Print Form
™
ECO-i Submittal Data
CHDX14053
Heat Pump: 12 tons VRF Outdoor Unit
Job Name:
Location:
Approval:
Date:
Engineer:
Construction:
Unit #:
Drawing #:
Submitted to:
Submitted by:
Reference:
Compressor Warranty: 6 Years
Parts Warranty: 1 Year
Coil Coated to Protect Against Corrosion
Salt Protection also avilable
Capacities
Fan
Cooling: Btu/h
Power Input: KW
Heating: Btu/h
Power Input: KW
153,600
13.3
170,600
13.2
Quantity/Type:
Fan Motor Output (KW):
1 Propeller Fan
0.7
Power Supply
V/PH/Hz.
208-230 / 3 / 60
Cooling Mode Nominal Conditions
Indoor: °F DB/°F WB
Outdoor: °F DB
Minimum circuit Amps (MCA): Amps
Max. Overcurrent Protection (MOCP):
57
70
80/67
95
25
Pipe Length (feet):
Weight (lbs):
760
Level Difference (feet):
0
Refrigerant:
410A
Heating Mode Nominal Conditions
Indoor: °F DB
Outdoor: °F DB/ °F WB
Pipe Length (feet):
70
47/43
25
Coil
Coil Face Area (sq. ft.):
Number of Rows:
22.5
4
Level Difference (feet):
0
Protection Devices
High Pressure Switch:
Overcurrent (CT Method):
Crankcase Heaters (W):
Operating Range
Cooling: °F DB:
Heating: °F DB:
Yes
Yes
25 + 32 x 2
14 to 109
-4 to 59
Compressor
External Finish:
Electrostatic Powder Coating
Quantity/Type:
1 Inverter driven rotary & 2 fxed speed scroll
Capacity Control Range:
10-100%
|
Panasonic Cu E28ekr User Manual
Philips Sc479 Dect User Manual
Samsung Avmdh C User Manual
Samsung Multifunction Printer Scx5639fr User Manual 3
Sears 20071224 User Manual
Sharp Af S85px User Manual
Sharp Fo Dc535 User Manual
Sharp Mx B402 User Manual
Turtle Beach Sony V331 User Manual
Vornado Air Cleaner Pco500 User Manual