must be met. The Smoke  
Alarm portion of this device is not intended to alert hearing impaired residents.  
Special purpose Smoke Alarms should be installed for hearing impaired resi-  
dents (CO Alarms are not yet available for the hearing impaired).  
Smoke/CO Alarms may not waken all individuals. Practice the escape  
plan at least twice a year, making sure that everyone is involved – from kids to  
grandparents. Allow children to master fire escape planning and practice before  
holding a fire drill at night when they are sleeping. If children or others do not  
readily waken to the sound of the Smoke/CO Alarm, or if there are infants or  
family members with mobility limitations, make sure that someone is assigned  
to assist them in fire drill and in the event of an emergency. It is recommended  
that you hold a fire drill while family members are sleeping in order to deter-  
mine their response to the sound of the Smoke/CO Alarm while sleeping and to  
determine whether they may need assistance in the event of an emergency.  
Smoke/CO Alarms cannot work without power. Battery operated units cannot  
work if the batteries are missing, disconnected or dead, if the wrong type of bat-  
teries are used, or if the batteries are not installed correctly. AC units cannot work  
if the AC power is cut off for any reason (open fuse or circuit breaker, failure along  
a power line or at a power station, electrical fire that burns the electrical wires,  
etc.). If you are concerned about the limitations of battery or AC power, install both  
types of units.  
This Smoke/CO Alarm will not sense smoke or CO that does not reach  
the sensors. It will only sense smoke or CO at the sensor. Smoke or CO may  
be present in other areas. Doors or other obstructions may affect the rate at  
which CO or smoke reaches the sensors. If bedroom doors are usually closed  
at night, we recommend you install an alarm device (Combination CO and  
Smoke Alarm, or separate CO Alarms and Smoke Alarms) in each bedroom  
and in the hallway between them.  
not give adequate early warning. Recommended minimum protection is one  
alarm device in every sleeping area, every bedroom, and on every level of your  
home. Some experts recommend battery powered Smoke and CO Alarms be  
used in conjunction with interconnected AC powered Smoke Alarms. For  
details, see “About Smoke Alarms” for details.  
Smoke/CO Alarms may not be heard. The alarm horn loudness meets or  
exceeds current UL standards of 85 dB at 10 feet (3 meters). However, if  
the Smoke/CO Alarm is installed outside the bedroom, it may not wake up  
a sound sleeper or one who has recently used drugs or has been drinking  
alcoholic beverages. This is especially true if the door is closed or only partly  
open. Even persons who are awake may not hear the alarm horn if the sound  
is blocked by distance or closed doors. Noise from traffic, stereo, radio,  
television, air conditioner, or other appliances may also prevent alert persons  
from hearing the alarm horn. This Smoke/CO Alarm is not intended for people  
who are hearing impaired.  
The Alarm may not have time to alarm before the fire itself causes  
damage, injury, or death, since smoke from some fires may not reach  
the unit immediately. Examples of this include persons smoking in bed,  
children playing with matches, or fires caused by violent explosions  
resulting from escaping gas.  
This Smoke/CO Alarm is not a substitute for life insurance. Though this  
Smoke/CO Alarm warns against increasing CO levels or the presence of  
smoke, BRK Brands, Inc. does not warrant or imply in any way that they will  
protect lives. Homeowners and renters must still insure their lives.  
IF YOUR SMOKE/CO ALARM SOUNDS  
WHAT TO DO FIRST–IDENTIFY THE TYPE OF ALARM  
For maximum protection, use both types of Smoke Alarms on each level  
and in every bedroom of your home.  
For additional coverage, install Alarms in all rooms, halls, and storage  
areas, where temperatures normally remain between 40˚ F and 100˚ F  
(4˚ C and 38˚ C).  
HOW CAN I PROTECT MY FAMILY FROM  
CO POISONING?  
Type of Alarm  
What You See and Hear  
WEEKLY TESTING  
A CO Alarm is an excellent means of protection. It monitors the air and sounds  
a loud alarm before Carbon Monoxide levels become threatening for average,  
healthy adults.  
Carbon Monoxide (CO)  
Voice: “Warning, evacuate carbon  
monoxide in [Location,  
INTRODUCTION  
FIRE SAFETY TIPS  
Recommended Placement  
SUGGESTED AREAS FOR INSTALLING  
example: “Kitchen”]. Evacuate.”  
NEVER use an open flame of any kind to test this unit. You might  
accidentally damage or set fire to the unit or to your home. The  
built-in test switch accurately tests the unit’s operation as required  
by Underwriters Laboratories, Inc. (UL). NEVER use vehicle exhaust!  
Exhaust may cause permanent damage and voids your warranty.  
A CO Alarm is not a substitute for proper maintenance of home appliances.  
To help prevent CO problems and reduce the risk of CO poisoning:  
SMOKE ALARMS, CO ALARMS, AND COMBO UNITS  
____ ppm.”  
Follow safety rules and prevent hazardous situations: 1) Use smoking  
materials properly. Never smoke in bed. 2) Keep matches or lighters away from  
children; 3) Store flammable materials in proper containers; 4) Keep electrical  
appliances in good condition and don’t overload electrical circuits; 5) Keep  
stoves, barbecue grills, fireplaces and chimneys grease- and debris-free;  
6) Never leave anything cooking on the stove unattended; 7) Keep portable  
heaters and open flames, like candles, away from flammable materials;  
8) Don’t let rubbish accumulate.  
Horn: 4 beeps, pause, 4 beeps, voice  
Power/Smoke LED: Off  
CO LED: Flashes Red  
KEY:  
Clean chimneys and flues yearly. Keep them free of debris, leaves, and  
nests for proper air flow. Also, have a professional check for rust and  
corrosion, cracks, or separations. These conditions can prevent proper  
air movement and cause backdrafting. Never “cap” or cover a chimney  
in any way that would block air flow.  
SMOKE ALARMS  
DO NOT stand close to the Alarm when the horn is sounding.  
Exposure at close range may be harmful to your hearing. When  
testing, step away when horn starts sounding.  
SMOKE ALARM WITH  
SILENCE FEATURE  
Smoke  
Voice: “Warning, evacuate smoke in  
[Location, example: “Kitchen”].  
Evacuate.”  
Horn: 3 beeps, pause, 3 beeps, voice  
Power/Smoke LED: Flashes Red  
CO LED: Off  
CO ALARMS  
Test and maintain all fuel-burning equipment annually. Many local gas or  
oil companies and HVAC companies offer appliance inspections for a  
nominal fee.  
Keep alarms clean, and test them weekly. Replace alarms immediately if they  
are not working properly. Smoke Alarms that do not work cannot alert you to a  
fire. Keep at least one working fire extinguisher on every floor, and an additional  
one in the kitchen. Have fire escape ladders or other reliable means of escape  
from an upper floor in case stairs are blocked.  
BOTH, OR COMBINATION  
SMOKE/CO ALARMS  
It is important to test this unit every week to make sure it is working  
properly. Using the test button is the recommended way to test this  
Smoke/CO Alarm.  
Make regular visual inspections of all fuel-burning appliances. Check  
appliances for excessive rust and scaling. Also check the flame on the  
burner and pilot lights. The flame should be blue. A yellow flame means  
fuel is not being burned completely and CO may be present. Keep the  
blower door on the furnace closed. Use vents or fans when they are  
available on all fuel-burning appliances. Make sure appliances are vent-  
ed to the outside. Do not grill or barbecue indoors, or in garages or on  
screen porches.  
Suggested locations are based on  
NFPA recommendations (NFPA 72  
for Smoke Alarms and NFPA 720 for  
Carbon Monoxide Alarms). Always  
refer to national and local codes  
before beginning any installation.  
1
You can test this Smoke/CO Alarm two ways:  
BASIC SAFETY INFORMATION  
IF THE CO ALARM SOUNDS  
1. Manually: Press and hold the Test/Silence button on the  
Alarm cover until Alarm Voice says “Testing” (typically  
3-5 seconds).  
2. Using Your Remote Control: Standing no further than  
20 feet (6 meters) away from the Smoke/CO Alarm, aim  
your IR remote at the Alarm and press the CHANNEL or  
VOLUME button until Alarm Voice says “Testing.  
If the Alarm does not respond to your remote control,  
there may be an obstruction between you and the Alarm, you may be  
standing too far away, or your remote control may not be compatible.  
During testing, you will see and hear the following sequence:  
• The Alarm Voice will say “Testing.” The Horn will sound 3 beeps,  
pause, 3 beeps. The Alarm Voice will say “Warning, evacuate smoke in  
[Location, example: “Kitchen”]. Evacuate.” The Power/Smoke LED  
flashes Red and the CO LED will be Off.  
This Smoke/CO Alarm has a limited life. Although this Smoke/CO Alarm  
and all of its parts have passed many stringent tests and are designed to be  
as reliable as possible, any of these parts could fail at any time. Therefore, you  
must test this device weekly. The unit should be replaced immediately if it is not  
operating properly.  
This Smoke/CO Alarm is not foolproof. Like all other electronic devices, this  
Smoke/CO Alarm has limitations. It can only detect smoke or CO that reaches  
the sensors. It may not give early warning of the source of smoke or CO is in a  
remote part of the home, away from the alarm device.  
In new construction AC and AC/DC smoke alarms MUST  
be interconnected to meet NFPA recommendations.  
“ALARM-MOVE TO FRESH AIR”  
• Dangers, Warnings, and Cautions alert you to important operating  
instructions or to potentially hazardous situations. Pay special  
attention to these items.  
• This Smoke/CO Alarm is approved for use in single-family  
residences. It is NOT designed for marine or RV use.  
When installing on the wall, the top edge of Smoke Alarms should be  
placed between 4 inches (102 mm) and 12 inches (305 mm) from the  
wall/ceiling line.  
When installing on the ceiling, place the alarm as close to the center as  
possible.  
If you hear the CO alarm horn and the CO red light is flashing,  
move everyone to a source of fresh air.  
Check for exhaust backflow from CO sources. Check the draft hood on  
an operating furnace for a backdraft. Look for cracks on furnace heat  
exchangers.  
DO NOT remove the batteries!  
This Smoke/CO Alarm may not sense smoke or CO on another level of  
the home. Example: This alarm device, installed on the second floor, may not  
sense smoke or CO in the basement. For this reason, one alarm device may  
2
Check the house or garage on the other side of shared wall.  
In either case, install at least 4 inches (102 mm) from where the wall and  
ceiling meet. See Avoiding Dead Air Spaces” for more information.  
Actuation of your CO Alarm indicates the presence of carbon monoxide  
(CO) which can kill you. In other words, when your CO Alarm sounds, you  
must not ignore it!  
Keep windows and doors open slightly. If you suspect that CO is  
escaping into your home, open a window or a door. Opening windows  
and doors can significantly decrease CO levels.  
This combination Smoke/Carbon Monoxide Alarm has two separate  
alarms. The CO Alarm is not designed to detect fire or any other gas.  
It will only indicate the presence of carbon monoxide gas at the  
sensor. Carbon monoxide gas may be present in other areas. The  
Smoke Alarm will only indicate the presence of smoke that reaches  
the sensor. The Smoke Alarm is not designed to sense gas, heat or  
flames.  
NOTE: For any location, make sure no door or other obstruction could keep  
carbon monoxide or smoke from reaching the Alarm.  
TROUBLESHOOTING GUIDE  
In addition, familiarize yourself with all enclosed materials. Read this  
manual in its entirety, and make sure you understand what to do if your  
CO Alarm sounds.  
IF THE CO ALARM SIGNAL SOUNDS:  
1. Operate the Test/Silence button.  
If the Alarm...  
Problem...  
You should...  
Installing Smoke/CO Alarms in Mobile Homes  
For minimum security install one Smoke/CO Alarm as close to each sleeping  
area as possible. For more security, put one unit in each room. Many older  
mobile homes (especially those built before 1978) have little or no insulation.  
If your mobile home is not well insulated, or if you are unsure of the amount  
of insulation, it is important to install units on inside walls only.  
Horn "chirps" about once per minute;  
Voice: "Replace battery in [Location]" every 5 hours  
Low battery warning.  
Install two new AA batteries*.  
2. Call your emergency services, fire department or 911. Write down the  
number of your local emergency service here:  
• Next the Horn will sound 4 beeps, pause, 4 beeps. The Alarm Voice  
will say “Warning, evacuate carbon monoxide in [Location, example:  
“Kitchen”]. Evacuate.” The Power/Smoke LED will be Off and the CO  
LED flashes Red.  
REGULATORY INFORMATION FOR  
SMOKE/CO ALARMS  
REGULATORY INFORMATION FOR CO ALARMS  
WHAT LEVELS OF CO CAUSE AN ALARM?  
Underwriters Laboratories Inc. Standard UL2034 requires residential CO  
Alarms to sound when exposed to levels of CO and exposure times as  
described below. They are measured in parts per million (ppm) of CO over  
time (in minutes).  
• This Smoke/CO Alarm cannot operate without working batteries.  
Removing the batteries for any reason, or failing to replace the  
batteries at the end of their service life, removes your protection.  
• NEVER ignore any alarm. See “If Your Smoke/CO Alarm Sounds”  
for more information on how to respond to an alarm. Failure to  
respond can result in injury or death.  
• The Silence Features are for your convenience only and will not  
correct a problem. See "Using the Silence Features" for details.  
Always check your home for a potential problem after any alarm.  
Failure to do so can result in injury or death.  
Test this Smoke/CO Alarm once a week. If the Alarm ever fails to  
test correctly, have it replaced immediately! If the Alarm is not  
working properly, it cannot alert you to a problem.  
• This product is intended for use in ordinary indoor locations of  
family living units. It is not designed to measure CO levels in  
compliance with Occupational Safety and Health Administration  
(OSHA) commercial or industrial standards. Individuals with  
medical conditions that may make them more sensitive to carbon  
monoxide may consider using warning devices which provide  
audible and visual signals for carbon monoxide concentrations  
under 30 ppm. For additional information on carbon monoxide  
and your medical condition contact your physician.  
Horn does three rapid "chirps" every minute;  
Voice: "Detector error in [Location, example  
"Kitchen"], please see manual" repeated every  
5 hours; LED has 3 rapid flashes with "chirps".  
Device is not working properly, and needs to be  
replaced.  
Units under warranty should be returned to  
manufacturer for replacement. See “Limited  
Warranty” for details.  
__________________________________________________________________  
3. Immediately move to fresh air—outdoors or by an open door or window.  
Do a head count to check that all persons are accounted for. Do not re-  
enter the premises, or move away from the open door or window until the  
emergency services responder has arrived, the premises have been aired  
out, and your CO Alarm remains in its normal condition.  
If the unit does not alarm, make sure the batteries are correctly installed, and  
test again. If the unit still does not alarm, replace it immediately.  
WHERE THIS ALARM SHOULD NOT BE INSTALLED  
Do NOT locate this Smoke/CO Alarm:  
Carbon Monoxide Alarm ONLY:  
CO Alarm goes back into alarm 4 minutes after you  
Silence it.  
In a location where it could be easily triggered when using your remote to  
operate your TV, VCR, etc.  
In garages, furnace rooms, crawl spaces and unfinished attics. Avoid  
extremely dusty, dirty or greasy areas.  
CO levels indicate a potentially dangerous situation.  
IF YOU ARE FEELING SYMPTOMS OF CO  
POISONING, EVACUATE your home and call 911  
or the Fire Department. Refer to "If The CO Alarm  
Sounds" for details.  
REGULAR MAINTENANCE  
4. After following steps 1-3, if your CO Alarm reactivates within a 24-hour  
period, repeat steps 1-3 and call a qualified appliance technician to investi-  
gate for sources of CO from fuel-burning equipment and appliances, and  
inspect for proper operation of this equipment. If problems are identified  
during this inspection have the equipment serviced immediately. Note any  
combustion equipment not inspected by the technician, and consult the  
manufacturers’ instructions, or contact the manufacturers directly, for more  
information about CO safety and this equipment. Make sure that motor  
vehicles are not, and have not, been operating in an attached garage or  
adjacent to the residence. Write down the number of a qualified appliance  
technician here:  
UL2034 Required Alarm Points*:  
This unit has been designed to be as maintenance-free as possible, but there  
are a few simple things you must do to keep it working properly.  
If the alarm is exposed to 400 ppm of CO, IT MUST ALARM BETWEEN  
4 and 15 MINUTES.  
If the alarm is exposed to 150 ppm of CO, IT MUST ALARM BETWEEN  
10 and 50 MINUTES.  
If the alarm is exposed to 70 ppm if CO, IT MUST ALARM BETWEEN  
60 and 240 MINUTES.  
Where combustion particles are produced. Combustion particles form  
when something burns. Areas to avoid include poorly ventilated kitchens,  
garages, and furnace rooms. Keep units at least 20 feet (6 meters) from the  
sources of combustion particles (stove, furnace, water heater, space heater)  
if possible. In areas where a 20-foot (6 meter) distance is not possible – in  
modular, mobile, or smaller homes, for example – it is recommended  
the Smoke Alarm be placed as far from these fuel-burning sources as  
possible. The placement recommendations are intended to keep these  
Alarms at a reasonable distance from a fuel-burning source, and thus  
reduce “unwanted” alarms. Unwanted alarms can occur if a Smoke Alarm  
is placed directly next to a fuel-burning source. Ventilate these areas as  
much as possible.  
Within 5 feet (1.5 meters) of any cooking appliance. In air streams near  
kitchens. Air currents can draw cooking smoke into the smoke sensor and  
cause unwanted alarms.  
In extremely humid areas. This Alarm should be at least 10 feet (3 meters)  
from a shower, sauna, humidifier, vaporizer, dishwasher, laundry room,  
utility room, or other source of high humidity.  
CO Alarm sounds frequently even though no high  
levels of CO are revealed in an investigation.  
The CO Alarm may be improperly located. Refer to  
“Where to Install This Alarm” for details.  
Relocate your Alarm. If frequent alarms continue,  
have home rechecked for potential CO problems.  
You may be experiencing an intermittent  
CO problem.  
Use only the replacement batteries listed below. The unit may not  
operate properly with other batteries. Never use rechargeable batteries  
since they may not provide a constant charge.  
Test it at least once a week.  
* Approximately 10% COHb exposure at levels of 10% to 95% Relative  
Humidity (RH).  
The unit is designed not to alarm when exposed to a constant level  
of 30 ppm for 30 days.  
Smoke Alarm ONLY:  
Clean the Smoke/CO Alarm at least once a month; gently vacuum the  
outside of the Smoke/CO Alarm using your household vacuums soft  
brush attachment. A can of clean compressed air (sold at computer or  
office supply stores) may also be used. Follow manufacturer instructions  
for use. Test the Smoke/CO Alarm. Never use water, cleaners or solvents  
since they may damage the unit.  
If the Smoke/CO Alarm becomes contaminated by excessive dirt, dust  
and/or grime, and cannot be cleaned to avoid unwanted alarms, replace  
the unit immediately.  
Smoke Alarm sounds when no smoke is visible.  
Unwanted alarm may be caused by non-emergency  
source like cooking smoke.  
Silence Alarm using remote control or manual  
button; clean the Alarms cover with a soft, clean  
cloth. If frequent unwanted alarms continue,  
relocate your Alarm. Alarm may be too close to a  
kitchen, cooking appliance, or steamy bathroom.  
__________________________________________________________________  
NOTE: A qualified appliance technician is defined as “a person, firm,  
corporation, or company that either in person or through a representative, is  
engaged in and responsible for the installation, testing, servicing, or replace-  
ment of heating, ventilation, air conditioning (HVAC) equipment, combustion  
appliances and equipment, and/or gas fireplaces or other decorative  
combustion equipment.”  
CO Alarms are designed to alarm before there is an immediate life threat.  
Since you cannot see or smell CO, never assume it’s not present.  
*For a list of acceptable replacement batteries, see “Regular Maintenance.”  
STEP BY STEP GUIDE TO PROGRAMMING  
THIS ALARM  
For First Time and When Changing Batteries  
An exposure to 100 ppm of CO for 20 minutes may not affect average,  
healthy adults, but after 4 hours the same level may cause headaches.  
An exposure to 400 ppm of CO may cause headaches in average, healthy  
adults after 35 minutes, but can cause death after 2 hours.  
If you have questions that cannot be answered by reading this manual, call Consumer Affairs at 1-800-323-9005, M-F 7:30 a.m. to 5:00 p.m. (CST)  
Relocate the unit if it sounds frequent unwanted alarms. See “Where This  
Alarm Should Not Be Installed” for details.  
AFTER AN ALARM  
Action:  
Alarm Will Say:  
In direct sunlight.  
Standards: Underwriters Laboratories Inc. Single and Multiple Station carbon  
monoxide alarms UL2034.  
Choosing a replacement battery:  
LIMITED WARRANTY  
After the emergency responders arrive, the premises aired out, and your CO  
Alarm remains in its normal condition, you can check what the highest carbon  
monoxide level sensed was:  
1. Insert batteries (2, AA batteries).  
“Welcome, First Alert Carbon  
Monoxide and Smoke Alarm.”  
In turbulent air, like near ceiling fans or open windows. Blowing air may  
prevent CO or smoke from reaching the sensors.  
In areas where temperature is colder than 40˚ F (4˚ C) or hotter than 100˚ F  
(38˚ C). These areas include non-airconditioned crawl spaces, unfinished  
attics, uninsulated or poorly insulated ceilings, porches, and garages.  
In insect infested areas. Insects can clog the openings to the sensing  
chamber.  
Less than 12 inches (305 mm) away from fluorescent lights. Electrical  
“noise” can interfere with the sensor.  
Your Smoke/CO Alarm requires two standard AA batteries. The following  
batteries are acceptable as replacements: Eveready Energizer E91. These  
batteries are available at many local retail stores.  
BRK Brands, Inc., ("BRK") the maker of First Alert® brand products warrants that for a period of five years from the date of purchase, this product will be free from  
defects in material and workmanship. BRK, at its option, will repair or replace this product or any component of the product found to be defective during the warranty  
period. Replacement will be made with a new or remanufactured product or component. If the product is no longer available, replacement may be made with a similar  
product of equal or greater value. This is your exclusive warranty.  
According to Underwriters Laboratories Inc. UL2034, Section 1-1.2: “Carbon  
monoxide alarms covered by these requirements are intended to respond to the  
presence of carbon monoxide from sources such as, but not limited to, exhaust  
from internal-combustion engines, abnormal operation of fuel-fired appliances,  
and fireplaces. CO Alarms are intended to alarm at carbon monoxide levels  
below those that could cause a loss of ability to react to the dangers of Carbon  
Monoxide exposure.” This CO Alarm monitors the air at the Alarm, and is  
designed to alarm before CO levels become life threatening. This allows you  
precious time to leave the house and correct the problem. This is only possible  
if Alarms are located, installed, and maintained as described in this manual.  
Gas Detection at Typical Temperature and Humidity Ranges: The CO Alarm  
is not formulated to detect CO levels below 30 ppm typically. UL tested for false  
alarm resistance to Methane (500 ppm), Butane (300 ppm), Heptane (500 ppm),  
Ethyl Acetate (200 ppm), Isopropyl Alcohol (200 ppm) and Carbon Dioxide (5000  
ppm). Values measure gas and vapor concentrations in parts per million.  
“No location programmed” if first  
time or “[Location, example:  
“Kitchen”] location programmed”  
when changing batteries.  
To select location, press and hold  
test button now.”  
Action:  
1. Press & Hold Test Button  
Alarm Will Say:  
“Highest carbon monoxide level was  
___ ppm. Please see manual.”  
To clear highest carbon monoxide  
level, press and hold test button  
now.”  
This warranty is valid for the original retail purchaser from the date of initial retail purchase and is not transferable. Keep the original sales receipt. Proof of purchase is  
required to obtain warranty performance. BRK dealers, service centers, or retail stores selling BRK products do not have the right to alter, modify or any way change the  
terms and conditions of this warranty.  
This warranty does not cover normal wear of parts or damage resulting from any of the following: negligent use or misuse of the product, use on improper voltage or  
current, use contrary to the operating instructions, disassembly, repair or alteration by anyone other than BRK or an authorized service center. Further, the warranty  
does not cover Acts of God, such as fire, flood, hurricanes and tornadoes or any batteries that are included with this unit.  
BRK shall not be liable for any incidental or consequential damages caused by the breach of any express or implied warranty. Except to the extent prohibited by applicable  
law, any implied warranty of merchantability or fitness for a particular purpose is limited in duration to the duration of the above warranty. Some states, provinces or  
jurisdictions do not allow the exclusion or limitation of incidental or consequential damages or limitations on how long an implied warranty lasts, so the above limitations  
or exclusion may not apply to you. This warranty gives you specific legal rights, and you may also have other rights that vary from state to state or province to province.  
Actual battery service life depends on the Smoke/CO Alarm and the environ-  
ment in which it is installed. All the batteries specified above are acceptable  
replacement batteries for this unit. Regardless of the manufacturers suggested  
battery life, you MUST replace the battery immediately once the unit starts  
“chirping” (the “low battery warning”).  
2. Press & Hold Test Button, or use  
your IR remote control’s channel  
or volume button, if you would like  
to program the location or change  
the location of the Alarm. Release  
button after Alarm responds.  
To save location, press and hold  
test button after location is heard.”  
Alarm will speak list of locations  
(see below).  
In “dead air” spaces. See “Avoiding Dead Air Spaces.  
2. Press & Hold Test Button, if you  
would like to clear the highest  
level sensed.  
If you would like to keep the  
highest level in memory, do not  
press anything.  
“Highest carbon monoxide level  
cleared.”  
To replace the batteries (without removing Alarm from the ceiling or wall):  
AVOIDING DEAD AIR SPACES  
“Dead air” spaces may prevent smoke from reaching the Smoke/CO Alarm.  
To avoid dead air spaces, follow installation recommendations below.  
1. Open the battery compartment.  
Alarm will say nothing.  
2. Press tabs A and B as shown in the diagram  
and remove each battery.  
3. After you hear the location of  
where you are placing the Alarm,  
Press & Hold the Test Button or  
use your IR remote control’s  
channel or volume button.  
“[Location, example: “Kitchen”]  
location saved.”  
If no location is chosen: “No location  
saved.”  
How to Obtain Warranty Service  
On ceilings, install Smoke/CO Alarms as close to the center of the ceiling as  
possible. If this is not possible, install the Smoke/CO Alarm at least 4 inches  
(102 mm) from the wall or corner.  
For wall mounting (if allowed by building codes), the top edge of Smoke/CO  
Alarms should be placed between 4 inches (102 mm) and 12 inches (305 mm)  
from the wall/ceiling line, below typical “dead air” spaces.  
On a peaked, gabled, or cathedral ceiling, install first Smoke/CO Alarm  
within 3 feet (0.9 meters) of the peak of the ceiling, measured horizontally.  
Additional Smoke/CO Alarms may be required depending on the length, angle,  
etc. of the ceiling's slope. Refer to NFPA 72 for details on requirements for  
sloped or peaked ceilings.  
3. Insert the new batteries, making sure they  
snap completely into the battery compartment.  
Audible Alarm: 85 dB minimum at 10 feet (3 meters).  
Service: If service is required, do not return the product to your retailer. In order to obtain warranty service, contact the Consumer Affairs Division at 1-800-323-9005,  
7:30 AM - 5:00 PM Central Standard Time, Monday through Friday. To assist us in serving you, please have the model number and date of purchase available when calling.  
25 Spur Drive, El Paso, TX 79906  
B
Match the terminals on the ends of the  
batteries with the terminals on the unit.  
REGULATORY INFORMATION FOR SMOKE ALARMS  
RECOMMENDED LOCATIONS FOR SMOKE ALARMS  
Installing Smoke Alarms in Single-Family Residences  
The National Fire Protection Association (NFPA), recommends one Smoke Alarm  
on every floor, in every sleeping area, and in every bedroom. In new construction,  
the Smoke Alarms must be AC powered and interconnected. See “Agency  
Placement Recommendations” for details.  
A
Battery: BRK Brands, Inc. make no warranty, express or implied, written or oral, including that of merchantability or fitness for any particular purpose with respect  
4. Close the battery compartment, and then test  
the unit by pressing the Test/Silence button or  
by using your remote control.  
to battery.  
Your Alarm has now been programmed for the location of your choice.  
Available locations:  
Basement  
Hallway  
Office  
Utility Room  
Child’s Bedroom  
Dining Room  
Family Room  
Guest Bedroom  
Kitchen  
For your records, please record:  
First Alert® is a registered trademark of the First Alert Trust.  
Living Room  
Master Bedroom  
No Location  
Date Purchased: ____________Where Purchased: ______________________  
Printed in Mexico M08-0048-006  
Q
10/06  
Continued...  
5
6
7
1
2
3
4
 
WHAT YOU WILL SEE AND HEAR WITH THIS ALARM  
Under Normal Operations  
OPTIONAL LOCKING FEATURES  
The optional locking features are designed to discourage unauthorized removal of the batteries or alarm. It is not necessary to  
activate the locks in single-family households where unauthorized battery or alarm removal is not a concern.  
Voice: Silent  
Power/Smoke LED: Flashes  
Green once a minute  
CO LED: Off  
STEP BY STEP GUIDE TO PROGRAMMING THIS ALARM  
AND USING THE OPTIONAL LOCKING FEATURES  
This Smoke/CO Alarm has two separate locking features: one to lock the battery compartment, and the other to lock the Smoke/CO Alarm to  
the mounting bracket. You can choose to use either feature independently, or use them both.  
Horn: Silent  
When You Test the Alarm  
M08-0086-001  
T
01/04  
Tools you will need: • Needle-nose pliers or utility knife • Standard flathead screwdriver.  
MODEL SCO7  
Voice: Testing.” “Warning, evacuate smoke in [Location,  
Printed in Mexico  
example: Kitchen]. Evacuate.”  
Both locking features use locking pins, which are molded into the mounting bracket. Depending on which  
locking features you use, remove one or both pins from the mounting bracket using needle-nose pliers or  
a utility knife.  
Horn: 3 beeps, pause, 3 beeps, voice  
Power/Smoke LED: Flashes Red  
All Rights Reserved. © 2004 BRK Brands, Inc.  
BRK Brands, Inc., 3901 Liberty Street Road, Aurora, IL 60504-8122  
CO LED: Off  
followed by  
Voice: Warning, evacuate carbon monoxide in [Location,  
example: Kitchen]. Evacuate.”  
Horn: 4 beeps, pause, 4 beeps, voice  
Power/Smoke LED: Off  
To permanently remove either locking pin, insert a flathead screwdriver between the locking pin and  
the lock, and pry the pin out of the lock.  
PROGRAMMING THE ALARM FOR THE FIRST TIME  
Action:  
Alarm Will Say:  
CO LED: Flashes Red  
TO LOCK THE BATTERY COMPARTMENT  
TO UN-LOCK THE BATTERY COMPARTMENT  
1. Insert batteries (2, AA  
batteries).  
Welcome, First Alert Carbon  
Monoxide and Smoke Alarm.  
No location programmed. To  
select location, press and hold  
test button now.”  
If Battery Becomes Low or is Missing  
Voice: Replace battery in [Location, example Kitchen].”  
Repeated every 5 hours  
Do not lock the battery compartment until you activate the  
1. Remove the Smoke/CO Alarm  
from the mounting bracket. If the  
unit is locked to the bracket, see  
the section To Un-Lock the  
Mounting Bracket.”  
battery and test the Smoke/CO Alarm.  
1. Install the batteries before attaching  
the Alarm to the bracket. Insert the  
two (2) AA batteries (included) into  
the battery compartment. Match the  
terminals on the end of the battery  
with the terminals on the unit.  
Horn: chirps once a minute  
Power/Smoke LED: Flashes approximately once a minute  
CO LED: Off  
If Alarm is Not Operating Properly  
2. Press & Hold Test Button, or  
use your IR remote controls  
channel or volume button, if  
you would like to program  
the location. Release button  
after Alarm responds.  
To save location, press and  
hold test button after location  
is heard.Alarm will speak list  
of locations (see below).  
2. Insert a flathead screwdriver under  
the head of the locking pin, and  
gently pry it out of the battery  
compartment lock. (If you plan to  
re-lock the battery compartment,  
save the locking pin.)  
Voice: Detector error in [Location, example Kitchen],  
please see manual.Repeated every 5 hours  
Horn: Three rapid chirps every minute  
Power/Smoke LED: Flashes approximately once a minute  
CO LED: Off  
Match +to +and -to -.If the  
batteries are not fully inserted, the  
unit cannot receive battery power.  
3. After you hear the location  
of where you are placing the  
Alarm, Press & Hold the  
Test Button or use your IR  
remote controls channel or  
volume button.  
[Location, example Kitchen]  
location saved.”  
If no location is chosen: No  
location saved.”  
2. Push and hold test button until the  
alarm sounds.  
3. To re-lock the battery compart-  
ment, close the battery door and  
reinsert locking pin in lock.  
Alarm Levels of CO are Detected  
Voice: Warning, evacuate carbon monoxide in [Location,  
example: Kitchen]. Evacuate.” “____ ppm.”  
Horn: 4 beeps, pause, 4 beeps, voice*  
Power/Smoke LED: Off  
CO LED: Flashes Red  
*NOTE: If unit goes into CO alarm, the regular 4 beeps-brief pause  
cycle will repeat for four minutes. After four minutes, the pause will  
increase to one minute.  
4. Reattach the Smoke/CO Alarm  
to the mounting bracket.  
If the unit does not alarm during  
testing, DO NOT lock the battery  
compartment! Install a new battery  
and test again. If the unit still does  
not alarm, replace it immediately.  
Your Alarm has now been programmed for the location of your  
choice.  
Available locations:  
Basement  
Kitchen  
Childs Bedroom  
Dining Room  
Family Room  
Guest Bedroom  
Hallway  
Living Room  
Master Bedroom  
No Location  
Office  
When replacing the batteries,  
always test the Smoke/CO Alarm  
before re-locking the battery  
compartment.  
3. Using needle-nose pliers or a utility  
knife, detach one locking pin from  
the mounting bracket.  
Smoke is Detected  
Voice: Warning, evacuate smoke in [Location, example:  
Utility Room  
4. Push the locking pin through the hole  
near the battery door latch on the  
back of the Smoke/CO Alarm.  
Kitchen]. Evacuate.”  
Horn: 3 beeps, pause, 3 beeps, voice  
Power/Smoke LED: Flashes Red  
CO LED: Off  
IF YOU ARE CHANGING THE BATTERIES  
Action:  
Alarm Will Say:  
1. Insert batteries (2, AA  
batteries).  
Welcome, First Alert Carbon  
Monoxide and Smoke Alarm.  
Location [If location already  
programmed, example  
Smoke Alarm is Silenced  
CO Alarm is Silenced  
TO LOCK THE MOUNTING BRACKET:  
TO UN-LOCK THE MOUNTING BRACKET:  
Voice: Horn silenced.  
Detector active.”  
Horn: Off  
Voice: Horn silenced.  
Detector active.”  
Horn: Off  
Power/Smoke LED: Off  
CO LED: Flashes Red  
Kitchen] programmed. To  
select location, press and hold  
test button now.”  
1. Using needle-nose pliers,  
detach one locking pin from  
the mounting bracket.  
1. Insert a flathead screwdriver into  
the rectangular cut-out on the  
mounting bracket nearest to the  
locking pin.  
Power/Smoke LED:  
Flashes Red  
CO LED: Off  
2. Press & Hold Test Button, or  
use your IR remote controls  
channel or volume button, if  
you would like to change  
the location.  
To change location, press and  
hold test button after location  
is heard.Alarm will speak list  
of locations (see above).  
2. Insert the locking pin through  
the hole on the back of the  
Smoke/CO Alarm as shown in  
the diagram.  
The Smoke Alarm will  
remain silent for up to 15  
minutes, then return to  
normal operation.  
If the smoke has not  
clearedor continues to  
increasethe device will  
go back into alarm.  
The CO Alarm will remain  
silent for up to 4 minutes.  
2. Pry the Smoke/CO Alarm away  
from the bracket by pushing up on  
the screwdriver and turning the  
Smoke/CO Alarm counterclockwise  
(left) at the same time.  
After 4 minutes, if CO  
levels remain potentially  
dangerous the horn will  
start sounding again.  
3. When you attach the  
Smoke/CO Alarm to the  
mounting bracket, the locking  
pins head will fit into a notch  
on the bracket.  
3. After you hear the location  
of where you are placing the  
Alarm, Press & Hold the  
Test Button or use your IR  
remote controls channel or  
volume button.  
[Location, example Kitchen]  
location saved.”  
If no location is chosen: No  
location saved.”  
IF YOUR SMOKE/CO ALARM SOUNDS  
If the CO Alarm sounds (4 beeps, pause, 4 beeps, Warning,  
evacuate carbon monoxide in [Location]. Evacuate. ____ ppm.):  
WEEKLY TESTING  
USING THE SILENCE FEATURES  
1. Operate the Silence Feature.  
You can test this Smoke/CO Alarm two ways:  
2. Call your emergency services, fire department or 911. Write  
down the number of your local emergency service here:  
_______________________________________________________  
3. Immediately move to fresh airoutdoors or by an open door or  
window. Do a head count to check that all persons are  
accounted for. Do not re-enter the premises, or move away  
from the open door or window until the emergency services  
responder has arrived, the premises have been aired out, and  
your CO Alarm remains in its normal condition.  
4. After following steps 1-3, if your CO Alarm reactivates within a  
24-hour period, repeat steps 1-3 and call a qualified appliance  
technician to investigate for sources of CO from fuel-burning  
equipment and appliances, and inspect for proper operation of  
this equipment.  
NEVER use an open flame of any kind to test this unit.  
You might accidentally damage or set fire to the unit or  
to your home. The built-in test switch accurately tests  
the units operation as required by Underwriters  
Laboratories, Inc. (UL). If you choose to use an aerosol  
smoke product to test the Alarm, be certain to use one  
that has been Listed to Underwriters Laboratories, Inc.  
Safety Standards, and use it only as directed. Use of  
non-UL Listed products or improper use of UL Listed  
products may affect the Alarms sensitivity, and may  
void your warranty. NEVER use vehicle exhaust! Exhaust  
may cause permanent damage and voids your warranty.  
Never remove the batteries to quiet an unwanted alarm.  
Removing the batteries disables the alarm and removes your  
protection.  
The Alarm Silence Feature can temporarily quiet an unwanted  
alarm for several minutes. You can silence the Smoke/CO Alarm  
two ways:  
1. Manually: Press and hold the Test/Silence button on the  
Alarm cover until Alarm Voice says Testing(typically 3-5  
seconds).  
2. Using Your Remote Control: Standing no further than 20 feet  
(6 meters) away from the Smoke/CO Alarm, aim your IR  
remote at the Alarm and press the CHANNEL or VOLUME  
button until Alarm Voice says Testing.  
During testing, you will see and hear the following sequence:  
The Alarm Voice will say Testing.The Horn will sound  
3 beeps, pause, 3 beeps. The Alarm Voice will say Warning,  
evacuate smoke in [Location, example: Kitchen]. Evacuate.”  
The Power/Smoke LED flashes Red and the CO LED will be  
Off.  
Next the Horn will sound 4 beeps, pause, 4 beeps. The Alarm  
Voice will say Warning, evacuate carbon monoxide in  
[Location, example: Kitchen]. Evacuate.The Power/Smoke  
LED will be Off and the CO LED flashes Red.  
If the Alarm does not respond to your remote control, there  
may be an obstruction between you and the Alarm, you may  
be standing too far away, or your remote control may not be  
compatible.  
If the unit does not alarm, make sure the batteries are  
correctly installed, and test again. If the unit still does not  
alarm, replace it immediately.  
1. Manually: Press the Test/Silence button on the alarm cover  
for at least 3-5 seconds.  
2. Using Your Remote Control: Standing no further than 20  
feet (6 meters) away from the Alarm, aim your IR remote at  
the Alarm and press the CHANNEL or VOLUME button for  
at least 3-5 seconds.  
DO NOT stand close to the Alarm when the horn is  
sounding. Exposure at close range may be harmful to  
your hearing. When testing, step away when horn  
starts sounding.  
After the Test/Silence or remote control button is released, the  
Alarm Voice will say Horn silenced, detector active.”  
5. After the emergency responders arrive, the premises aired out,  
and your CO Alarm remains in its normal condition, you can  
check what the highest carbon monoxide level sensed was:  
The Low Battery Warning Silence Feature can temporarily quiet  
the low battery warning chirpfor up to 8 hours. You can silence  
the low battery warning chirptwo ways:  
Alarm Will Say:  
Action:  
1. Press & Hold Test Button  
It is important to test this unit every week to make sure it is  
working properly. Using the test button or remote control is the  
recommended way to test this Smoke/CO Alarm.  
Highest carbon monoxide  
level was ___ ppm. Please see  
manual.To clear highest carbon  
monoxide level, press and hold  
test button now.”  
1. Manually: Press the Test/Silence button on the alarm cover  
for at least 3-5 seconds.  
2. Using Your Remote Control: Standing no further than 20  
feet (6 meters) away from the Alarm, aim your IR remote at  
the Alarm and press the CHANNEL or VOLUME button for  
at least 3-5 seconds.  
2. Press & Hold Test Button, if  
you would like to clear the  
highest level sensed.  
If you would like to keep the  
highest level in memory, do  
not press anything.  
Highest carbon monoxide level  
cleared.”  
Once the low battery warning chirpsilence feature is activated,  
the unit continues to flash the Green light twice a minute for 8  
hours. After 8 hours, the low battery chirpwill resume. Replace  
the batteries as soon as possible; this unit will not operate  
without battery power!  
Alarm will say nothing.  
First Alert® is a registered trademark of the First Alert Trust.  
Printed in Mexico M08-0086-001  
T
01/04  
1
2
3
4
 

Belkin Bluetooth Headset F8T001 User Manual
Black Box Computer Hardware IC113C User Manual
Blakeslee Dishwasher Dishwashing Kitchen Equipment User Manual
Bock Water heaters Water Heater Gas Water Heaters User Manual
Bosch Appliances Dishwasher SMS69L22GB User Manual
Bosch Appliances Home Security System APC AMC2 4W User Manual
Bradford White Corp Water Heater 238 48248 00 User Manual
Bryant Air Conditioner 116B User Manual
Carrier Furnace 58MEC User Manual
Chamberlain Garage Door Opener 2280 267 User Manual