UNINTERRUPTIBLE POWER SYSTEM
SINGLE PHASE - .6/.8/1.0/1.2 kVA
SINGLE PHASE - .6/.8/1.0 kVA PLUS
1500 and 1500 SERIES
MANUFACTURED IN THE U.S.A.
OPERATION MANUAL
March, 2003
Part # 46370-002
TOSHIBA
NOTE
The instructions contained in this manual are not intended to cover all of the details
or variations in equipment, nor to provide for every possible contingency
to be met in connection with installation, operation, or maintenance. Should further
information be desired or should particular problems arise which are not covered
sufficiently for the purchaser's purposes, the matter should be referred to the local
Toshiba sales office.
The contents of this instruction manual shall not become a part of or modify any
prior or existing agreement, commitment, or relationship. The sales contract
contains the entire obligation of Toshiba International Corporation's UPS Division.
The warranty contained in the contract between the parties is the sole warranty of
Toshiba International Corporation's UPS Division and any statements contained
herein do not create new warranties or modify the existing warranty.
Any electrical or mechanical modifications to this equipment,
without prior written consent of Toshiba International
Corporation, will void all warranties and may void UL listing
or other safety certification. Unauthorized modifications also
can result in personal injury, death, or destruction of the
equipment.
UNINTERRUPTIBLE POWER SUPPLY
If additional information or technical assistance is required call Toshiba's marketing
department toll free at (800) 231-1412 or write to: Toshiba International Corporation,
13131 W. Little York Road, Houston, TX 77041-9990.
Please complete the following information for your records and to remain within this
equipment manual:
Model Number:
Serial Number:
Date of Installation:
Inspected By:
i
TOSHIBA
CONTENTS
SECTION
PAGE
Disclaimer................................................................................................. i
Contents ................................................................................................ ii-iii
Introduction ............................................................................................. iv
General Safety Instructions.................................................................... v
Important Safety Instructions.............................................................. vi-vii
Product Description ...............................................................................1-1
1.0
1.1
1.2
1.3
1.4
Theory of Operation ........................................................................ 1-1
Application and Use ........................................................................ 1-1
Power Backup ................................................................................. 1-1
Power Conditioning ......................................................................... 1-1
2.0
3.0
Inspection/Storage/Disposal .................................................................2-1
2.1
2.2
2.3
Inspection of the new UPS equipment ........................................... 2-1
Storage of UPS equipment ............................................................. 2-1
Disposal .......................................................................................... 2-1
Precautions ............................................................................................ 3-1
3.1
3.2
3.3
Installation Precautions (General) .................................................. 3-1
Prestart Precautions ....................................................................... 3-2
Operating Precautions .................................................................... 3-2
4.0
5.0
Specifications.........................................................................................4-1
4.1
4.2
Standard Series Specifications....................................................... 4-1
Plus Series Specifications (with isolation transformer)................... 4-3
Operating the UPS ................................................................................. 5-1
5.1
Operation Modes ............................................................................ 5-1
5.1.1 AC Input Mode (normal operation) ........................................ 5-1
5.1.2 Battery Backup Mode ............................................................ 5-1
5.1.3 Circuit Bypass Mode .............................................................. 5-2
System Protection Features ........................................................... 5-2
5.2
ii
TOSHIBA
CONTENTS (Cont'd)
SECTION
PAGE
5.0
Operating the UPS (cont'd).................................................................... 5-1
5.3
Operation Monitoring ...................................................................... 5-3
5.3.1 Visual Indicator Functions...................................................... 5-3
5.3.2 Audible Alarm Functions ........................................................ 5-3
5.3.3 Visual and Audible Indicator Function Chart ......................... 5-3
Front Panel Layout.......................................................................... 5-4
UPS On Line Mode Display ............................................................ 5-4
Battery Recharging ......................................................................... 5-5
Battery Backup Time....................................................................... 5-6
Battery Low Voltage Tolerances ..................................................... 5-6
Battery Check Function................................................................... 5-6
5.4
5.5
5.6
5.7
5.8
5.9
5.10 System Reset.................................................................................. 5-6
6.0
UPS Control Interface ............................................................................6-1
6.1
6.2
DB25 Connector Pinout .................................................................. 6-1
RS-232C Communication Interface ................................................ 6-2
6.2.1 UPS Shutdown (via RS-232C) .............................................. 6-2
Dry Contact Interface ...................................................................... 6-2
6.3
7.0
8.0
Troubleshooting Procedures.................................................................7-1
7.1
7.2
Non-Fatal Fault Mode ..................................................................... 7-1
Fatal Fault Mode ............................................................................. 7-2
Preventive Maintenance/Parts Replacement........................................8-1
8.1
8.2
8.3
Preventive Maintenance ................................................................. 8-1
Parts Replacement ......................................................................... 8-1
Fuse Rating Chart ........................................................................... 8-2
9.0
External Dimensions/Panel Layout/Shipping Weights ........................9-1
9.1
9.2
9.3
External Dimensions ....................................................................... 9-1
Panel Layout ................................................................................... 9-2
Shipping Weights ............................................................................ 9-2
iii
TOSHIBA
INTRODUCTION
Thank you for purchasing the 1500/1500 Plus Series UPS. This Series features the very
latest state of the art microprocessor technology and also uses IGBT transistors for fast, high
power and low noise PWM (pulse width modulation) switching. Also, the Plus Series features a
low impedance transformer to provide isolation even during bypass operation.
It is the intent of this manual to provide a guide for safely installing, operating, and maintaining
the UPS. This operation manual contains a section of general safety instructions and is marked
throughout with warning symbols. Read this operation manual thoroughly before installation
and operation of this electrical equipment.
All safety warnings must be followed to ensure personal safety.
Follow all precautions to attain proper equipment performance and longevity.
General safety instructions are found on page v and important safety
instructions are found on pages vi, vii, and viii. Read and save these instructions
for future reference.
The manual is divided into major sections of interest. Section 1 contains the product description
with the theory of operation and applications. All of the initial inspection, storage, installation,
operating, and prestart precautions can be found in Sections 2 and 3.
Section 4 contains the equipment standard specifications.
Section 5 outlines the operating modes, protective features, battery recharging, battery low
voltage tolerances, alarm and panel indicator functions.
Section 6 shows the control interface pin configurations.
Sections 7 and 8 are devoted to troubleshooting procedures, preventative maintenance
techniques and periodic parts replacement. A fuse rating chart is also shown.
Section 9 shows front, rear, and side panel layout views with dimensional data. Labels,
connector and switch placement, and shipping weights are also shown.
We hope that you find this operation manual informative and easy to use. If additional information
or technical assistance is needed, please call toll free (800) 231-1412 or write to: Toshiba
International Corporation, 13131 W. Little York Road, Houston, TX 77041-9990.
Again, thank you for the purchase of this product.
TOSHIBA INTERNATIONAL CORPORATION
© Copyright 1994
iv
TOSHIBA
GENERAL SAFETY INSTRUCTIONS
Warnings in this manual appear in any of four ways:
1)
2)
3)
4)
Danger - The danger symbol is a lightning bolt mark enclosed in a triangle which precedes
the 3/16" high letters spelling the word "DANGER". The danger symbol is used to indicate
imminently hazardous situations, locations, and conditions which, if not avoided, WILL
result in death, serious injury, and/or severe property damage.
DANGER
Warning - The warning symbol is an exclamation mark enclosed in a triangle which
precedes the 3/16" high letters spelling the word "WARNING". The warning symbol is
used to indicate potentially hazardous situations and conditions which, if not avoided
COULD result in serious injury or death. Severe property damage COULD also occur.
WARNING
Caution - The caution symbol is an exclamation mark enclosed in a triangle which
precedes the 3/16" high letters spelling the word "CAUTION". The caution symbol is used
to indicate potentially hazardous situations and conditions which, if not avoided may result
in injury. Equipment damage may also occur.
CAUTION
Attention warnings - The attention warning symbol is an exclamation mark enclosed in a
triangle which precedes the 3/16" high letters spelling the word "ATTENTION". The
Attention warning symbol is used to indicate situations and conditions that can cause
operator injury and/or equipment damage:
ATTENTION
Other warning symbols may appear along with the Danger and Caution symbol and are used to specify
special hazards. These warnings describe particular areas where special care and/or procedures are
required in order to prevent serious injury and possible death:
1)
Electrical warnings - The electrical warning symbol is a lighting bolt mark enclosed in
a triangle. The Electrical warning symbol is used to indicate high voltage locations and
conditions that may cause serious injury or death if the proper precautions are not
observed:
2)
Explosion warnings - The explosion warning symbol is an explosion mark enclosed in
a triangle. The Explosion warning symbol is used to indicate locations and conditions
where molten, exploding parts may cause serious injury or death if the proper
precautions are not observed:
v
TOSHIBA
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS-
This manual contains important instructions
that should be followed during the installation and maintenance of the UPS and it's batteries. Use for
models UE1A1A006C6, UE1A1A006C6T, UE1A1A008C6, UE1AIA008C6T, UE1A1A010C6,
UE1A1A010C6T, UE1A1A012C6.
- The maximum ambient temperature in which this UPS unit should be operated or stored is
104 °F (40 °C).
- The nominal battery voltage range is indicated in Section 5.6.
- Servicing of the batteries should only be performed by a qualified Toshiba Representative who is
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away from
batteries.
- When replacing batteries, use the same number and type of one of the following sealed, lead-acid
batteries (do not mix types of batteries):
Model Capacity
600 VA / 600 VA Plus
800 VA / 800 VA Plus
1000 VA / 1000 VA Plus
1200 VA
Manufacturer
Type
Quantity
Yuasa
NP4-12FR
5
Yuasa
HPH5-12FR
5
Misuse of this equipment could result in human injury and equipment
damage. In no event will Toshiba Corporation be responsible or liable for
either indirect or consequential damage or injury that may result from the use of this equipment.
CAUTION
Do not dispose of the batteries in a fire. The batteries may explode.
CAUTION
Do not open or mutilate the batteries. Released electrolyte is harmful
CAUTION
to the eyes and skin and could also be toxic.
This unit contains sealed lead acid batteries. Lack of preventative
WARNING
maintenance could result in batteries exploding and emitting gasses and/or
flame. Annual preventative maintenance must be performed by an authorized, trained technician.
Failure to replace a battery before it becomes exhausted may cause the
WARNING
case to crack, possibly releasing electrolytes from inside the battery, and
resulting in secondary faults such as odor, smoke, and fire.
vi
TOSHIBA
IMPORTANT SAFETY INSTRUCTIONS
Installation and servicing of batteries should be performed by personnel
knowledgeable of batteries and the required precautions. Keep
unauthorized personnel away from the batteries.
WARNING
Proper maintenance to the battery system of this unit must be done by a
qualified service technician, this is essential to the safety and reliability of
your UPS system. Refer to service manual.
WARNING
A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed
DANGER
when working with batteries:
1) Verify that the UPS is off and that the power cord is disconnected from the power source.
2) Remove watches, rings or other metal objects.
3) Use tools with insulated handles to prevent inadvertent shorts.
4) Wear rubber gloves and boots.
5) Do not lay tools or metal parts on top of batteries.
6) Determine if the battery is inadvertently grounded. If inadvertently grounded, remove
source of ground. Contact with any part of a grounded battery can result in
electrical shock. The likelihood of such shock will be reduced if such grounds are
removed during installation and maintenance.
7) Verify circuit polarities prior to making connections.
8) Disconnect charging source and load prior to connecting or disconnecting terminals.
9) VRLA batteries contain an explosive mixture of hydrogen gas. Do not smoke, cause a flame
or spark in the immediate area of the batteries. This includes static electricity from the body.
10) Do not attempt to open the batteries in order to add water or sample the specific gravity of the
electrolyte. The batteries are valve regulated lead acid type and such servicing is not
possible without damaging the battery.
11) Use proper lifting means when moving batteries and wear all appropriate safety clothing and
equipment.
12) Do not dispose of lead acid batteries except through channels in accordance with local, state
and federal regulations.
vii
TOSHIBA
INSTRUCTIONS IMPORTANTES CONCERNANT
LA SÉCURITÉ
Cette notice contient des
instructions importantes concernant
la sécurité.
CONSERVER CES INSTRUCTIONS
Une battery peut présenter un risque de choc électrique, de brûlure par
transfert d' énergie.
ATTENTION
ATTENTION
Pour le remplacement, utiliser le même nombre de batteries du modéle
suivant.
Model Capacity
600 VA / 600 VA Plus
800 VA / 800 VA Plus
Manufacturer
Type
Quantity
Yuasa
NP4-12FR
5
1000 VA / 1000 VA Plus
1200 VA
Yuasa
NPH5-12FR
5
L' élimination des batteries est règlementèe. Consulter les codes locaux
ATTENTION à cet effet.
© Copyright 1994
viii
TOSHIBA
1.0
Product Description
1.1
Theory of Operation
An uninterruptible power supply is a system that is installed between the commercial
power and the load equipment. It is used during short-term blackouts or brownouts. The
UPS provides steady ac output power during these commercial power interruptions.
This power is provided for a long enough time so that the load can be shutdown in an
orderly fashion. This prevents loss of data and possible damage to both hardware and
software.
During normal operation the UPS uses commercial ac power. In addition, it also takes
in all of the high voltage spikes and transients caused by switching and faults, and all
of the common mode and normal mode noise which is associated with commercial ac
power. The UPS converts it all to flat dc power. From this dc power, the UPS charges
its batteries and generates its own extremely high quality ac waveform output. The
result of this process is maximum power conditioning.
If the ac power supplied to the UPS drops below a specified voltage level, the unit's
batteries automatically begin supplying power instead of receiving it. This insures that
the loads connected to the UPS continue to receive power with no interruption. When
ac input power becomes available again, operation returns to normal. The unit's
batteries begin to recharge so they will be ready for the next power interruption.
1.2
Application and Use
Toshiba's 1500 and 1500 Plus Series of on-line uninterruptible power supply (UPS)
systems provide continuous computer-grade ac power in a compact, high performance,
and energy efficient unit. The UPS unit assures safe and reliable operation of critical
office equipment. This can range from word processors and personal computers to
mini-computers and local area networks. All units feature an audible alarm which sounds
if the battery voltage drops below standard during use. This is an additional aid to help
in retaining the valuable office data banks. All units allow for computer interfacing and
an external battery pack option (see specifications).
1.3
1.4
Power Backup
When an electrical power failure occurs, the UPS unit's internal maintenance-free
batteries automatically supply back-up power to the load without interruption. For
example, when used to support a computer, the UPS back-up assures enough
additional time to complete the activity and store data. This allows an orderly shutdown
after a power failure has occurred.
Power Conditioning
When commercial power is present, the UPS supplies conditioned power to the load
while maintaining its batteries in a charged condition. The UPS protects against the
normal everyday problems associated with heavy use of raw commercial ac power,
including power sags, surges, signal interference, and spikes. This protection keeps
power-line problems from reaching the loads where they can cause equipment to
operate erratically, hard-disk crashes, or cause damage to hardware and software.
1 - 1
TOSHIBA
2.0
Inspection/Storage/Disposal
2.1
Inspection of the new UPS equipment
Upon receipt of the UPS, a careful inspection for shipping damage should be made.
After Uncrating:
1) Check the unit for loose, broken, bent or otherwise damaged parts. If damage
has occurred during shipment, keep all original crating and packing materials
for return to shipping agent. Warranty will not apply to units which are damaged
during shipment.
2) Check to see that the rated capacity and the model number specified on the
nameplate conform to the order specifications.
2.2
Storage of UPS equipment.
If the UPS equipment is to be subject to long or short term storage the following
guidelines should be used.
Avoid:
1) Storage in sites subject to extreme changes in temperature or high humidity.
2) Storage in sites subject to exposure of high levels of dust or metal particles
3) Storage on inclined floor surfaces or in sites subject to excessive vibration.
Before storing:
1) Charge the units batteries.
2) Place the STOP/RUN switch in the STOP position.
Storing:
1) Store within a temperature range of -20° to 40° C (-4° to 104° F).
2) For best results, store the UPS in the original shipping container and place on a
wood or metal pallet.
3) The optimum storage temperature is 21° C (70° F). Higher ambient
temperatures cause UPS batteries to need recharging more frequently.
After storing:
1) If stored in an ambient temperature under 20° C (68° F); recharge the batteries
every 9 months.
2) If stored in an ambient temperature of 20° to 30° C (68° to 86° F); recharge the
batteries every 6 months.
3) If stored in an ambient temperature of 30° to 40° C (86° to 104° F); recharge the
batteries every 3 months.
2.3
Disposal
Please contact your state environmental agency for details on disposal of electrical
components and packaging in your particular area.
It is illegal to dump lead-acid batteries in landfills or to dispose of them improperly.
Please help our Earth by contacting the environmental protection agencies in your area,
the battery manufacturer, or call Toshiba toll-free at (800) 231-1412 for more information
about recycling.
2 - 1
TOSHIBA
3.0
Precautions
3.1
Installation Precautions (General)
CAUTION
1) Install the unit in a well ventilated location; allow at least 10 cm (4 inches) on
all sides for air ventilation and for maintenance.
2) Install the unit in a stable, level, and upright position which is free of vibration.
3) Install the unit where the ambient temperature is within the correct operating
range (see Specifications Section 4.0).
4) Do not install the UPS in areas that are subject to high humidity.
5) Do not allow direct sunlight to shine on the unit.
6) Do not install the UPS in areas which are subject to contamination such as
high levels of airborne dust, metal particles, or inflammable gas.
7) Avoid installation near sources of electrical noise and always make sure that
the unit ground is intact to prevent electrical shock and to help reduce
electrical noise.
8) Do not install where water or any foreign object may get inside the UPS.
9) This UPS generates and can radiate radio-frequency energy during operation.
Although RFI noise filters are installed inside the unit, there is no guarantee
that the UPS will not influence some sensitive devices which are operating
close by. If such interference is experienced, the UPS should be installed farther
away from the affected equipment and/or powered from a different source than
that of the affected equipment.
3 - 1
TOSHIBA
3.0
Precautions
3.2
Prestart Precautions
CAUTION
1) Before connecting the UPS to a power source; move the operation switch
(STOP/RUN), on the front panel (See sections 9.1), to the STOP position.
3.3
Operating Precautions
CAUTION
1) The UPS should not be powered up until the entire operation manual has
been reviewed.
2) The input power source voltage and frequency must be within the specified
ranges (See Specification sections 4.1 and 4.2). Voltages and frequencies
outside of the permissible tolerance ranges may cause internal protection
devices to activate.
3) The UPS should not be used with a load whose rated input is greater than the
rated UPS output.
4) Do not use the UPS to provide power to motors that require high starting current
or a long starting time such as vacuum cleaners and machine tools (oversizing
for lock rotor current required).
5) Do not insert metal objects or combustible materials in the unit's ventilation slots.
6) Do not place, hang, or paste any objects on the top or on the exterior surfaces
of the UPS.
7)
Always use caution when connecting or disconnecting load equipment.
The UPS may be supplying power to the output load receptacles
through the bypass circuit. This can occur when the STOP/RUN
switch is in the STOP position and the unit is connected to a source of
supply power (see Circuit-bypass Mode section 5.1.3).
3 - 2
TOSHIBA
4.0
Specifications
4.1 Standard Series Specifications
MODEL NUMBER
UE1A1A006C6
UE1A1A008C6
UE1A1A010C6
CAPACITY
600 VA (0.42 kW)
800 VA (0.56 kW)
1000 VA (0.7 kW)
Input
Input voltage Single phase, 120 Vac, +10% to -30% (*)
Input frequency 45 to 65 Hz
Input capacity
600 VA
800 VA
1000 VA
Input power factor Approximate unity (0.95 to 1.0)
Battery rated voltage 60 Vdc
Battery
Output
Battery backup time when fully charged 12 min. at full load (**) 8 min. at full load (**)
7 min. at full load (**)
with 0.7 power factor at 77° F (25° C) 30 min. at half load (**) 20 min. at half load (**) 18 min. at half load (**)
Recharge time Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries Sealed lead-acid
Output voltage Single-phase, 120 volts
Output voltage regulation Within +/- 3%, steady state
Output frequency 50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Rated load power factor 0.7 lagging (0.6 to 1.0)
Voltage transient characteristic +/- 8% under 100% load step change
Rated output current (rms)
5.0A
6.7A
8.3A
Maximum output current (peak)
15.0A
20.0A
25.0A
Inverter overload capacity 150% for 30 seconds
Crest factor 3.0
Environment
Operating temperature 32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operatinghumidity 30 to 90%, no condensation
Altitude(****) Less than 3000 ft (1000 m) above sea level
External dimensions 8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)
Net weight
Acoustical noise 50 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) 85% 85% 87%
40.3 lb (18.3 kg)
40.3 lb (18.3 kg)
43.7 lb (19.8 kg)
Switches
Bypass switch Automatic bypass is provided when the run switch is in the stop
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 msec)
Interfaces
IBM (TM) AS/400
LAN Manager See section 6.0 for details.
Fault detect and input power loss
RS232 ASCII
Options
Software for unattended
computershutdown Contact Toshiba for details on this option
External battery pack Contact Toshiba for details on this option
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) Above 3000 ft (1000 m), output capacity reduced.
Download from Www.Somanuals.4com-.1All Manuals Search And Download.
TOSHIBA
4.0
Specifications
4.1 Standard Series Specifications (Cont'd)
MODEL NUMBER
UE1A1A012C6
CAPACITY
1200 VA (0.84 kW)
Input
Input voltage Single phase, 120 Vac, +10% to -30% (*)
Input frequency 45 to 65 Hz
Input capacity 1200 VA
Input power factor Approximate unity (0.95 to 1.0)
Battery
Output
Battery rated voltage 60 Vdc
Battery backup time when fully charged 5 min. at full load (**)
with 0.7 power factor at77° F (25° C) 12 min. at half load (**)
Recharge time Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries Sealed lead-acid
Output voltage Single-phase, 120 volts
Output voltage regulation Within +/- 3%, steady state
Output frequency 50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Rated load power factor 0.7 lagging (0.6 to 1.0)
Voltage transient characteristic +/- 8% under 100% load step change
Rated output current (rms) 10.0A
Maximum output current (peak) 30.0A
Inverter overload capacity 150% for 30 seconds
Crest factor 3.0
Environment
Operating temperature 32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operatinghumidity 30 to 90%, no condensation
Altitude(****) Less than 3000 ft (1000 m) above sea level
External dimensions 8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)
Net weight 43.7 lb (19.8 kg)
Acoustical noise 50 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) 87%
Switches
Bypass switch Automatic bypass is provided when the run switch is in the stop
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 mS)
Interfaces
IBM (TM) AS/400
LAN Manager See section 6.0 for details.
Fault detect and input power loss
RS232 ASCII
Options
Software for unattended
computershutdown Contact Toshiba for details on this option
External battery pack Contact Toshiba for details on this option
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) Above 3000 ft (1000 m), output capacity reduced.
Download from Www.Somanuals.4com-.2All Manuals Search And Download.
TOSHIBA
4.0
Specifications
4.2 Plus Series Specifications (w/ isolation transformer)
MODEL NUMBER
UE1A1A006C6T
UE1A1A008C6T
UE1A1A010C6T
CAPACITY
600 VA (0.42 kW)
800 VA (0.56 kW)
1000 VA (0.7 kW)
Input
Input voltage Single phase, 120 Vac, +10% to -30% (*)
Input frequency 45 to 65 Hz
Input capacity
600 VA
800 VA
1000 VA
Input power factor Approximate unity (0.95 to 1.0)
Battery rated voltage 60 Vdc
Battery
Output
Battery backup time when fully charged 12 min. at full load (**) 8 min. at full load (**)
7 min. at full load (**)
with 0.7 power factor at 77° F (25° C) 30 min. at half load (**) 20 min. at half load (**) 18 min. at half load (**)
Recharge time Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)
Type of batteries Sealed lead-acid
Output voltage Single-phase, 120 volts
Output voltage regulation Within +/- 3%, steady state
Outputfrequency(*****) 50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)
Output voltage waveform Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load
Commonmode Less than 0.5V peak
Normal mode Less than 10V peak
Rated load power factor 0.7 lagging (0.6 to 1.0)
Voltage transient characteristic +/- 8% under 100% load step change
Rated output current (rms)
5.0A
6.7A
8.3A
Maximum output current (peak)
15.0A
20.0A
25.0A
Inverter overload capacity 150% for 30 seconds
Crest factor 3.0
Environment
Operating temperature 32 to 104° F (0 to 40° C), optimal at 77° F (25° C)
Storage temperature -4 to 104° F (-20 to 40° C)
Operatinghumidity 30 to 90%, no condensation
Altitude(****) Less than 3000 ft (1000 m) above sea level
External dimensions 8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)
Net weight
Acoustical noise 50 dB at max. output, measured 3.3 ft (1 m) from front panel
Efficiency (ac-dc-ac) 83% 83% 85%
57.5 lb (26.1 kg)
57.5 lb (26.1 kg)
60.9 lb (27.6 kg)
Switches
Bypass switch Automatic bypass is provided when the run switch is in the stop
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 msec)
Interfaces
IBM (TM) AS/400
LAN Manager See section 6.0 for details.
Fault detect and input power loss
RS232 ASCII
Options
Software for unattended
computershutdown Contact Toshiba for details on this option
External battery pack Contact Toshiba for details on this option
(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.
(**) Battery backup time may vary depending on the operating conditions including ambient temperature at the
installation site.
(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used
for battery backup.
(****) Above 3000 ft (1000 m), output capacity reduced.
(*****) Output voltage and capacity derated for 50 Hz output.
4 - 3
TOSHIBA
5.0
Operating the UPS
5.1
Operation Modes
5.1.1 AC Input Mode (normal operation)
Bypass circuit
UPS
Power
input plug
receptacles
(rear panel)
Fuse
UPS
main
circuit
5-15P
Transformer
(Plus Series)
5-15R
= power flow
+
UPS batteries
-
Power flow in AC input mode
The above illustration shows circuit power flow in the ac input mode. The UPS
unit's rectifier, included in a boost chopper circuit, converts ac input power to dc
power. This dc power runs the unit's transistor inverter and charges the batteries.
The boost chopper circuit maintains a constant voltage, with current limiting, for
charging the batteries and assures proper sine waveform generation for the
output current. The unit's batteries are maintained in a constantly charged state
when the UPS is in the normal operation mode. On the front panel, LED's labeled
"On Line" and "AC Input" should be on and the "Fault" LED should be off
(See Section 9.2 Panel Layout).
5.1.2 Battery Backup Mode
Bypass circuit
UPS
receptacles
(rear panel)
Power
input plug
Fuse
UPS
main
circuit
5-15P
Transformer
(Plus Series)
5-15R
= power flow
+
UPS batteries
-
Power flow in battery backup mode
The above illustration shows circuit power flow in battery backup mode. When
commercial ac power failures occur, the UPS's batteries instantly begin supplying
dc voltage to the UPS's main inverter circuit. This circuit changes (inverts) the dc
power into ac power. The ac power is available at the unit's output receptacles.
This back-up process will continue until the UPS's battery voltage drops below a
specific minimum level. When this occurs, the batteries will stop supplying power
to the load. This minimum level is the rated minimum voltage (Vmin). The rated
battery voltage chart in section 5.6 (See Section 5.7 for battery backup time)
shows (Vmin). On the front panel, LED's labeled AC Input and Fault should be
off. The On Line and Backup LEDs should be on (See Section 9.2 Panel
Layout).
5 - 1
TOSHIBA
5.0
Operating the UPS
5.1
Operation Modes
5.1.3 Circuit-bypass mode
Bypass circuit
UPS
Power
receptacles
(rear panel)
input plug
5-15P
Fuse
UPS
main
circuit
Transformer
(Plus Series)
5-15R
= power flow
+
UPS batteries
-
Power flow in circuit-bypass mode.
If the UPS unit is severely overloaded or develops an internal fault, the power flow
is automatically switched from the unit's main circuit to the bypass circuit mode.
Power flow through the bypass is shown in the above illustrations. This change-
over occurs automatically in approximately 4 milliseconds. The switching period
is not long enough to cause interruptions to occur in most UPS equipment loads.
The energy flow must be transferred manually from the UPS's bypass
circuit back to the inverter circuit after first correcting the fault. Toggle the
STOP/RUN switch (on the unit's front panel) first to STOP and then back to RUN.
This procedure resets the UPS and transfers back to inverter. During circuit-
bypass mode the AC-Input LED is ON, the On-Line LED is OFF, and the Fault
LED may be ON or OFF.(See Section 9.2 Panel Layout).
5.2
System Protection Features
The schematic shown below depicts the electrical locations of the protection devices on
the UPS.
Input
Abnormal
Overcurrent
Fuse
Rectifier/
Charger/
Chopper
Input
Output
Output
Inverter
Transformer
(Plus Series)
+
Batteries
Low Battery
Level
Overvoltage/
Undervoltage
Current Limit
Overload
Overheating
5 - 2
TOSHIBA
5.0
Operating the UPS
5.3
Operation Monitoring
5.3.1 Visual Indicator Functions
The following LED (light emitting diode) indicators are located on the front panel
(see Section 9.2 "Panel Layout"). Refer to these lamps for visual information
about the operating condition of the UPS (see Section 5.3.3 "Visual and Audible
Indicator Function Chart").
1) AC Input: This green LED lights when normal ac input power is being
supplied to the UPS unit.
2) On Line: This green LED lights when the inverter output voltage is normal.
3) Fault: This red LED lights when an abnormal operating condition is
detected. Operation of the unit's inverter is inhibited until the fault has been
corrected and the system reset (see Section 5.10 "System Reset").
5.3.2 Audible Alarm Functions
The UPS is equipped with an audible alarm system which activates under various
operating conditions. Sound patterns are used to indicate these conditions (see
Section 5.3.3 "Visual and Audible Indicator Function Chart"). Alarms for the
battery backup mode or low battery voltage will stop automatically when AC input
voltage is restored. Alarms for a fault condition will continue to sound until the
UPS has been reset (see Section 5.10 "System Reset").
5.3.3 Visual and Audible Indicator Function Chart
Audible
Condition
Cause
Visual
Indicators
UPS
Operation
Alarm
Pattern
Overcurrent (OC)
Problem in chopper or
inverter circuit.
1) "Fault" LED 1) Auto
is ON
2) "On Line"
transfer
to bypass
ON
DC Bus Overvoltage (DCOV) DC Bus > 115% of rated.
LED is OFF 2) Chopper
3) "AC Input" stopped
OFF
Ouput Overvoltage (OV)
Undervoltage (UV)
Overheat (OH)
V out > 110% of rated.
V out < 85% of rated.
Heatsink exceeds 90º C.
LED is ON 3) Inverter
1.5s
2s
stopped
ON
Overload (OL)
Output current and over-
load specifications have
been exceeded.
OFF
.5s .5s
ON
Battery problem
Problem in battery
circuit.
1) Replace
Battery
1) Bypass or
On-Line
OFF
2s
1s
LED is ON
mode.
ON
Normal battery backup
operation
Loss of AC power
1) "Fault" LED 1) Chopper
is OFF
running
2) Inverter
running
OFF
2) "On Line"
LED is ON
3) "AC Input"
LED is OFF
70s
5s
ON
Low battery voltage
Battery voltage too low,
Shutdown imminent.
OFF
.5s
1s
5 - 3
TOSHIBA
5.0
Operating the UPS
5.4
Front Panel Layout
ON LINE (green lamp)
Lights green when the UPSs inverter is supplying power to the load.
AC INPUT (green lamp)
Lights green when normal ac input power is being supplied to the UPS
Unit.
FAULT (red lamp)
Lights red when the UPS unit has tripped in the fault mode.
REPLACE BATTERY (red lamp)
Lights red to indicate batteries may need to be replaced.
5.5
UPS On-Line Mode Display
The following chart shows normal operating conditions when the UPS On-Line
lamp is green.
Output
Display Status
Explanation
Output
Display Status
Explanation
When output current is
between 30% and 100%,
the green lamps light in
15% increments (from
bottom to top) to indicate
relative output value
(This sample display
shows output current at
45% to 60% of rated
current).
During battery backup all
green lamps flash and the
red Backup lamp is lit
continuously. As the
batteries discharge, the
green lamps extinguish
from top to bottom to
indicate remaining battery
capacity (This sample
display shows battery
voltage between 75% and
90% of battery capacity).
Normal
Battery
Backup
All the green lamps will
light and the red Overload
lamp will flash. If the load
exceeds 135% of the max.
rated output the red
Overload lamp will light
continuously.Remove
overload as quickly as
possible to prevent fault
(fault timeouts vary
depending on overload
condition).
All green lamps are off
and the red Backup lamp
is lit continuously or
flashing.
Low
Battery
During
Battery
Backup
Overload
= Steady-lit LED
=FlashingLED
5 - 4
TOSHIBA
5.0
Operating the UPS (Cont'd)
5.6
Battery Recharging
The graph below shows the typical voltage requirements for recharging the UPS unit's
batteries.
Current
Voltage
Charging
current
Battery
charge
voltage
0.4 amp (A)
Vmax.
Vmin.
Discharge
shut-off point
Fully
charged
0
Time
0
Period 2
Period 3
Period 1
The recharge process usually consists of three periods. During the first period, the
current is maintained at approximately 0.4 amperes. In the second period, the constant-
voltage control starts and the current gradually decreases as the batteries continue to
charge. In the third period, a slight current flows into the batteries to keep them fully
charged. After a complete discharge, a full recharge usually requires 24 hours (90%
recharge in 8 hours).
The chart depicted below shows the rated maximum and minimum battery voltages,
and the charge current for each of the sizes.
Rated battery voltages
Model
Vmax.
68.2
68.2
68.2
68.2
Vmin.
48.0
48.0
48.0
48.0
Charge
0.4 (A)
0.4 (A)
0.4 (A)
0.4 (A)
600 VA / 600 VA Plus
800 VA / 800 VA Plus
1000 VA / 1000 VA Plus
1200 VA
5 - 5
TOSHIBA
5.0
Operating the UPS
5.7
Battery Backup Time
The UPS unit's batteries provide about 5-12 minutes of back-up time depending on the
capacity of the UPS. These times are valid when a unit is operating under full load. When
the units are operating at half load, the batteries can power the load equipment about 3
times longer. The exact length of these times will depend on the UPS model used,
condition of the batteries, amount of load, temperature and other variables. See battery
backup time in the standard specifications Sections 4.1 through 4.2.
5.8
Battery Low Voltage Tolerances
Excessive discharge will cause the UPS unit's battery voltage to drop. The chart shown
below lists the voltage level at which each UPS unit's low-voltage alarm will sound and
also at what level the low-voltage condition will cause the unit to automatically shut down.
UPS Capacity
600VA
60.0
800VA
60.0
1000VA 1200VA
600VA
Plus
800VA
Plus
1000VA
Plus
Nominal voltage
in Vdc
60.0
52.8
48.0
60.0
52.8
48.0
60.0
52.8
48.0
60.0
52.8
48.0
60.0
52.8
48.0
Alarm voltage
in Vdc
52.8
52.8
Shutdown voltage
48.0
48.0
5.9
Battery Check Function
Part of the UPS start-up procedure is an automatic 'Battery Check' to see if a problem
exists in the battery circuit. When the UPS is started it will begin operation in the bypass
mode. An automatic voltage level test of the batteries is made while operating in the
bypass mode for five seconds. A failure of this first test will activate visual and audible
alarms (see section 5.3.3 "battery problem"). If this test is passed, then the UPS will auto-
transfer from bypass mode to on line operating mode. A ten second automatic voltage
check of the batteries is made after the UPS has auto-transferred from bypass to on line
mode. Normal on line operation continues if the second test is passed. If the second test
fails, then the "Fault" LED will flash and up to three additional automatic battery voltage
checks are made at 3 hour intervals while the inverter continues to operate. If the
batteries are found to be normal during one of these three tests then the "Fault" LED
will stop flashing and normal inverter operation will continue. A failure of the third and
final check will activate visual and audible alarms (see section 5.3.3 "battery problem")
causing an auto-transfer back to bypass. If the batteries are indicated "bad" then
STOP the UPS and allow a 24 hour charge on the batteries before restarting.
5.10
System Reset
The UPS is reset by moving the STOP/RUN switch from "run" to "stop" and then back
to "run". Use the reset procedure to transfer from bypass back to inverter after a fault
occurs. Some faults may only be cleared by shutting down the UPS, waiting for all LED's
on the front panel to go off, and then restarting the UPS.
5 - 6
TOSHIBA
6.0
UPS Control Interface
6.1
DB25 Connector Pinout
RS-232C serial communication and Dry Contacts are both standard features available
through a DB25 female connector located on the back panel of the UPS (see Section 9.1).
The RS-232C serial communication interface allows control of the UPS from a personal
computer running special Toshiba software. The computer is connected to the UPS
through a serial RS-232C communication port. The Dry Contact interface is available as
open or closed contacts. An adapter is available from Toshiba for splitting the RS-232C
and Dry Contact interfaces into two separate DB9 connectors. Contact Toshiba for more
information on this option. The following chart shows the pin assignments for the DB25
connector.
Pin
Symbol
0V
Description
1
2
Supply used by Slide-In Options cards (-)
Supply used by Slide-In Options cards (+)
UPS receive line
+9V
3
RXD_UPS
TXD_UPS
TXD_AUX
RXD_AUX
4
UPS transmit line
5
Auxiliary transmit line
6
Auxiliary receive line
7
(not used)
8
SNMPSIG1
RS_Common
SNMPSIG2
DTR
SNMP option card function
Common line for RS-232C communication
SNMP option card function
UPS data terminal ready
UPS data set ready
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
DSR
RTS
UPS request to send
CTS
UPS clear to send
(not used)
Dry_Common
Backup_O
Backup_C
Low_Battery
Inverter
Common line for Dry Contact signals
Open during Battery Backup
Closed during Battery Backup
Closed during Low Battery
Closed during On-Line mode
Closed during Bypass mode
Closed during Fault
Bypass
Fault
(not used)
SD_Signal
Shutdown command signal line
Shutdown command common line
SD_Common
6 - 1
TOSHIBA
6.0
UPS Control Interface
6.2
RS-232C Serial Communication Interface
The available data from the UPS, via RS-232C communication, is shown below:
Output voltage
Output current
Battery voltage
Input frequency
Output frequency
Operating conditions
Utility power OK
Low battery voltage detected
UPS in BYPASS mode
UPS operating status
(described as yes or no)
UPS in NORMAL mode
Input and output frequency synchronized
UPS fault occurred
DC bus overcurrent
DC bus overvoltage
DC bus undervoltage
'Fault details
(described as occurred
or not occurred)
Input overcurrent
Overheat
Overload being timed
Overload (allowable time exceeded)
Output overvoltage (during NORMAL mode)
Output undervoltage (during NORMAL mode)
6.2.1 UPS Shutdown (via RS-232C)
When the UPS is operating from its internal batteries, a shutdown order can be
sent to the UPS telling it to turn OFF after a user-specified amount of time. This
function can allow you to stop discharging the UPS batteries after an orderly
system shutdown has been completed. The UPS can be programmed to turn
OFF up to 8 minutes after the shutdown command is given. This command can
be cancelled before the specified time has elapsed.
6.3
Dry Contact Interface
The Dry Contact interface uses pins 16 trough 22. Pins 24 and 25 are used for the
shutdown function. The following schematic shows the contact state and pin assignments
for each signal output along with the associated DB25 connector pinout.
16 Dry Contact common
17
18
Notes:
1) Pin switches are shown
Battery Backup
}
in their inactive states
(ex. if battery voltage is
low then pin 19 will be
connected to pin 16)
19 Battery voltage low
20 UPS on
2) Contacts are rated as
follows:
21 Bypass on
dc: 48V, 0.1A
ac: 30Vrms (42V-peak)
0.07A(0.1A-peak)
22 Fault detect signal
6 - 2
TOSHIBA
7.0
Troubleshooting Procedures
Faults are those abnormal conditions that can occur and cause the unit to shutdown normal
operation. The faults are detected by the protection circuitry (see System Protection Features
Section 5.2) in the unit. The UPS Fault lamp will light red. "Troubleshooting" involves monitoring
the bar graph lamps on the front panel and then interpreting the readout by using the fault mode
display charts.
7.1
Non-Fatal Fault Mode
Non-fatal faults may or may not cause the unit to shut down. These faults normally will
cause the UPS to transfer to bypass mode. Use "System Restart" procedures (see
Section 5.10) to transfer the UPS back to On Line mode. Use the following chart to
decode the display. All non-fatal faults will cause the red Fault LED to flash.
Non-Fatal Fault Mode Display Chart
Fault
Display status
Probable cause
Corrective action
Remove cause of
short circuit. If none is
found, contact your
Toshiba service
Output low
voltage
Inverter fault or short
circuit in UPS output
representative.
Output
overvoltage
Resonance with load
equipment
Remove load
equipment one piece
at a time.
DC
undervoltage
Chopper fault
Contact your Toshiba
service representative.
Check for airflow
restriction. If none is
found, contact your
Toshiba service
Cooling fin
overheating
Cooling fan outage or
closed cooling airflow
path
representative.
Battery damaged or
something wrong in the
Battery
Contact your Toshiba
problem
battery circuit (battery may service representative.
not be connected)
Output
overload
Capacity of load
equipment to high
Review UPS rating
or reduce load
equipment.
7 - 1
TOSHIBA
7.0
Troubleshooting Procedures
7.2
Fatal Fault Mode
Fatal faults may or may not cause the UPS to shutdown. Use "System Reset" procedures
(see Section 5.10) to transfer UPS back to On Line mode. Use the following chart to
decode the display. All fatal faults will cause the red Fault LED to light continuously.
Fatal Fault Mode Display Chart
Fault
Display status
Probable cause
Corrective action
DC
Inverter fault
overcurrent
DC
overvoltage
Chopper fault
Chopper fault
Contact your Toshiba
service representative.
Input
overcurrent
UPS system
error
Trouble with the control
PWB
= Flashing LED
= Steady-lit LED
7 - 2
TOSHIBA
8.0
Preventive and Scheduled Maintenance/Parts Replacement
8.1
Preventive Maintenance
Toshiba's 1500 and 1500 Plus Series of uninterruptible power systems have been
designed to provide years of trouble-free operation requiring a minimum of preventive
maintenance.
The best preventive measure that the UPS user can take is to keep the area around the
unit, particularly the air inlet vents, clean and free of moisture and dust accumulations.
If the atmosphere of the installation site is very dusty, use a vacuum cleaner to
periodically remove dust accumulations from the system. Schedule authorized service
centers to perform internal parts inspections annually.
Before performing any maintenance, the technician should
be familiar with and follow the important safety instructions
located on pages vi and vii.
CAUTION
Proper maintenance of the battery system of this unit by a
qualified service technician is essential to the safety and
reliability of your UPS system. Refer to service manual.
WARNING
8.2
Parts Replacement
The following list shows intervals for periodic maintenance and replacement of certain
UPS parts.
1)
Batteries: VRLA batteries are maintenance free with respect to electrolyte only.
The charging voltage, temperature, performance and connection resistance must
be monitored periodically. Necessary corrective actions must be made in order to
assure safe reliable power is supplied by the UPS. The aforementioned items
affect the life of batteries, so replacement should be done once every 3 to 5 years
at a minimum. All of the batteries must be replaced at the same time.
Quarterly maintenance
a) Visual checks
1) Leakage
2) Corrosion on positive terminal
b) Check battery temperature at the negative terminal.
c) Measure and record the system float charging voltage.
d) Measure and record the individual units float charging voltage.
Semi-Annual maintenance
a) Repeat the quarterly checks.
b) Perform a 10 second high rate (e.g. 100 amp) load test on the
individual batteries.
c) Optionally test for the purpose of trending the battery over time.
d) Re-torque all inter-battery connecting hardware (if applicable).
e) Perform inter-battery connector resistance checks.
2)
3)
Aluminum electrolytic capacitors: Replace once every 5 years.
Fuses: Replace once every 7 years (see output fuse rating chart on the following
page).
4)
Cooling fan: Replace once every 3 years.
8 - 1
TOSHIBA
8.0
Preventive and Scheduled Maintenance/Parts Replacement
8.3
Fuse Rating Chart
The following chart shows the recommended fuses for all UPS sizes.
Fuse rating
Model
600 VA
Amp rating
15.0A
Fuse model no.
LittleFuse 314015
LittleFuse 314015
LittleFuse 314015
LittleFuse 314015
LittleFuse 314015
LittleFuse 314015
LittleFuse 314015
800 VA
15.0A
1000 VA
15.0A
1200 VA
15.0A
600 VA Plus
800 VA Plus
1000 VA Plus
15.0A
15.0A
15.0A
Download from Www.Somanuals.8com-.2All Manuals Search And Download.
TOSHIBA
9.0
External Dimensions/Shipping Weights/Panel Layout
9.1
External Dimensions
8.00
Input power
cord connector
Fuse
Slide-in
Option
Card
Run/Stop
switch.
0: Stop
1: Run
10.00
Front
View
Rear
View
Output
Receptacles
Computer
Interface
Air Vents
Connector
20.38
Side
View
9 - 1
TOSHIBA
9.0
External Dimensions/Shipping Weights/Panel Layout
9.2
Panel Layout
9.3
Shipping Weights
UPS
Model
Shipping Weight
Pounds
Kilograms
22.2
600 VA
48.8
48.8
52.2
52.2
66.0
66.0
69.4
800 VA
22.2
1000 VA
23.7
1200 VA
23.7
600 VA Plus
800 VA Plus
1000 VA Plus
30.0
30.0
31.5
9 - 2
TOSHIBA INTERNATIONAL CORPORATION
INDUSTRIAL DIVISION
13131 West Little York Rd., Houston Texas 77041
Tel: [800] 231-1412 Fax: [713] 466-8773 Telex: 762078
Printed in U.S.A.
|