inSTaLLaTiOn and mainTenanCe inSTrUCTiOnS
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
m500S Supervised Control module
SpeCifiCaTiOnS
Normal Operating Voltage:
Maximum Current Draw:
Operating Current:
15 to 32 VDC
6.5mA (LED On)
350 µA max., 1 communication every 5 seconds 47k EOL resistor; 485 µA max. (Communicating, NAC Shorted)
4 VDC
Maximum NAC Line Loss:
External Supply Voltage (between Terminals T10 and T11)
Maximum (NAC):
Maximum (Speakers):
Max. NAC Current Ratings:
Temperature Range:
Humidity:
Regulated 24VDC
70.07 V RMS, 50 W
For class B wiring system, the current rating is 3A; For class A wiring system, the current rating is 2A
32˚F to 120˚F (0˚C to 49˚C)
10% to 93% Non-condensing
1
Dimensions:
41/2˝ H × 4˝ W × 1 /4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories:
SMB500 Electrical Box; CB500 Barrier
BefOre inSTaLLing
figUre 2a. mOdULe mOUnTing
figUre 2B:
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
WiTh Barrier:
NOTICE: This manual should be left with the owner/user of this equipment.
generaL deSCripTiOn
M500S Supervised Control Modules are intended for use in intelligent, two-
wire systems, where the individual address of each module is selected using
the built-in rotary decade switches. This module is used to switch an external
power supply, which can be a DC power supply or an audio amplifier (up
to 80 VRMS), to notification appliances. It also supervises the wiring to the
connected loads and reports their status to the panel as NORMAL, OPEN,
or SHORT CIRCUIT. The M500S has two pairs of output termination points
available for fault-tolerant wiring and a panel-controlled LED indicator. This
module can be used to replace an M500C module that has been configured for
supervised wiring operation.
ISOLATED
QUADRANT
COmpaTiBiLiTY reqUiremenTS
To ensure proper operation, these modules shall be connected to listed com-
patible system control panels only.
figUre 1. COnTrOLS and indiCaTOrS:
C1050-00
Wiring
NOTE: All wiring must conform to applicable local codes, ordinances, and reg-
ulations. When using control modules in nonpower limited applications, the
System Sensor CB500 Module Barrier must be used to meet UL requirements
for the separation of power-limited and nonpower-limited terminals and wir-
ing. The barrier must be inserted into a 4˝×4˝×21/8˝ junction box, and the
control module must be placed into the barrier and attached to the junction
box (Figure 2A). The power-limited wiring must be placed into the isolated
quadrant of the module barrier (Figure 2B).
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
C0909-01
mOUnTing
2. Set the address on the module per job drawings.
The M500S mounts directly to 4-inch square electrical boxes (see Figure 2A).
The box must have a minimum depth of 21/8 inches. Surface mounted electri-
cal boxes (SMB500) are available from System Sensor.
3. Secure module to electrical box (supplied by installer), as shown in
Figure 2A.
SS-460-001
1
I56-3850-002
figUre 5. TYpiCaL Wiring fOr Speaker SUperviSiOn and SWiTChing, nfpa STYLe Y:
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE PANEL INSTALLATION MANUAL FOR DETAILED INFORMATION.
CONNECT MODULES TO LISTED COMPATIBLE
CONTROL PANELS ONLY
WIRES MUST BE
AUDIO CIRCUIT
SUPERVISED PER NFPA
DO NOT LOOP WIRE AROUND TERMINALS
10 & 11. BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
( – )
FROM PANEL OR
PREVIOUS DEVICE
CONTROL
MODULE
( + )
AUDIO AMPLIFIER, 70.7 Vrms MAX.
AMPLIFIER MUST PROVIDE WIRING
SUPERVISION PER NFPA.
( – )
( + )
) ( –
) ( +
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
( – )
– ( )
IS RECOMMENDED
47K EOL
RESISTOR
ELR-47K
( + )
( + )
(–)
(+)
MODULE POLARITIES ARE
SHOWN IN ALARM
TO NEXT
DEVICE
SUPERVISION
TO NEXT CONTROL MODULE
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
SPEAKERS MUST BE LISTED FOR FIRE
PROTECTION. REFER TO THE RELAY CONTACT
RATING TABLE FOR MAXIMUM LOAD.
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0915-03
figUre 6. TYpiCaL faULT TOLeranT Wiring fOr Speaker SUperviSiOn and SWiTChing, nfpa STYLe Z:
AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE PANEL INSTALLATION MANUAL FOR DETAILED INFORMATION.
CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY
AUDIO CIRCUIT
FROM
DO NOT LOOP WIRE AROUND TERMINALS
10 & 11. BREAK WIRE TO ENSURE
SUPERVISION OF CONNECTIONS.
WIRES MUST BE
( – )
( + )
PANEL OR
PREVIOUS
DEVICE
SUPERVISED PER NFPA
CONTROL
MODULE
AUDIO AMPLIFIER, 70.7 Vrms MAX.
( – )
AMPLIFIER MUST PROVIDE WIRING
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
SUPERVISION PER NFPA.
( + )
) ( –
) ( +
TWISTED PAIR
IS RECOMMENDED
47K EOL RESISTOR
IS INTERNAL AT
( – )
( + )
( – )
( + )
ALL WIRING SHOWN IS SUPERVISED
AND POWER LIMITED
TERMINALS 8 & 9
(–)
(+)
TO NEXT
DEVICE
BYPASS CAPACITORS: 100µ
A2143-20 NONPOLARIZED
<10µA LEAKAGE
TO NEXT CONTROL MODULE
LAST MODULE MUST RETURN
WIRES FOR SUPERVISION
SUPERVISION
SPEAKERS MUST BE LISTED FOR
FIRE PROTECTION. REFER TO THE
RELAY CONTACT RATING TABLE
FOR MAXIMUM LOAD.
MODULE POLARITIES ARE
SHOWN IN ALARM
*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.
C0916-03
SS-460-001
3
I56-3850-002
WARNING
All relay switch contacts are shipped in the standby state (open) state, but may have transferred to the activated (closed) state during shipping. To ensure that
the switch contacts are in their correct state, modules must be made to communicate with the panel before connecting circuits controlled by the module.
Three-Year LimiTed WarranTY
System Sensor warrants its enclosed module to be free from defects in materials and
workmanship under normal use and service for a period of three years from date of
manufacture. System Sensor makes no other express warranty for this module. No agent,
representative, dealer, or employee of the Company has the authority to increase or
alter the obligations or limitations of this Warranty. The Company’s obligation of this
Warranty shall be limited to the repair or replacement of any part of the module which
is found to be defective in materials or workmanship under normal use and service
during the three year period commencing with the date of manufacture. After phoning
System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return Authorization
number, send defective units postage prepaid to: System Sensor, Repair Department, RA
#__________, 3825 Ohio Avenue, St. Charles, IL 60174. Please include a note describing
the malfunction and suspected cause of failure. The Company shall not be obligated to
repair or replace units which are found to be defective because of damage, unreasonable
use, modifications, or alterations occurring after the date of manufacture. In no case shall
the Company be liable for any consequential or incidental damages for breach of this
or any other Warranty, expressed or implied whatsoever, even if the loss or damage is
caused by the Company’s negligence or fault. Some states do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation or exclusion
may not apply to you. This Warranty gives you specific legal rights, and you may also
have other rights which vary from state to state.