Pelco Switch C808M G User Manual

I N S T A L L A T I O N / O P E R A T I O N  
VS5004/VS5008  
Sequential Switcher  
®
C808M-G (4/05)  
 
Description  
The VS5004 and VS5008 sequential switchers are designed to switch up to four (VS5004) or eight (VS5008) cameras manually or automatically to  
one or two monitors with automatic response to alarm inputs. Both versions are Coaxitron® compatible and can be placed on a desktop or rack  
mounted.  
MODELS  
VS5004  
VS5004/220  
VS5008  
Sequential switcher with four camera inputs and two monitor outputs, 120 VAC  
Same as VS5004 except 230 VAC  
Sequential switcher with eight camera inputs and two monitor outputs, 120 VAC  
Same as VS5008 except 230 VAC  
VS5008/220  
C808M-G (4/05)  
3
 
   
Installation  
TERMINATED CAMERA INPUTS AND ONE MONITOR OUTPUT  
1. Make all equipment connections. Refer to Figure 1 (VS5004) or Figure 2 (VS5008).  
VS5008 only: When configured for one-monitor operation, the monitor must be connected to the MON 2 output. The MON 1 output must  
be terminated with a 75-ohm BNC terminator.  
2. Make alarm connections if required. Refer to Figure 3 (VS5004) or Figure 4 (VS5008) and do the following:  
VS5004  
a. Input: Connect the alarm contact between the appropriate input (pins 1-4) and common (pin 5) on the 6-pin connector receptacle.  
Pins 1 thru 4 directly correspond with the like-numbered front panel camera switches of the VS5004. The alarm output is an  
open-collector NPN transistor. Current from the output to circuit ground should not exceed 600 mA.  
b. Output: To activate an external device during an alarm, connect the device at pins 5 and 6 on the 6-pin connector.  
VS5008  
a. Input: Connect the alarm contact between the appropriate ALARM INPUT (terminals 1-8) and common (COM) terminal. The alarm  
output is an open-collector NPN transistor. Current from the output to circuit ground should not exceed 40 mA.  
b. Output: To activate an external device during an alarm, connect the device at the ALARM OUT terminal and the common (COM)  
terminal.  
3. Set the ALARM switch to the ON position.  
NOTES:  
When an alarm occurs, the monitor immediately switches to the alarmed channel, and the associated LED blinks. Multiple alarmed  
channels sequence every five seconds (VS5004) or three seconds (VS5008). The alarm has priority over the MONITOR/AUTO/BYPASS  
switch settings.  
Once triggered, the alarm remains on until the input condition is removed or the ALARM switch is moved to the OFF position.  
When the ALARM switch is set to the OFF position, all alarm inputs are ignored.  
4. For channels with cameras connected to the video inputs, set the front panel switches to the AUTO position. All unconnected video inputs  
should have their channel switches set to the BYPASS position.  
NOTE: All channels with a switch in the AUTO position will automatically sequence through the monitor. To view one specific channel  
continuously, set the corresponding switch to the MONITOR position. To remove a channel from the sequence, set the corresponding switch to  
the BYPASS position.  
5. Connect the AC adapter to the 12 VAC input plug on the rear of the VS5004 or VS5008. Connect the transformer to a 120 VAC (VS5004 or  
VS5008) or 230 VAC (VS5004/220 or VS5008/220) power source. After power up, the switcher will begin sequencing.  
6. Using a screwdriver, adjust the DWELL interval control to the desired setting. This control adjusts the interval time from a minimum of  
1 second to a maximum of 70 seconds nominal. To increase the interval, turn the control clockwise. To decrease the interval, turn the  
control counterclockwise. The DWELL interval control is a precision 15-turn potentiometer. Each complete turn of this control will adjust the  
time interval by approximately 4 to 5 seconds.  
MON 1  
BRIGHT  
CONTRAST  
12 VAC  
INPUT  
ALARM  
4
3
2
1
MON 1  
MON 2  
IN 1 2 3 4  
OUT 6  
COMMON 5  
Figure 1. VS5004 Terminated Camera Inputs - One Monitor  
4
C808M-G (4/05)  
 
     
NOTE: MON 1 MUST BE  
TERMINATED.  
CAMERAS  
MON 1  
ALARM  
INPUT  
COM  
12 VAC  
8
7
6
5
4
3
2
1
MON 2 MON X  
1
2
3
4
5
6
7
8
INPUT  
ALARM OUT  
VS5008 (REAR)  
Figure 2. VS5008 Terminated Camera Inputs - One Monitor  
6-PIN CONNECTOR  
RECEPTACLE  
YEL  
BRN  
RD  
REAR VIEW  
4
5
6
1
2
3
GRN  
BLK  
OR  
CAMERAS  
3
12VAC  
INPUT  
ALARM  
MON 1  
MON 2  
4
4
2
1
IN 1 2 3 4  
OUT 6 -- TO VCR  
COMMON  
3
2
1
5
TO EXTERNAL  
ALARM CIRCUITRY  
Figure 3. VS5004 Alarm Connections  
C808M-G (4/05)  
5
 
   
UP TO EIGHT ALARM INPUTS (ALARM INPUT FROM  
MOTION DETECTOR, DOOR CONTACT, ETC., THROUGH  
NORMALLY OPEN SWITCH). EACH ALARM DEVICE MUST BE  
CONNECTED TO THE "COM" TERMINAL.  
UP TO EIGHT VIDEO INPUTS  
CAMERAS  
MON 1  
ALARM  
COM  
12 VAC  
INPUT  
INPUT  
8
7
6
5
4
3
2
1
MON 2 MON X  
1
2
3
4
5
6
7
8
ALARM OUT  
VS5008 (REAR)  
VCR  
OPEN COLLECTOR OUTPUT FOR  
VCR ACTIVATION IN ALARM  
CONDITION. ONLY ONE VCR  
CAN BE USED IN THIS  
CONFIGURATION.  
Figure 4. VS5008 Alarm Connections  
6
C808M-G (4/05)  
 
 
LOOPING CAMERA INPUTS AND ONE MONITOR OUTPUT  
1. Convert the switcher to looping operation. Refer to Figure 5 and do the following:  
NOTE: Looping and terminated inputs may be mixed.  
a. Remove the cover.  
b. Remove the rear panel of the chassis.  
c. Locate the 75-ohm resistors located on the inside of the rear panel BNC jacks.  
d. For each input to be looped, use wire cutters to clip one of the attached resistor leads.  
e. Replace the cover.  
2. Make all equipment connections. Refer to Figure 6 (VS5004) or Figure 7 (VS5008).  
VS5008 only: When configured for one-monitor operation, the monitor must be connected to the MON 2 output. The MON 1 output must  
be terminated with a 75-ohm BNC terminator.  
3. Make alarm connections if required. Refer to Figure 3 (VS5004) or Figure 4 (VS5008) and do the following:  
VS5004  
a. Input: Connect the alarm contact between the appropriate input (pins 1-4) and common (pin 5) on the 6-pin connector receptacle.  
Pins 1 thru 4 correspond directly with the like-numbered front panel camera switches of the VS5004. The alarm output is an  
open-collector NPN transistor. Current from the output to circuit ground should not exceed 600 mA.  
b. Output: To activate an external device during an alarm, connect the device at pins 5 and 6 on the 6-pin connector.  
VS5008  
a. Input: Connect the alarm contact between the appropriate ALARM INPUT (terminals 1-8) and common (COM) terminal. The alarm  
output is an open-collector NPN transistor. Current from the output to circuit ground should not exceed 40 mA.  
b. Output: To activate an external device during an alarm, connect the device at the ALARM OUT terminal and the common (COM)  
terminal.  
4. Set the ALARM switch to the ON position.  
NOTES:  
When an alarm occurs, the monitor immediately switches to the alarmed channel, and the associated LED blinks. Multiple alarmed  
channels sequence every five seconds (VS5004) or three seconds (VS5008). The alarm has priority over the MONITOR/AUTO/BYPASS  
switch settings.  
Once triggered, the alarm remains on until the input condition is removed or the ALARM switch is moved to the OFF position.  
When in the ALARM switch is set to the OFF position, all alarm inputs are ignored.  
5. For channels with cameras connected to the video inputs, set the front panel switches to the AUTO position. All unconnected video inputs  
should have their channel switch set to the BYPASS position.  
NOTE: All channels with a switch in the AUTO position will automatically sequence through the monitor. To view one specific channel  
continuously, set the corresponding switch to the MONITOR position. To remove a channel from the sequence, set the corresponding switch to  
the BYPASS position.  
6. Connect the AC adapter to the 12 VAC input plug on the rear of the VS5004 or VS5008. Connect the transformer to a 120 VAC (VS5004 or  
VS5008) or 230 VAC (VS5004/220 or VS5008/220) power source. After power up, the switcher will begin sequencing.  
7. Using a screwdriver, adjust the DWELL interval control to the desired setting. This control adjusts the interval time from a minimum of  
1 second to a maximum of 70 seconds nominal. To increase the interval, turn the control clockwise. To decrease the interval, turn the  
control counterclockwise. The DWELL interval control is a precision 15-turn potentiometer. Each complete turn of this control will adjust the  
time interval by approximately 4 to 5 seconds.  
C808M-G (4/05)  
7
 
 
75-OHM RESISTOR  
CLIP HERE  
FOR EACH  
CHANNEL  
REAR PANEL (SWITCHER)  
BNC CONNECTOR  
Figure 5. Looping Conversion Modification  
MON 1  
BRIGHT  
CONTRAST  
12 VAC  
INPUT  
ALARM  
4
3
2
1
MON 1  
MON 2  
IN 1 2 3 4  
OUT 6  
COMMON 5  
VIDEO INPUTS  
ADDITIONAL EQUIPMENT  
TERMINATED  
Figure 6. VS5004 Looping Camera Inputs - One Monitor  
8
C808M-G (4/05)  
 
   
NOTE: IN THIS CONFIGURATION,  
MON 1 MUST BE TERMINATED  
AND THE UNIT MUST BE MODIFIED  
TO BE LOOPING (REFER TO FIGURE 5).  
CAMERAS  
MON 1  
ALARM  
COM  
12 VAC  
INPUT  
INPUT  
8
7
6
5
4
3
2
1
MON 2 MON X  
1
2
3
4
5
6
7
8
ALARM OUT  
VS5008 (REAR)  
VIDEO INPUTS  
ADDITIONAL EQUIPMENT  
TERMINATED  
Figure 7. VS5008 Looping Camera Inputs - One Monitor  
TERMINATED CAMERA INPUTS AND TWO MONITOR OUTPUTS  
1. Convert the VS5004 to dual-monitor operation. Refer to Figure 8 and do the following:  
a. Remove the cover.  
b. Remove the rear panel of the chassis.  
c. Remove the four screws attaching the PC board to the chassis.  
d. Pull the PC board and rear panel assembly out of the chassis.  
e. Turn the PC board over and rewire.  
f.  
Replace the PC board, rear panel assembly, and cover.  
2. Make all equipment connections. Refer to Figure 9 (VS5004) or Figure 10 (VS5008).  
VS5004 only: In this configuration, MON 1 must be terminated with a 75-ohm terminator and MON 2 must be terminated in the HI Z position.  
3. Make alarm connections if required. Refer to Figure 3 (VS5004) or Figure 4 (VS5008) and do the following:  
VS5004  
a. Input: Connect the alarm contact between the appropriate input (pins 1-4) and common (pin 5) on the 6-pin connector receptacle.  
Pins 1 thru 4 correspond directly with the like-numbered front panel camera switches of the VS5004. The alarm output is an  
open-collector NPN transistor. Current from the output to circuit ground should not exceed 600 mA.  
b. Output: To activate an external device during an alarm, connect the device at pins 5 and 6 on the 6-pin connector.  
VS5008  
a. Input: Connect the alarm contact between the appropriate ALARM INPUT (terminals 1-8) and common (COM) terminal. The alarm  
output is an open-collector NPN transistor. Current from the output to circuit ground should not exceed 40 mA.  
b. Output: To activate an external device during an alarm, connect the device at the ALARM OUT terminal and the common (COM)  
terminal.  
C808M-G (4/05)  
9
 
   
4. Set the ALARM switch to the ON position.  
NOTES:  
With all channel switches set to the AUTO position, both monitors immediately switch to the alarmed channel and the associated LED  
blinks. Multiple alarmed channels sequence every five seconds (VS5004) or three seconds (VS5008). The alarm has priority over the  
MONITOR/AUTO/BYPASS switch settings.  
If a channel switch is set to the MONITOR position, Monitor 1 switches to the alarmed channel while Monitor 2 displays the selected  
(MONITOR) channel.  
If a channel switch is set to the BYPASS position, Monitor 1 switches to that channel if it is alarmed.  
Once triggered, the alarm remains on until the input condition is removed or the ALARM switch is moved to the OFF position.  
When in the ALARM switch is set to the OFF position, all alarm inputs are ignored.  
5. For channels with cameras connected to the video inputs, set the front panel switches to the AUTO position. All unconnected video inputs  
should have their channel switch set to the BYPASS position.  
NOTES:  
With all channel switches in the AUTO position, both monitors sequence simultaneously.  
Monitor 2 can be manually switched to any channel for continuous viewing by setting the desired channel’s switch to the MONITOR  
position. If multiple channels are set to MONITOR, only the lowest numbered channel will be displayed. This does not affect the  
sequencing for Monitor 1.  
To remove a channel from the sequence, set the corresponding switch to the BYPASS position.  
6. Connect the AC adapter to the 12 VAC input plug on the rear of the VS5004 or VS5008. Connect the transformer to a 120 VAC (VS5004 or  
VS5008) or 230 VAC (VS5004/220 or VS5008/220) power source. After power up, the switcher will begin sequencing.  
7. Using a screwdriver, adjust the DWELL interval control to the desired setting. This control adjusts the interval time from a minimum of  
1 second to a maximum of 70 seconds nominal. To increase the interval, turn the control clockwise. To decrease the interval, turn the  
control counterclockwise. The DWELL interval control is a precision 15-turn potentiometer. Each complete turn of this control will adjust the  
time interval by approximately 4 to 5 seconds.  
MON 1 MON 2  
PCB 90000101 COMPONENT SIDE  
J1  
1
1
G
J2  
X5  
H5  
BLU  
X4  
H6  
H3  
X3  
X2  
ORG  
B4  
B3  
V4  
V3  
H2  
H1  
4
1
5
2
6
3
B2 V2  
VG  
RED  
BRN  
X1  
B1 V1  
X6  
B5  
MON1  
GRN  
W/RED  
TO CONVERT PC BOARD TO TWO MONITOR OPERATION,  
REROUTE THE JUMPER WIRES AS FOLLOWS.  
WIRE COLOR  
REMOVE WIRE  
CONNECT WIRE  
FROM PIN  
TO PIN  
B1  
B2  
B3  
B4  
B5  
H5  
X6  
BROWN  
RED  
ORANGE  
YELLOW  
GREEN  
BLUE  
H1  
H2  
H3  
H4  
H5  
X6  
G
WHITE/RED  
Figure 8. VS5004 Conversion For Two-Monitor Operation  
10  
C808M-G (4/05)  
 
 
MON 2  
MON 1  
BRIGHT  
CONTRAST  
BRIGHT  
CONTRAST  
12 VAC  
INPUT  
ALARM  
4
3
2
1
MON 1  
MON 2  
IN 1 2 3 4  
OUT 6  
COMMON 5  
NOTE: IN THIS CONFIGURATION, MON 1 MUST BE TERMINATED WITH A 75-OHM TERMINATOR  
AND MON 2 MUST BE IN THE “HI Z” POSITION.  
Figure 9. VS5004 Terminated Camera Inputs - Two Monitors  
CAMERAS  
MON 1  
ALARM  
INPUT  
COM  
12 VAC  
INPUT  
8
7
6
5
4
3
2
1
MON 2 MON X  
1
2
3
4
5
6
7
8
ALARM OUT  
VS5008 (REAR)  
Figure 10. VS5008 Terminated Camera Inputs - Two Monitors  
C808M-G (4/05)  
11  
 
   
LOOPING CAMERA INPUTS AND TWO MONITOR OUTPUTS  
1. Convert the VS5004 to dual-monitor operation. Refer to Figure 8 and do the following:  
a. Remove the cover.  
b. Remove the rear panel of the chassis.  
c. Remove the four screws attaching the PC board to the chassis.  
d. Pull the PC board and rear panel assembly out of the chassis.  
e. Turn the PC board over and rewire.  
2. Convert to looping operation. Refer to Figure 5 and do the following:  
NOTE: Looping and terminated inputs may be mixed.  
a. Locate the 75-ohm resistors located on the inside of the rear panel BNC jacks.  
b. For each input to be looped, use wire cutters to clip one of the attached resistor leads.  
c. Replace the cover.  
3. Make all equipment connections. Refer to Figure 11 (VS5004) or Figure 12 (VS5008).  
(VS5004 only) In this configuration, MON 1 must be terminated with a 75-ohm terminator and MON 2 must be terminated in the  
HI Z position.  
4. Make alarm connections if required. Refer to Figure 3 (VS5004) or Figure 4 (VS5008) and do the following:  
VS5004  
a. Input: Connect the alarm contact between the appropriate input (pins 1-4) and common (pin 5) on the 6-pin connector receptacle.  
Pins 1 thru 4 correspond directly with the like-numbered front panel camera switches of the VS5004. The alarm output is an  
open-collector NPN transistor. Current from the output to circuit ground should not exceed 600 mA.  
b. Output: To activate an external device during an alarm, connect the device at pins 5 and 6 on the 6-pin connector.  
VS5008  
a. Input: Connect the alarm contact between the appropriate ALARM INPUT (terminals 1-8) and common (COM) terminal. The alarm  
output is an open-collector NPN transistor. Current from the output to circuit ground should not exceed 40 mA.  
b. Output: To activate an external device during an alarm, connect at the ALARM OUT terminal and the common (COM) terminal.  
5. Set the ALARM switch to the ON position.  
NOTES:  
With all channel switches set to the AUTO position, both monitors immediately switch to the alarmed channel and the associated LED  
blinks. Multiple alarmed channels sequence every five seconds (VS5004) or three seconds (VS5008). The alarm has priority over the  
MONITOR/AUTO/BYPASS switch settings.  
If a channel switch is set to the MONITOR position, Monitor 1 switches to the alarmed channel while Monitor 2 displays the selected  
(MONITOR) channel.  
If a channel switch is set to the BYPASS position, Monitor 1 switches to that channel if alarmed.  
Once triggered, the alarm remains on until the input condition is removed or the ALARM switch is moved to the OFF position.  
When in the ALARM switch is set to the OFF position, all alarm inputs are ignored.  
6. For channels with cameras connected to the video inputs, set the front panel switches to the AUTO (center) position. All unconnected video  
inputs should have their channel switch set to the BYPASS (down) position.  
NOTES:  
With all channel switches in the AUTO position, both monitors sequence simultaneously.  
Monitor 2 can be manually switched to any channel for continuous viewing by setting the desired channel’s switch to the MONITOR  
position. If multiple channels are set to MONITOR, only the lowest numbered channel will be displayed. This does not affect the  
sequencing for Monitor 1.  
To remove a channel from the sequence, set the corresponding switch to the BYPASS position.  
12  
C808M-G (4/05)  
 
 
7. Connect the AC adapter to the 12 VAC input plug on the rear of the VS5004 or VS5008. Connect the transformer to a 120 VAC (VS5004 or  
VS5008) or 230 VAC (VS5004/220 or VS5008/220) power source. After power up, the switcher will begin sequencing.  
8. Using a screwdriver, adjust the DWELL interval control to the desired setting. This control adjusts the interval time from a minimum of  
1 second to a maximum of 70 seconds nominal. To increase the interval, turn the control clockwise. To decrease the interval, turn the  
control counterclockwise. The DWELL interval control is a precision 15-turn potentiometer. Each complete turn of this control will adjust the  
time interval by approximately 4 to 5 seconds.  
MON 2  
MON 1  
BRIGHT  
CONTRAST  
BRIGHT  
CONTRAST  
12 VAC  
INPUT  
ALARM  
4
3
2
1
MON 1  
MON 2  
IN 1 2 3 4  
OUT 6  
COMMON 5  
VIDEO INPUTS  
ADDITIONAL EQUIPMENT  
TERMINATED  
NOTE: MON 1 MUST BE TERMINATED WITH A 75-OHM TERMINATOR AND MON 2 MUST BE IN  
THE “HI Z” POSITION.  
Figure 11. VS5004 Looping Camera Inputs - Two Monitors  
NOTE: In this configuration  
the unit must be modified in  
order to be looping (refer to figure 5).  
CAMERAS  
MON 1  
ALARM  
COM  
12 VAC  
INPUT  
INPUT  
8
7
6
5
4
3
2
1
MON 2 MON X  
1
2
3
4
5
6
7
8
ALARM OUT  
VS5008 (REAR)  
VIDEO INPUTS  
ADDITIONAL EQUIPMENT  
TERMINATED  
Figure 12. VS5008 Looping Camera Inputs- Two Monitors  
C808M-G (4/05)  
13  
 
   
COAXITRON CONTROL  
To convert for use with a Coaxitron transmitter, do the following:  
1. Convert the VS5004 to dual-monitor operation. Refer to Figure 8 and do the following:  
a. Remove the cover.  
b. Remove the rear panel of the chassis.  
c. Remove the four screws attaching the PC board to the chassis.  
d. Pull the PC board and rear panel assembly out of the chassis.  
e. Turn the PC board over and rewire.  
2. Convert to looping operation. Refer to Figure 5 and do the following:  
NOTE: Looping and terminated inputs may be mixed.  
a. Locate the 75-ohm resistors located on the inside of the rear panel BNC jacks.  
b. For each input to be looped, use wire cutters to clip one of the attached resistor leads.  
c. Replace the cover.  
3. Make all equipment connections. Refer to Figure 13 (VS5004) or Figure 14 (VS5008).  
VS5004  
The Coaxitron transmitter must be passive (nonamplified).  
To operate a camera via Coaxitron signals, the corresponding channel switch must be in the MONITOR position.  
VS5008  
The Coaxitron transmitter must be active (amplified).  
4. Make alarm connections if required. Refer to Figure 3 (VS5004) or Figure 4 (VS5008) and do the following:  
VS5004  
a. Input: Connect the alarm contact between the appropriate input (pins 1-4) and common (pin 5) on the 6-pin connector receptacle.  
Pins 1 thru 4 correspond directly with the like-numbered front panel camera switches of the VS5004. The alarm output is an  
open-collector NPN transistor. Current from the output to circuit ground should not exceed 600 mA.  
b. Output: To activate an external device during an alarm, connect the device at pins 5 and 6 on the 6-pin connector.  
VS5008  
a. Input: Connect the alarm contact between the appropriate ALARM INPUT (terminals 1-8) and common (COM) terminal. The alarm  
output is an open-collector NPN transistor. Current from the output to circuit ground should not exceed 40 mA.  
b. Output: To activate an external device during an alarm, connect the device at the ALARM OUT terminal and the common (COM)  
terminal.  
5. Set the ALARM switch to the ON position.  
NOTES:  
When an alarm occurs, the monitor immediately switches to the alarmed channel, and the associated LED blinks. Multiple alarmed  
channels sequence every five seconds (VS5004) or three seconds (VS5008). The alarm has priority over the MONITOR/AUTO/BYPASS  
switch settings.  
VS5008 with two-monitor configuration:  
If a channel switch is set to the MONITOR position, Monitor 1 switches to the alarmed channel while Monitor 2 displays the selected  
(MONITOR) channel.  
If a channel switch is set to the BYPASS position, Monitor 1 switches to that channel if alarmed.  
Once triggered, the alarm remains on until the input condition is removed or the ALARM switch is moved to the OFF position.  
When in the ALARM switch is set to the OFF position, all alarm inputs are ignored.  
14  
C808M-G (4/05)  
 
 
6. For channels with cameras connected to the video inputs, set the front panel switches to the AUTO position. All unconnected video inputs  
should have their channel switch set to the BYPASS position.  
NOTES:  
VS5004 and VS5008 with one-monitor configuration: All channels with a switch set in the AUTO position will automatically sequence  
through the monitor. To view one specific channel continuously, set the corresponding switch to the MONITOR position. To remove a  
channel from the sequence, set the corresponding switch to the BYPASS position.  
VS5008 with two-monitor configuration:  
With all channel switches in the AUTO position, both monitors sequence simultaneously.  
Monitor 2 can be manually switched to any channel for continuous viewing by setting the desired channel’s switch to the MONITOR  
position. If multiple channels are set to MONITOR, only the lowest numbered channel will be displayed. This does not affect the  
sequencing for Monitor 1.  
To remove a channel from the sequence, set the corresponding switch to the BYPASS position.  
7. Connect the AC adapter to the 12 VAC input plug on the rear of the VS5004 or VS5008. Connect the transformer to a 120 VAC (VS5004 or  
VS5008) or 230 VAC (VS5004/220 or VS5008/220) power source. After power up, the switcher will begin sequencing.  
8. Using a screwdriver, adjust the DWELL interval control to the desired setting. This control adjusts the interval time from a minimum of  
1 second to a maximum of 70 seconds nominal. To increase the interval, turn the control clockwise. To decrease the interval, turn the  
control counterclockwise. The DWELL interval control is a precision 15-turn potentiometer. Each complete turn of this control will adjust the  
time interval by approximately 4 to 5 seconds.  
C808M-G (4/05)  
15  
 
MON 1  
COAXITRON®  
RECEIVER  
TO FIXED CAMERAS OR  
ADDITIONAL RECEIVERS  
BRIGHT  
CONTRAST  
12 VAC  
INPUT  
ALARM  
4
3
2
1
MON 1  
MON 2  
IN 1 2 3 4  
OUT 6  
COMMON 5  
VS5004 (REAR)  
LOOPING  
INPUT FROM OUTPUT FROM  
OUTPUT  
RECEIVER  
MONITOR  
J8  
J7  
J6  
COAXITRON® TRANSMITTER  
(REAR)  
Figure 13. VS5004 with Coaxitron Control  
COAXITRON  
RECEIVER  
UP TO EIGHT RECEIVERS  
CAMERAS  
MON 1  
ALARM  
INPUT  
COM  
12 VAC  
8
7
6
5
4
3
2
1
MON 2 MON X  
1
2
3
4
5
6
7
8
INPUT  
ALARM OUT  
VS5008 (REAR)  
LOOPING INPUT FROM OUTPUT TO  
OUTPUT  
RECEIVER  
MONITOR  
J8  
J7  
J6  
COAXITRON TRANSMITTER  
(REAR)  
NOTE: IN THIS CONFIGURATION, THE LOOPING OUTPUT (J8) IS UNTERMINATED.  
Figure 14. VS5008 with Coaxitron Control  
16  
C808M-G (4/05)  
 
   
Specifications  
VIDEO  
Inputs  
Terminating (75 ohms) or looping  
75 ohms  
Outputs  
Monitor 1  
Monitor 2  
VS5004  
VS5008  
Hi Z  
75 ohms  
Monitor X  
VS5008  
Coaxitron transmitter (nonamplified) output  
Unity  
Gain  
Dwell  
Adjustable from 1-70 seconds nominal  
Frequency  
Response  
Maximum  
Signal Level  
Tilt  
Flat within +/-1 dB to 10 MHz  
2 Vp-p  
Less than 2%  
Crosstalk  
Better than -40 dB at 5.5 MHz  
ELECTRICAL  
Power Requirements  
for Transformer  
1.5 VA (0.125 A) at 12 volts RMS +/-15%, 50/60 Hz from a dedicated, isolated 120 or 230 VAC power  
source. Wall transformer is provided with unit  
NOTE: These units are also capable of operating on 12 VDC for mobile applications.  
Connectors  
Alarm In  
BNC  
Normally open relay contact, 10 V at 1 mA  
Open collector  
Alarm Out  
GENERAL  
Construction  
Chassis  
Cover  
Steel, zinc plated  
Steel, black polyester powder coat  
Aluminum, black polyester powder coat with white silk screen  
Panel  
Environment  
32° to 120°F (0° to 49°C)  
Dimensions  
VS5004  
VS5008  
1.75" H x 5.63" W x 8.75" D inches (4.45 x 14.30 x 22.23 cm)  
1.75" H x 14.50" W x 8.50" D inches (4.45 x 36.83 x 21.59 cm)  
Weight  
VS5004  
VS5008  
2.5 lb (1.13 kg)  
7 lb (3.17 kg)  
Rating  
Meets Nema Type 1 standards  
C808M-G (4/05)  
17  
 
 
18  
C808M-G (4/05)  
 
PRODUCT WARRANTY AND RETURN INFORMATION  
WARRANTY  
Pelco will repair or replace, without charge, any merchandise proved defective in material or  
workmanship for a period of one year after the date of shipment.  
If a warranty repair is required, the Dealer must contact Pelco at (800) 289-9100 or  
(559) 292-1981 to obtain a Repair Authorization number (RA), and provide the following  
information:  
Exceptions to this warranty are as noted below:  
1. Model and serial number  
2. Date of shipment, P.O. number, Sales Order number, or Pelco invoice number  
3. Details of the defect or problem  
Five years on FT/FR8000 Series fiber optic products.  
Three years on Genex® Series products (multiplexers, server, and keyboard).  
If there is a dispute regarding the warranty of a product which does not fall under the  
warranty conditions stated above, please include a written explanation with the product  
when returned.  
Three years on Camclosure® and fixed camera models, except the CC3701H-2,  
CC3701H-2X, CC3751H-2, CC3651H-2X, MC3651H-2, and CC3651H-2X camera models,  
which have a five-year warranty.  
Method of return shipment shall be the same or equal to the method by which the item was  
received by Pelco.  
Two years on standard motorized or fixed focal length lenses.  
Two years on Legacy®, CM6700/CM6800/CM9700 Series matrix, and DF5/DF8 Series  
fixed dome products.  
RETURNS  
In order to expedite parts returned to the factory for repair or credit, please call the factory at  
(800) 289-9100 or (559) 292-1981 to obtain an authorization number (CA number if returned  
for credit, and RA number if returned for repair).  
Two years on Spectra®, Esprit®, ExSite, and PS20 Scanners, including when used in  
continuous motion applications.  
Two years on Esprit® and WW5700 Series window wiper (excluding wiper blades).  
All merchandise returned for credit may be subject to a 20% restocking and refurbishing  
charge.  
Eighteen months on DX Series digital video recorders, NVR300 Series network video  
recorders, and EnduraSeries distributed network-based video products.  
Goods returned for repair or credit should be clearly identified with the assigned CA or RA  
number and freight should be prepaid. Ship to the appropriate address below.  
One year (except video heads) on video cassette recorders (VCRs). Video heads will be  
covered for a period of six months.  
If you are located within the continental U.S., Alaska, Hawaii or Puerto Rico, send goods to:  
Six months on all pan and tilts, scanners or preset lenses used in continuous motion  
applications (that is, preset scan, tour and auto scan modes).  
Service Department  
Pelco  
3500 Pelco Way  
Clovis, CA 93612-5699  
Pelco will warrant all replacement parts and repairs for 90 days from the date of Pelco  
shipment. All goods requiring warranty repair shall be sent freight prepaid to Pelco, Clovis,  
California. Repairs made necessary by reason of misuse, alteration, normal wear, or accident  
are not covered under this warranty.  
If you are located outside the continental U.S., Alaska, Hawaii or Puerto Rico and are  
instructed to return goods to the USA, you may do one of the following:  
If the goods are to be sent by a COURIER SERVICE, send the goods to:  
Pelco assumes no risk and shall be subject to no liability for damages or loss resulting from  
the specific use or application made of the Products. Pelco’s liability for any claim, whether  
based on breach of contract, negligence, infringement of any rights of any party or product  
liability, relating to the Products shall not exceed the price paid by the Dealer to Pelco for  
such Products. In no event will Pelco be liable for any special, incidental or consequential  
damages (including loss of use, loss of profit and claims of third parties) however caused,  
whether by the negligence of Pelco or otherwise.  
Pelco  
3500 Pelco Way  
Clovis, CA 93612-5699 USA  
If the goods are to be sent by a FREIGHT FORWARDER, send the goods to:  
Pelco c/o Expeditors  
473 Eccles Avenue  
The above warranty provides the Dealer with specific legal rights. The Dealer may also have  
additional rights, which are subject to variation from state to state.  
South San Francisco, CA 94080 USA  
Phone: 650-737-1700  
Fax: 650-737-0933  
REVISION HISTORY  
Manual #  
C808M  
C808M-A  
C808M-B  
C808M-C  
C808M-D  
Date  
7/87  
2/91  
4/90  
9/92  
4/95  
Comments  
Original version.  
Updated format. Specification section rewritten. Rack-mount instruction section dropped.  
Incorporated addendum for dwell instructions.  
Optional accessories updated. Changes to dwell adjustment procedure.  
Added new Figure 5 drawing. Erroneous information on alarm operation (bridging) was deleted (ECO 94-222). Dwell internal timing changed from “3 to 70” to “1 to  
70” seconds (ECO 93-062). Specifications updated. Two-column format.  
C808M-E  
C808M-F  
C808M-G  
6/98  
12/99  
4/05  
Changed wiring color from blue to black in Figure 5. Changed manual format.  
Added information on use with Coaxitron transmitter. Changed to new manual format.  
Added VS5008 information from manual C809M-E.  
Pelco, the Pelco logo, Spectra, Genex, Esprit, Camclosure, and Legacy are registered trademarks of Pelco.  
© Copyright 2005, Pelco. All rights reserved.  
 
Worldwide Headquarters  
3500 Pelco Way  
Clovis, California 93612 USA  
USA & Canada  
Tel: 800/289-9100  
Fax: 800/289-9150  
International  
Tel: 1-559/292-1981  
Fax: 1-559/348-1120  
ISO9001  
United States Canada United Kingdom The Netherlands Singapore Spain Scandinavia France Middle East  
|
|
|
|
|
|
|
|
 

Perreaux Stereo Amplifier EP User Manual
Philips Cell Phone CD155 User Manual
Philips Indoor Furnishings P 5095 G User Manual
Philips Portable Speaker SPA5200 00 User Manual
Philips Work Light P 5722 C User Manual
Pinnacle Design TV Video Accessories TR4676FL User Manual
Pioneer Stereo Receiver VSX1017TXV User Manual
Planet Technology Switch FGSW 2620 User Manual
Pride Mobility Mobility Aid Jazzy Select 7 User Manual
ProForm Treadmill 1290 zlt User Manual