LUPS Series Uninterruptible Power Supplies LUPS
Page 1 of 2
550 - 1,500 VA Sine Wave UPS System
Operates incandescent, electronic ballast loads and HID lighting loads as well as critical loads requiring conditioned emergency power.
31.0”
16.6”
42.2 cm
78.7 cm
550 VA
223 lbs.
(101 kg)
1000 VA
223 lbs.
(101 kg)
1500 VA
262 lbs.
(119 kg)
Cabinet &
Electronics
Sealed Lead
Calcium Battery
39.0”
99.1 cm
10 Minute
Backup
44 lbs.
(19.9 kg) (26.8 kg)
59 lbs.
88 lbs.
(39.9 kg)
20 Minute
Backup
54 lbs.
(24.5 kg) (39.9 kg)
88 lbs.
108 lbs.
(49.0 kg)
90 Minute
Backup
121 lbs.
(55 kg)
203 lbs.
(92 kg)
288 lbs.
(131 kg)
How to Specify:
LUPS
Series
VA Rating
Voltage
Output Circuit
Breakers
OCB1 = (550 VA)
OCB3 = (1000, 1500 VA)
Configuration
Input Output
A = 120 120
B = 277 277
LUPS = LUPS Uninterruptible
Power Supply for
550 = 550 VA
1000 = 1,000 VA
1500 = 1,500 VA
Emergency Lighting
Applications
LUPSX = 10 Minute Backup
LUPSY = 20 Minute Backup
Overall Characteristics
Electronics
•
•
•
83% throughput efficiency
Input
Single conversion UPS, No transfer time
Operating temperature range of 32°F (0°C) to 104°F (40°C); 65°F (19°C) to
85°F (29°C) maximum for batteries
•
•
•
•
Input power factor self-correcting to > 0.95
Frequency 60.0 ±2.5 Hz
Input voltage tolerance +10% to -15%
Input harmonics < 8% THD
•
•
•
Standard 90 minutes of operating time
Full-time, isolating transformer
Variable Range Regulator allows wider range of acceptable input voltage
variation
Output
•
•
•
•
•
•
Solid-state PWM inverter with sine wave output
Output voltage regulation ±3% of nominal at full load
Output frequency 60 Hz ±0.2%
Load power factor capability is 0.6 lagging to unity
Overload rating: 125% for 10 minutes
Efficiency: 82% to 86%
•
ANSI/IEEE C62.41 category A & B surge voltage withstand capability
Housing
•
•
•
Free standing, NEMA 1 enclosure with locking doors
Acid resistant powder coat finish
Multiple conduit entries
Charger
•
•
•
Low voltage disconnect (LVD)
3 amp, 2-stage
Recharge time: UL 924 compliant
Standard Metering/Controls
•
•
•
•
•
•
AC input and output voltage
AC input breaker
AC output breaker
Battery disconnect device
Automatic battery monitor with alarm
LED indicating lamps for system on, system on battery, low battery warning
Options
FSU = Start-up Service
EXT = Extended Warranty (with FSU only)
Battery
Job Information
Type:
Maintenance free, sealed lead calcium battery has an estimated service life of
10 years, and operating temperature range of 65°F (19°C) to 85°F (30°C)*.
Job Name:
Cat. No.:
* Increases or decreases in temperature will affect battery performance. Optimum battery performance
realized at 77°F (25°C). Batteries are rated at 100% capacity at 77°F (25°C).
Lamp(s):
Notes: