ONPIER9AT4IN8G5INSTRUCTIONS
8-Channel Solid-State Relay (SSR) Digital Output
Module
Safety Guidelines for Hazardous Voltages
If hazardous voltages are connected to the module, take the
following precautions. A hazardous voltage is a voltage greater
than 42.4 Vpk or 60 VDC to earth ground.
Caution Ensure that hazardous voltage wiring is
performed only by qualified personnel adhering to local
electrical standards.
Caution Do not mix hazardous voltage circuits and
human-accessible circuits on the same module.
Caution When module terminals are hazardous voltage
LIVE (>42.4Vpk/60 VDC), you must ensure that devices
and circuits connected to the module are properly
insulated from human contact. You must use the NI 9939
connector backshell kit to ensure that the terminals are
not accessible.
© National Instruments Corp.
3
NI 9485 Operating Instructions
Figure 1 shows the NI 9939 connector backshell.
Figure 1. NI 9939 Connector Backshell
Safety Guidelines for Hazardous Locations
The NI 9485 is suitable for use in Class I, Division 2, Groups A, B,
C, D, T4 hazardous locations; Class I, Zone 2, AEx nA II T4 and
Ex nA II T4 hazardous locations; and nonhazardous locations only.
Follow these guidelines if you are installing the NI 9485 in a
potentially explosive environment. Not following these guidelines
may result in serious injury or death.
NI 9485 Operating Instructions
4
ni.com
Caution Do not disconnect I/O-side wires or connectors
unless power has been switched off or the area is known
to be nonhazardous.
Caution Do not remove modules unless power has been
switched off or the area is known to be nonhazardous.
Caution Substitution of components may impair
suitability for Class I, Division 2.
Caution For Zone 2 applications, install the system in an
enclosure rated to at least IP 54 as defined by IEC 60529
and EN 60529.
Caution For Zone 2 applications, install a protection
device across the positive and negative terminals of the
external power supply (or supplies). The device must
prevent the external power supply from exceeding
80 V if there is a transient overvoltage condition.
© National Instruments Corp.
5
NI 9485 Operating Instructions
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as EEx nA II T4 equipment
under DEMKO Certificate No. 03 ATEX 0324020X. The
equipment is marked
II 3G and is suitable for use in
Zone 2 hazardous locations.
Wiring the NI 9485
The NI 9485 has a 16-terminal, detachable screw-terminal
connector that provides connections for eight solid-state relay
channels. Each channel has two interchangeable terminals, CHa
and CHb. Refer to Table 1 for the terminal assignments for each
channel.
NI 9485 Operating Instructions
6
ni.com
Table 1. Terminal Assignments
Module
Terminal
Signal
CH0a
CH0b
CH1a
CH1b
CH2a
CH2b
CH3a
CH3b
CH4a
CH4b
CH5a
CH5b
CH6a
CH6b
CH7a
CH7b
0
1
2
3
0
1
2
3
4
5
6
7
8
4
5
6
7
8
9
10
11
12
13
14
15
9
10
11
12
13
14
15
© National Instruments Corp.
7
NI 9485 Operating Instructions
Wiring for High-Vibration Applications
If an application is subject to high vibration, National Instruments
recommends that you either use ferrules to terminate wires to the
detachable screw-terminal connector or use the NI 9939 backshell
kit to protect the connections. Refer to Figure 2 for an illustration.
Ferrule
Figure 2. 16-Pin Detachable Screw Terminal with Ferrule
NI 9485 Operating Instructions
8
ni.com
Connecting Loads to the NI 9485
You can connect loads to the NI 9485. Connect the load to one of
the leads of the power source. Connect either the CHa or the CHb
terminal to the load and the other terminal to the other lead of the
AC or DC power source. Figure 3 shows a possible configuration
where the load is connected to the CHb terminal and the DC or AC
power source.
CHa
+
or
–
Load
AC
CHb
NI 9485
Figure 3. Connecting a Load to the NI 9485
© National Instruments Corp.
9
NI 9485 Operating Instructions
When you write an ON command to a channel, the SSR is closed
and the terminal that is connected to the load allows current to flow
or allows voltage to be applied to the load. When you write an OFF
command to a channel, the switch opens, disconnecting the circuit
so no current flows and no voltage is applied to the load.
Protecting Inductive Loads
When inductive loads are connected to the NI 9485 relay outputs,
a large counter-electromotive force may occur at switching time
because of the energy stored in the inductive load. These flyback
voltages can damage the relay outputs and/or the external power
supply.
Limit flyback voltages at your inductive load by installing one of
the following:
•
•
For DC loads—Install a flyback diode within 18 in. of the load.
For AC loads—Install a metal oxide varistor (MOV) rated for
30 Vrms or slightly higher.
NI 9485 Operating Instructions
10
ni.com
Figures 4 and 5 show examples of using an external flyback diode
to protect DC inductive loads and an MOV to protect AC inductive
loads, respectively.
Flyback Diode for
DC Inductive Loads
CHa
Inductive
Load
+
–
VDC
CHb
NI 9485
Figure 4. Contact Protection for DC Inductive Loads
© National Instruments Corp.
11
NI 9485 Operating Instructions
MOV for AC
Inductive Loads
CHa
CHb
Inductive
Load
VAC
NI 9485
Figure 5. Contact Protection for AC Inductive Loads
Sleep Mode
This module supports a low-power sleep mode. Support for sleep
mode at the system level depends on the chassis that the module is
plugged into. Refer to the chassis documentation for information
about support for sleep mode. You can enable sleep mode in
software. Refer to the driver software documentation for more
information.
NI 9485 Operating Instructions
12
ni.com
Typically, when a system is in sleep mode, you cannot
communicate with the modules. In sleep mode, the SSRs open to
prevent current from flowing through the load. Consequently, the
system consumes minimal power and may dissipate less heat than
it does in normal mode. Refer to the Specifications section for more
information about power consumption and thermal dissipation.
Specifications
The following specifications are typical for the range –40 to 70 °C
unless otherwise noted.
Output Characteristics
Number of channels..........................8 digital output channels
Relay type.........................................Normally open solid-state
relay (SSR)
Switching voltage .............................60 VDC max, 30 Vrms max
© National Instruments Corp.
13
NI 9485 Operating Instructions
Switching current, per channel1
All channels................................0.75 A max
Up to four channels ....................1.2 A max
Switching rate (90% duty cycle)1 .....1 operation per second
Relay open time................................0.5 ms typ
Relay close time................................9.0 ms typ
On resistance.....................................200 mΩ max
Off state leakage ...............................30 μA typ
MTBF ...............................................2,172,740 hours at 25 °C;
Bellcore Issue 6, Method 1,
Case 3, Limited Part Stress
Method
Note Contact NI for Bellcore MTBF specifications
at other temperatures or for MIL-HDBK-217F
specifications.
1
For additional specifications related to faster switching rates and/or higher currents
at lower temperatures, go to ni.com/info and enter the info code rd9485specs.
NI 9485 Operating Instructions
14
ni.com
Power Requirements
Power consumption from chassis
Active mode ...............................500 mW max
Sleep mode .................................5 mW max
Thermal dissipation (at 70 °C)
Active mode ...............................1.5 W max
Sleep mode .................................5 mW max
Physical Characteristics
If you need to clean the module, wipe it with a dry towel.
Screw-terminal wiring ......................12 to 24 AWG copper
conductor wire with 10 mm
(0.39 in.) of insulation
stripped from the end
Ferrules .............................................0.25 mm2 to 0.5 mm2
Torque for screw terminals ...............0.5 to 0.6 N · m
(4.4 to 5.3 lb · in.)
Weight...............................................Approx. 145 g (5.1 oz)
© National Instruments Corp.
15
NI 9485 Operating Instructions
Safety
Safety Voltages
Connect only voltages that are within these limits.
Channel a-to-Channel b....................60 VDC max, 30 Vrms max
Isolation
Channel-to-channel
Continuous...........................60 VDC
Withstand .............................1,390 Vrms, verified by a 5 s
dielectric withstand test
Channel-to-earth ground
Continuous...........................250 Vrms
,
Measurement Category II
Withstand .............................2,300 Vrms, verified by a 5 s
dielectric withstand test
Measurement Category II is for measurements performed on
circuits directly connected to the electrical distribution system.
This category refers to local-level electrical distribution, such as
that provided by a standard wall outlet (for example, 115 V for U.S.
or 230 V for Europe). Do not connect to signals or use for
measurements within Measurement Categories III or IV.
NI 9485 Operating Instructions
16
ni.com
Safety Standards
The NI 9485 is designed to meet the requirements of the following
standards of safety for electrical equipment for measurement,
control, and laboratory use:
•
•
IEC 61010-1, EN-61010-1
UL 61010-1, CSA 61010-1
Note For UL and other safety certifications, refer to the
product label or visit ni.com/certification, search
by module number or product line, and click the
appropriate link in the Certification column.
Hazardous Locations
U.S. (UL) ..........................................Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
AEx nA II T4
Canada (C-UL) .................................Class I, Division 2,
Groups A, B, C, D, T4;
Class I, Zone 2,
Ex nA II T4
Europe (DEMKO).............................EEx nA II T4
© National Instruments Corp.
17
NI 9485 Operating Instructions
Environmental
National Instruments C Series modules are intended for indoor use
only but may be used outdoors if installed in a suitable enclosure.
Refer to the installation instructions for the chassis you are using
for more information about meeting these specifications.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2) .....–40 to 70 °C
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2) .....–40 to 85 °C
Ingress protection..............................IP 40
Operating humidity
(IEC 60068-2-56)..............................10 to 90% RH,
noncondensing
Storage humidity
(IEC 60068-2-56)..............................5 to 95% RH,
noncondensing
Maximum altitude.............................2,000 m
Pollution Degree (IEC 60664)..........2
NI 9485 Operating Instructions
18
ni.com
Shock and Vibration
To meet these specifications, you must panel mount the system
and either use ferrules to terminate wires to the detachable
screw-terminal connector or use the NI 9939 backshell kit to
protect the connections.
Operating vibration
Random (IEC 60068-2-34).........5 grms, 10 to 500 Hz
Sinusoidal (IEC 60068-2-6) .......5 g, 10 to 500 Hz
Operating shock
(IEC 60068-2-27)..............................30 g, 11 ms half sine,
50 g, 3 ms half sine,
18 shocks at 6 orientations
Electromagnetic Compatibility
This product is designed to meet the requirements of the following
standards of EMC for electrical equipment for measurement,
control, and laboratory use:
•
•
•
EN 61326 EMC requirements; Industrial Immunity
EN 55011 Emissions; Group 1, Class A
CE, C-Tick, ICES, and FCC Part 15 Emissions; Class A
© National Instruments Corp.
19
NI 9485 Operating Instructions
Note For EMC compliance, operate this device
according to product documentation.
CE Compliance
This product meets the essential requirements of applicable
European Directives, as amended for CE marking, as follows:
•
•
73/23/EEC; Low-Voltage Directive (safety)
89/336/EEC; Electromagnetic Compatibility Directive (EMC)
Note Refer to the Declaration of Conformity (DoC) for
this product for any additional regulatory compliance
information. To obtain the DoC for this product, visit
ni.com/certification, search by module number
or product line, and click the appropriate link in the
Certification column.
Waste Electrical and Electronic Equipment (WEEE)
EU Customers At the end of their life cycle, all products
must be sent to a WEEE recycling center. For more
information about WEEE recycling centers and National
Instruments WEEE initiatives, visit ni.com/
environment/weee.htm.
NI 9485 Operating Instructions
20
ni.com
National Instruments Contact Information
The National Instruments Web site is your complete resource for
technical support. At ni.com/support you have access to
everything from troubleshooting and application development
self-help resources to email and phone assistance from
NI Application Engineers.
National Instruments corporate headquarters is located at
11500 North Mopac Expressway, Austin, Texas, 78759-3504.
National Instruments also has offices located around the world to
help address your support needs. For telephone support in the
United States, create your service request at ni.com/support
and follow the calling instructions or dial 512 795 8248. For
telephone support outside the United States, contact your local
branch office:
Australia 1800 300 800, Austria 43 662 457990-0,
Belgium 32 (0) 2 757 0020, Brazil 55 11 3262 3599,
Canada 800 433 3488, China 86 21 5050 9800,
Czech Republic 420 224 235 774, Denmark 45 45 76 26 00,
Finland 385 (0) 9 725 72511, France 33 (0) 1 48 14 24 24,
Germany 49 89 7413130, India 91 80 41190000,
Israel 972 3 6393737, Italy 39 02 413091, Japan 81 3 5472 2970,
© National Instruments Corp.
21
NI 9485 Operating Instructions
Korea 82 02 3451 3400, Lebanon 961 (0) 1 33 28 28,
Malaysia 1800 887710, Mexico 01 800 010 0793,
Netherlands 31 (0) 348 433 466, New Zealand 0800 553 322,
Norway 47 (0) 66 90 76 60, Poland 48 22 3390150,
Portugal 351 210 311 210, Russia 7 495 783 6851,
Singapore 1800 226 5886, Slovenia 386 3 425 42 00,
South Africa 27 0 11 805 8197, Spain 34 91 640 0085,
Sweden 46 (0) 8 587 895 00, Switzerland 41 56 2005151,
Taiwan 886 02 2377 2222, Thailand 662 278 6777,
Turkey 90 212 279 3031, United Kingdom 44 (0) 1635 523545
NI 9485 Operating Instructions
22
ni.com
National Instruments, NI, ni.com, and LabVIEW are trademarks of National Instruments Corporation. Refer to the
Terms of Use section on ni.com/legal for more information about National Instruments trademarks. Other
product and company names mentioned herein are trademarks or trade names of their respective companies.
For patents covering National Instruments products, refer to the appropriate location: Help»Patents in your software,
the patents.txt file on your CD, or ni.com/patents.
© 2006–2007 National Instruments Corp. All rights reserved.
374820C-01
Mar07
|