LST Smoke Alarm HFM 153 27D User Manual

Manua
l
R
adi
o
C
al
l
P
oints  
HFM/153-27D, HM/152-27D  
• Manual call points for different  
applications  
• High range of radio transmission  
• 2 frequency bands (868MHz and  
fig. C  
434MHz)  
fig. B  
• Fault message when door is opened  
• Case according to EN 54-11/B  
• Communication with radio interface  
FUIF511-27D  
fig. A  
Description  
The red Manual Call Point HFM/153-27D (fig. A) and on a choice of several million codes, is created, which  
the blue Manual Call Point HM/152-27D with lettering allows the unambiguous identification of the detector.  
„HAUSALARM“ (fig. B) communicate with the RF Inter- Regular status messages, monitoring of the battery vol-  
face FUIF511-27D via a secured radio protocol. The tage and the long life of the included batteries ensure  
plastic case, which is designed in accordance with the high reliability of the system.  
EN 54-11/B, is provided with an integrated antenna and  
accommodates the 3.6V lithium battery.  
A built-in LED optically indicates the activated condition  
of the detector. The hinged door can be opened up to  
4 data channels in the frequency band 868MHz as well an angle of 180° and it is provided with a replaceable  
as 20 channels in the frequency band 434MHz are avai- pane of glass. If the detector has been activated, an  
lable for the bidirectional data transmission. The avai- integrated locking device prevents the closing of the  
lability of the channel is checked regularly. During the door. When the door is opened, the detector sends a  
learning phase of the detector, i.e., when the detector fault message to the radio interface.  
is registered at the radio interface, a unique key, based  
Specifications  
Operating voltage  
3.6V (lithium battery, battery life approx. 1.5 years)  
Ambient temperature  
Dimensions W × H × D  
Range of radio transmission (free air)  
Frequency band  
0°C to +60°C  
125 × 125 × 37 (mm)  
400m  
868MHz or 434MHz  
Building Safety. Building Security.  
A
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27  
Funk-HM_DBL_LST_EN_0804.PDF • PAGE 1  
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED  
 

KTI Networks Switch KGS 2401 User Manual
Land Pride Snow Blower RBT55 User Manual
Learning Resources Crib Toy LER 2984 User Manual
LG Electronics Computer Monitor 910B User Manual
Lincoln Oven Series 1100 User Manual
Linear Home Security System CCM 2 User Manual
Maytag Dryer Accessories SL 3 User Manual
Melissa Iron 741 043 User Manual
Mercedes Benz Barcode Reader CS1000 User Manual
Merco Savory Toaster RT 2VSE User Manual