MonitorModuleanalogue
• ADM loop technology with
System Sensor/200 protocol
• Monitored analogue input with
sensing range 4 – 20mA
• Connection of analogue sensors such
as gas detectors or flame detectors
• Current-limited sensor circuit
• Mounting by means of
Surface Mounting Box SMB500
Description
The Monitor Module M510E-4-20 is designed for the current-limited analogue input is monitored for wire
connection of analogue sensors with a 4 – 20mA breakage.
current interface.
With that, all sensors that are equipped with a corres- The Monitor Module M510E-4-20 is integrated into
ponding analogue output – for example, gas detectors an ADM loop with System Sensor/200 protocol and
or flame detectors – can be integrated into a fire detec- occupies one address in the number range of detector
tion system. By means of the module, sensors in 2- or addresses.
3-wire technology can be connected.
The two-coloured status LED is actuated by the fire
detection control panel and indicates the activated con-
The sensor circuit is powered by connecting an exter- dition and fault condition of the sensor.
nal power supply to the module. The integrated current
limiter prevents overloading of the module if the power The module is designed for mounting in a Surface
supply for the sensor is short-circuited. In addition, the Mounting Box SMB500.
Specifications
Operating voltage
Supply through loop voltage
max. 700µA (normal communication)
12 – 28VDC
Current consumption on the loop
External power supply
Current consumption external power supply
typ. 10mA (24V, without sensor)
Current limiting, sensor supply (3-wire technology)
Current limiting, analogue input
500mA
25mA
Ambient temperature
Relative humidity
Dimensions L × W × H
Weight
-10°C to +60°C (no icing)
10 – 95% (no condensation)
121 × 107 × 32 (mm)
100g
Order number
249112
Order name
Monitor Module 1xAnalog In/SS M510E-4-20