500kW Containerized
Diesel Generator Set
Model
Emissions
Standby Rating
Prime Rating
60 Hertz
EGC500DD
EPA Certified
500kW (625kVA)
450kW (562kVA)
(Shown with optional ISO trailer chassis)
Standard Features
Detroit Diesel Heavy Duty Diesel Engine
Full Load Acceptance
4-cycle design, turbocharged, aftercooled, direct injection
Polymide blade cooling fan
Accepts 100% of standby nameplate rating in one step, in compliance
with NFPA, para 5-13.2.6
Engine coolant heater
Generator Control Panel
Meets EPA emissions standards for mobile off-highway
InteligenTM vibration-isolated controller
Manual or remote engine start/stop
RS232/Modbus communication support
Safety shutdowns
Fuel System
800 gallon, single wall fuel tank
Fuel priming system
Externally mounted emergency stop switch
Fuel/water separators and drip pan
External fuel fill
Generator mainline circuit breaker, 100% rated, electronically
operated, UL listed
Electric fuel pump
30 micron Racor® fuel filter system
Specially Designed Container
20 ft. ISO container, sound-attenuated, foam-lined for extremely
quiet operation
Alternator
Brushless, 4-pole, synchronous, WYE connection
Solidly mounted battery rack and cooling system
Intregral vibration isolators
Class H insulation system conforms to NEMA MG1-22, BS5000,
CSA-C22-2, IEC-34-1 standards for temperature rise
Exterior polyurethane coating system provides long life in extreme
operating conditions
Drip-proof, self-venting, amortisseur windings
Epoxy impregnated windings with tropical insulation for increased
environmental protection and long life
Interior DC lights and timer switch
Critical grade silencer with heat blankets
Crankcase filteration system
Electronic Voltage Regulator
■
■
Electronic automatic voltage regulator provides precise regulation
Warranty
Engine-generator sets are covered by an express written, one-year
limited warranty
Separate three-phase excitation for fast recovery from block loads
and motor starting
EGC500DD Rev 2
500kW Containerized
Diesel Generator Set
Cooling System
Exhaust Manifold Type
Radiator Design
Dry
Standard horizontal discharge
Coolant Capacity - Engine
Coolant Capacity - Engine and Radiator
Water Pump Design/Type
Coolant Flow
11.6 gal. (44 L)
42 gal. (159 L)
Belt Driven, Centrifugal
79 gal/min (299 L)
11535 BTU/min (202.7 kW)
23 hp (17 kW)
Heat Rejection to Coolant
Fan Horsepower
Inteligen Digital Genset Controller
Thermostat
188.6 °F (87 °C)
Digital Controller Features
■
■
■
■
■
■
■
Large graphic back-lit LCD display 128x64 pixel resolution
Automatic and manual starting and stopping
Phase sequence supervision
Fuel System
Recommended Fuel
ASTM-D975-No.1 or No. 2-D
6.0 ft. (1.8 m)
Automatic shutdown/alarm function
Fuel Pump Maximum Lift
Filter Micron Size - 98% Efficiency
Total Fuel Flow
Input frequency 50-60 Hz
2
Parameters adjustable via PC or iG keyboard
186.1 gal./hr. (704.5 L/Hr.)
Predefined and user definable configurations available.
One configuration includes set of inputs/outputs and parameters
Fuel Consumption
Diesel Fuel @ % of Load
gal/hr
10.1
18.1
26.8
37.7
L/hr
38.2
■
■
■
■
■
■
■
■
■
■
■
Adjustable parameters for each configuration
6 LED indicators
25%
50%
68.5
Push buttons for simple control
4 programmable outputs (out of 20 functions selection)
4 binary configuration inputs
75%
101.4
142.7
100%
Lamp test during start up
Real time clock
Sealed membrane panel to IP65
180 x 113 mm front panel mounted case
Speed measurement from magnetic pickup
Lubrication System
Type
Full Pressure System
2 Spin-on, Full Flow
12.2 gal. (46.0 L)
Oil Filters
Oil pressure, Coolant temperature, Battery voltage and Fuel level
measurements
Oil Pan Capacity
Oil Capacity with Filters
Oil Pressure at Rated Speed
14.3 gal. (54.0 L)
■
■
■
■
■
■
■
■
■
■
Running Hour Meter
47 - 57 psi (324 - 393 kPa)
All Generator metering, kVAr, kW, V1-V3, Hz, I1-I3, kWh, kVAh
Generator under/over voltage alarm/shutdown
Generator under/over frequency alarm/shutdown
Over Current alarm/shutdown
Exhaust System
Exhaust Temperature at Rated kW
(Dry Exhaust)
Warm up and cooling functions
o
980 F (527 C)
o
Pre-lubrication function with timers
Adjustable crank attempts
Exhaust Flow at Rated kW
Silencer Type
4080 cfm (115.5 m3/min)
Critical
Data logging
Maximum Allowable Backpressure
Exhaust Outlet Size at hook-up
41.1 in/wc (10.2 kPa)
5.0 in. (127 mm)
Remote communications (RS232/Modbus)
EGC500DD Rev 2
500kW Containerized
Diesel Generator Set
Optional Features and Accessories
Generator Set
Container
Genset-to-Genset Paralleling Control System
ISO Trailer Chassis (20 ft.)
Base Load-to-Utility Paralleling Control System
Custom Outlet Panels
Double-wall Fuel Tank (600-gallon capacity)
Fluid Containment
Rotary Voltage Selector Switch
(High Wye/Low Wye Voltages)
Manual Fuel Valves (For Internal or External Fuel
Supply)
Auxiliary Oil Reservoir with Level Control (15-gallon)
Centrifugal Oil Filter System
Fueling Platform (Aluminum Step Construction
with Hand Rail)
Entrance Ladder (6-step, Aluminum Construction)
Interior Lights (AC Work lights)
Oil Pan Heater with Thermostat
Alternator Strip Heater
Custom Paint Colors (Artic White is Standard)
AC Battery Charger with Shore Power Receptacle
SPECIAL OPTIONS AVAILABLE UPON REQUEST
20 ft. Container
Weight and Dimensions
A
B
C
D
E
96 in.
(2,438 mm) (6,045 mm) (3,810 mm) (4,495 mm) (1,117 mm)
238 in.
150 in.
177 in.
44 in
Weight (Wet)*
22,500 lbs (10,206 kg)
29,980 lbs (13,599 kg)
Weight (Wet with trailer)*
* Weight is approximate. Wet weight does not include fuel.
Backfeed to a utility system can cause electrocution and/or property
damage. Do not connect to any building’s electrical system except
through an approved device. Specifications are subject to change
without notice.
Your MQ Power dealer is:
MQ POWER
POST OFFICE BOX 6254
CARSON, CA 90749
310-537-3700
•
800-421-1244
FAX: 310-632-2656
E-MAIL: [email protected]
© COPYRIGHT 2007, MQ POWER
Rev. 2 (10-07) EGC500DD
|